Table 4 — ICVC Display Data (cont)
EXAMPLE 2 — MAINTSTAT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press ( will be highlighted).
3. Press .
NOTES:
1. Numbers in parenthesis below, indicate the equivalent CCN index for BEST++ programming or BACnet Translator use.
2. Off (0), Local (1), CCN (2), Reset (3)
3. Timeout (0), Ready (1), Recycle (2), Startup (3), Running (4), Demand (5), Ramping (6), Tripout (7), Override (8), Tripout (9), Ctl Test (10),
Lockout (11), Pumpdown (12), Prestart (13)
4. Normal (1), Alert (2), Alarm (3).
5. All variables with capital letter point names are available for CCN read operation. Those shown with (*) support write operations for all CCN
devices.
EXAMPLE 3 — VPF STAT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation. Those shown with (**) shall support write operations
for the ICVC only.
DESCRIPTION STATUS UNITS POINT
Control Mode NOTE 2 NOTE 2 MODE
Run Status NOTE 3 NOTE 3 STATUS
Start Inhibit Timer 0-15 min T_START
Occupied? 0/1 NO/YES OCC
System Alert/Alarm 1-3 NOTE 4 SYS_ALM
*Chiller Start/Stop 0/1 STOP/START CHIL_S_S
*Remote Start Contact 0/1 OPEN/CLOSE REMCON
Temperature Reset –30-30 DEG F T_RESET
*Control Point 10-120 DEG F LCW_STPT
Chilled Water Temp –40-245 DEG F CHW_TMP
*Active Demand Limit 40-100 % DEM_LIM
Percent Line Current 0-999 % LNAMPS_P
Percent Line Kilowatts 0-999 % LINEKW_P
Auto Demand Limit Input 4-20 mA AUTODEM
Auto Chilled Water Reset 4-20 mA AUTORES
Remote Reset Sensor –40-245 DEG F R_RESET
Total Compressor Starts 0-99999 c_starts
Starts in 12 Hours 0-8 STARTS
Compressor Ontime 0-500000.0 HOURS c_hrs
*Service Ontime 0-32767 HOURS S_HRS
Ice Build Contact 0-1 OPEN/CLOSE ICE_CON
Emergency Stop 0/1 ENABLE/EMSTOP EMSTOP
Alarm Relay 0/1 NORMAL/ALARM ALM
DESCRIPTION STATUS UNITS POINT
**Target VFD Speed 0-110 % VFD_OUT
Actual Guide Vane Pos 0-100 % GV_ACT
Diffuser Actuator 0-100 % DIFF_ACT
Condenser Refrig Temp –40-245 DEG F CRT
Calc Evap Sat Temp –40-245 DEG F ERT
Active Delta Tsat 0-200 ^F DTS_A
Surge Line Delta Tsat 0-200 ^F DTS_C
Chilled Water Delta T –40-245 ^F CHW_DT
Hot Gas Bypass Relay 0/1 OFF/ON HGBYPASS
Surge Prevention Active? 0/1 NO/YES SHG_ACT
Surge Line High Offset 0.1-3.0 SP_HIGH
Surge/HGBP Delta Tsmin 0.0-150.0 ^F DTsatmin
Surge/HGBP IGVmin 0.0-110.0 % GV_MIN
Surge/HGBP Delta Tsmax 0.0-150.0 ^F DTsatmax
Surge/HGBP IGVmax 0.0-110.0 % GV_MAX
Surge Line Shape Factor –1.000-0.000 shapefac
Surge Line Speed Factor 0.00-3.00 VFD_POW
Surge Delta % Amps 5-40 % surge_a
Surge Time Period 7-10 min surge_t
MENU
STATUS
MAINSTAT
SELECT
MENU
STATUS
VPF_STAT
SELECT