48/50PG20-28
Single Package Rooftop Units
with COMFORTLINK TMControls
and PURON® (R-410A) Refrigerant
Controls, Start-Up, Operation, Service and
Troubleshooting Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ............................... 2
GENERAL .................................................. 2
BASIC CONTROL USAGE ................................ 2-5
ComfortLink TM Control ..................................... 2
Scrolling Marquee ......................................... 3
Accessory Navigator TM Display ............................ 3
Operation .................................................. 3
System Pilot TM ............................................. 4
CCN Tables and Display ................................... 4
Conventions Used in this Manual .......................... 4
START-UP ............................................... 6-35
Unit Preparation ........................................... 6
Compressor Mounting ..................................... 6
Refrigerant Service Ports .................................. 6
Crankcase Heater(s) ....................................... 6
Corn pressor Rotation ...................................... 6
Internal Wiring ............................................. 6
Subcooler Heat Exchanger (SHX) .......................... 6
Evaporator Fan ............................................ 6
Condenser Fans and Motors ............................... 6
Retu m-Air Filters .......................................... 6
Outdoor-Air Inlet Screens .................................. 6
Gas Heat (48PC Only) ...................................... 6
Orifice Change (48PC Only) ................................ 7
Power Supply .............................................. 7
Air Baffles ................................................. 7
Accessory Installation ..................................... 7
CONTROLS QUICK START ............................. 35,36
Thermostat Control ....................................... 35
Space Temperature Sensor Control --
Direct Wired (%55 or T-56) .............................. 35
Space Temperature Sensor Control -- CCN (T-58) ......... 35
Space Temperature Sensor Control -- CCN Linkage ...... 35
Space Humidity Control -- Humidistat .................... 35
Space Humidity Control -- Thermidistat TM ................ 35
Space Humidity Control -- Relative Humidity Sensor ..... 35
CCN Communication ...................................... 35
Accessories .............................................. 35
Service Test .............................................. 35
Control Configuration Checklist .......................... 36
Programming Operating Schedules ....................... 36
SERVICE TEST ......................................... 36-38
THIRD PARTY CONTROL ............................... 38,39
Thermostat ............................................... 38
Humidistat ................................................ 38
Humidity Sensor .......................................... 38
Remote Occupancy ....................................... 38
Fire Shutdown ............................................ 38
Alarm Output ............................................. 38
Outdoor Enthalpy ......................................... 38
lAG Switch ................................................ 39
IAQ Sensor ............................................... 39
OAQ Sensor .............................................. 39
CONTROLS OPERATION ............................... 39-52
Display Configuration ..................................... 39
Modes .................................................... 39
Unit Configuration ........................................ 39
Occupancy Determination ................................ 40
Indoor Fan ................................................ 41
Cooling ................................................... 41
THERMOSTAT (ONTROL
Page
SPA(E SENSOR CONTROL
OUTDOOR FANS
Gas Heating (48PC Units) ................................ 42
THERMOSTAT CONTROL
SPA(E SENSOR ( ONTROL
SUPPLY AIR TEMPERATURE (SAT) SENSOR
Electric Heat (50PG Units) ................................ 44
THERMOSTAT CONTROL
SPA(E SENSOR ( ONTROL
SUPPLY AIR TEMPERATURE (SAT) SENSOR
Economizer .............................................. 44
THERMOSTAT CONTROL
SPA(E SENSOR ( ONTROL
ECONOMIZER ACTUATOR ( OMMUNICATIONS
E%_OC(UPIED FREE COOLING
POWER EXHAUST
Optional Humdi-MiZer Dehumidification System ......... 45
SETTING UP THE SYSTEM
REHEAT MODE SELECTION PROCESS
REHEAT MODE DIAGNOSTIC HELP
AIR BAFFLES
indoor Air Quality ........................................ 49
Temperature Compensated Start ......................... 51
Carrier Comfort Network@ (CCN) Configuration .......... 5;
Alarm Handling ........................................... 52
TROUBLESHOOTING .................................. 52-67
Complete Unit Stoppage ................................. 52
Restart Procedure ........................................ 54
Control Module Communication .......................... 54
Alarms and Alerts ........................................ 54
VIEWING AND CLEARING UNIT ALARMS
DIAGNOSTI( ALARM (ODES AND POSSIBLE (AUSES
Cooling Troubleshooting ................................. 57
Humidi-MiZer Troubleshooting ........................... 57
Economizer Troubleshooting ............................. 57
Heating Troubleshooting ................................. 60
Phase Loss Protection ................................... 60
Thermistor Troubleshooting .............................. 61
Transducer Troubleshooting ............................. 64
Forcing Inputs and Outputs .............................. 64
MAJOR SYSTEM COMPONENTS ...................... 67-84
General ................................................... 67
Main Base Board (MBB) .................................. 67
Economizer Control Board (ECB) ........................ 67
Integrated Gas Control (IGC) Board ...................... 67
Low Voltage Terminal Strip (TB2) ......................... 67
Scrolling Marquee Display ................................ 80
Accessory Navigator TM Display ........................... 80
Carrier Comfort Network@ Interface ...................... 8O
Subcooler Heat Exchanger ............................... 80
Field-Installed Accessories ............................... 82
SPA(E TEMPERATURE SENSOR (T-55)
SPA(E TEMPERATURE SENSOR (T-56)
SPACE TEMPERATURE SENSOR (T-58)
SPA(E TEMPERATURE SENSOR AVERAGING
ECONOMIZER
POWER EXHAUST
TWO-POSITION DAMPER
INDOOR AIR QUALITY
OUTDOOR AIR QUALITY
SMOKE DETE( TORS
FILTER STATUS
FAN STATUS
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No 04-53480028-01 Printed io U.SA Form 48/50PG-5T Pg 1 6-06 Replaces: 48/50PG-2T
Page view 0
1 2 3 4 5 6 ... 111 112

Summary of Contents

Page 1 - Troubleshooting Instructions

48/50PG20-28Single Package Rooftop Unitswith COMFORTLINK TMControlsand PURON® (R-410A) RefrigerantControls, Start-Up, Operation, Service andTroublesho

Page 2

Table 6 -- Fan Performance -- 48PGD24 -- Vertical Supply/Return UnitsAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)AIRFLOW 0.4 0.6(Cfm)5,5006,0006,5007,0

Page 3 - 1rlenu strllcture

APPENDIX A -- LOCAL DISPLAY AND CCN TABLES (cont)MODE -- CONFIGURATION (cont)ITEM I EXPANSIONCONFIGURATION (cont)AIR.Q Air Quality ConfigurationIA.CF

Page 4 - "1o o

ITEMTIME CLOCKTIMETiMEDATEMNTHDOMYEARDAYDSTSTR.MSTR.WSTR.DM.ADDSTP.MSTP.WSTP.DM.SUBSCH.LPER.xOCC.xUNC.xMON.xTUE.xWED,xTHU.xFRI.xSAT.xSUN.xHOL.x(repeat

Page 5 - Range {±)

ITEMOPERATING MODESMODESYSHVACOCCT.OVRLINKC.LOCH.LOCE.LOCCOOLCOOLOK.CLMS.TGOK.ECOK.MCC.LOCCA.LOCB.LOCC.LOAVL.CREQ.CACT.CCMP.ACMP.BCMP.CST, AST, BST, C

Page 6 - (1/8" NPT PLUG)

ITEMOPERATING MODES (cont)ECONEC,ENOCCIDFCOOLE.LOCEH.LOELLOFC.LOEN.LOEC.MXEC.MNAQ.DVAQ.MNAQ.OVOVR.PAQ.LOOAQ.LLP.OVEC.CPEC.APEC.MPE.CAL(Display TRIM--

Page 7

APPENDIX B -- CONTROL MODES WITHHUMIDI-MIZER TM SYSTEM AND ECONOMIZERThermostat input shown tbr cooling demand (versus tem-perature sensor and set poi

Page 9

Copyright 2006 Carrier CorporationManufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and

Page 10

Model Number:Serial Number:Date:Technician:CONTROL SET POINT AND CONFIGURATION LOGSo.rare Versions:MBB: CESR131320--ECB: CESR131249--MARQ: CESR131171-

Page 11

ITEMCONFiGURATiON (cont)COOL (cont)SATSA.PDSA.NDSAT,USAT,LSPTCLPDCLNDC.LAGCIR.ACS.AICS,A2A!,FNA2,FNA3,FNCIR.BCS,BIBI,FNB2,FNB3.FNCIR.CCS.C1Ct.FNC2.FNC

Page 12

MODE -- CONFIGURATION (cont)ITEM I EXPANSIONCONFIGURATION (cont)OFC (cont)3.OFF Fan Lev3 Off TemperatureHMZRREHTR.DECR.INCRH.FNRF.LVRF. ONRF. OFRA.LOR

Page 13

Table 7 -- Fan Performance -- 48PGE24 -- Vertical Supply/Return UnitsAVAILABLE EXTERNAL STATIC PRESSUREAIRFLOW 0.2(Cfm)5,5006,0006,5007,0007,5008,0008

Page 14

ITEMCONFIGURATION (cont)ECON (cont)FC.TMFC.LOPE,ENPE.1PE,2EN.SWE,TRVE,MXBE,MXME,MXTE,DBDEC,PEC,IEC,DEC.DTAIR.QIA,CFIA,FNII,CFII,FNAQ.MNEC,MNOVR.POA.CF

Page 15

ITEMCONFIGURATION (cont)TRIMSPT.CSPT.TSAT.CSAT.TRAT.CRAT.TCCNCCN.ACCN,BBAUDBRODB.TIMB,OATB.GSB,ACKSCH.OSCH.NHOL.GOV.TLOV.EXOV.SPMODE -- CONFIGURATION

Page 16

UNIT START-UP CHECKLISTMODEL NO.: SERIAL NO.:DATE: TECHNICIAN:I. PRE-START-U P:[] VERIFY THAT ALL PACKING MATERIALS HAVE BEEN"REMOVED FROM UNIT[]

Page 17

Table 8 -- Fan Performance -- 48PGF24 -- Vertical Supply/Return UnitsAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)AIRFLOW 0.2 0.4 0.6(Cfm)5,5006,0006,50

Page 18 - Bhp Rpm Bhp Rpm

Table 9 -- Fan Performance -- 48PGD28 -- Vertical Supply/Return UnitsAVAILABLE EXTERNAL STATIC PRESSUREAIRFLOW(Cfm)ABCD6,5007,0007,5008,0008,5009,0009

Page 19

Table 10 -- Fan Performance -- 48PGE28 -- Vertical Supply/Return UnitsAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)AIRFLOW 0.8(Cfm)ABC6,5007,0007,5008,0

Page 20

Table 11 -- Fan Performance -- 48PGF28 --Vertical Supply/Return UnitsAVAILABLE EXTERNAL STATIC PRESSUREAIRFLOW(Cfm)AB6,5007,0007,5008,0008,5009,0009,5

Page 21

AIRFLOW(Cfm)500055006000650070007500800085009000Rpm533571610650691732775817860Table 12 -- Fan Performance -- 50PG20 --Vertical Supply/Return UnitsAVAI

Page 22

Table 13- Fan Performance- 50PG24- Vertical Supply/Return UnitsAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)AIRFLOW 0.6(Cfm)5,5006,0006,5007,0007,5008,0

Page 23 - 1352 6.58

AIRFLOW(Cfm)6,5007,0007,5008,0008,5009,0009,50010,00010,50011,00011,50012,00012,500BCDTable 14 -- Fan Performance -- 50PG28 --Vertical Supply/Return U

Page 24 - 601 H 1276

AIRFLOW(Cfm)500055006000650070007500800085009000Table 15 -- Fan Performance -- 48PGD20 -- Horizontal Supply and Return UnitsRpm862937F10131089G 116612

Page 25

CONTENTS (cont)PageENTHALPY SENSORSRETURN/SUPPLY AIR TEMPERATURE SENSORSPA(E HUMIDITY SENSORELECTRIC HEATSERVICE ...

Page 26

AIRFLOW(Cfm)500055006000650070007500800085009000FGHTable 16 -- Fan Performance -- 48PGE20 -- Horizontal Supply and Return UnitsRpm87596210291106118412

Page 27

AIRFLOW(Cfm)500055006000650070007500800085009000Table 17 -- Fan Performance -- 48PGF20 -- Horizontal Supply and Return UnitsRpm875952F10291106G 1184H

Page 28

Table 18 -- Fan Performance -- 48PGD24 -- Horizontal Supply and Return UnitsAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)AIRFLOW 0.8(Cfm)FGH5,5006,0006,

Page 29

Table 19 -- Fan Performance -- 48PGE24 -- Horizontal Supply and Return UnitsAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)AIRFLOW 0.2(Cfm)5,5006,0006,500

Page 30

AIRFLOW(Cfm)5,5006,0006,5007,0007,5008,0008,5009,0009,50010,000Table 20 -- Fan Performance -- 48PGF24 -- Horizontal Supply and Return UnitsFGHRpm95210

Page 31

Table 21 -- Fan Performance -- 48PGD28 -- Horizontal Supply and Return UnitsAVAILABLE EXTERNAL STATIC PRESSUREAIRFLOW 0.2(Cfm)6,5007,0007,5008,0008,50

Page 32

AIRFLOW(Cfm)6,5007,0007,5008,0008,5009,0009,50010,00010,50011,OOO11,50012,00012,500EFGTable 22 -- Fan Performance -- 48PGE28 -- Horizontal Supply and

Page 33

Table 23 -- Fan Performance -- 48PGF28 -- Horizontal Supply and Return UnitsAVAILABLE EXTERNAL STATIC PRESSUREAIRFLOW 0.2(Cfm)6,5007,0007,5008,0008,50

Page 34 - TM (20, 24)

AIRFLOW(Cfm)500055006000650070007500800085009000Table 24 -- Fan Performance -- 50PG20 -- Horizontal Supply/Return UnitsRpm5756196637087538008478949410

Page 35

Table 25 -- Fan Performance -- 50PG24 -- Horizontal Supply/Return UnitsAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)AIRFLOW 0.6(Cfm)5,5006,0006,5007,000

Page 36 - TM system equipped units

Scrolling Marquee -- This device is the keypad imer-face used to access the control information, read sensor values,and test the unit. The Scrolling M

Page 37 - TIMECLOCK

Table 26 -- Fan Performance -- 50PG28 -- Horizontal Supply/Return UnitsAVAILABLE EXTERNAL STATIC PRESSURE (in. wg)AIRFLOW 0.2(Cfm)EFGH6,5007,0007,5008

Page 38

5OPG202428Table 28 -- Air Quantity Limits (50PG20-28 Units)Minimum Cfm500055006500COOLINGMaximum Cfm9,000I0,000I2,000ELECTRIC HEATHigh Heat (75 kW)Med

Page 39 - TM operation is included

Table 29 -- Evaporator Fan Motor Specifications -- 48PG20-28 Units (cont)UNIT48PGDRIVELowORIENTATIONVerticalMid-Low VerticalMid-High VerticalHigh Vert

Page 40 - TM controller: When OCCU

Table 30 -- Evaporator Fan Motor Specifications -- 50PG20-28 Units (cont)UNiT50PG2428DRIVELowORIENTATIONVerticalMid-Low VerticalMid-High VerticalHigh

Page 41

Table 31 -- Accessory/FlOP Static Pressure (in. wg)* -- 48/50PG20-28 UnitsCOMPONENT I 4,000Economizer 0.02Humidi-MiZer TM (20, 24)Humidi-MiZer (28)4,5

Page 42 - DMD.C+ fRO.C* C.LAG< (Z.ND

Table 34 -- Fan Rpm At Motor Pulley Settings* -- 50PG20-2850PG DRIVELow Range VerticalMid-Low Range VerticalMid-High Range Vertical20 and 24 High Rang

Page 43 - (HIDDEN)

Control Configuration Checklist- Refer to check-list CL- 1 for recording site specific unit control configurations.Programming Operating Schedules --

Page 44

DISPLAYMENUTIMECLOCKSCH.LTable 35 -- Setting an Occupied Time Schedule -- Weekdays Only for 7:30 to 22:30SUB-SUB KEYPAD ITEM DISPLAYMODE ENTRYPER.1[][

Page 45 - (Tempera

DISPLAY MENU/SUB-MENU/NAMESERVICE TESTTESTINDPECONE.CALPE1PE2ALRMCCHFANSIDFOFC1OFC2OFC3COOLCMRACMRBCMRCOROVHMZRRH1 .ARH1 .BRH1 CRH2.ARH2.BRH2CCRCRHVAR

Page 46 - TM System

IAQ Switch -- For units with the economizer option oraccessory and the ECB control board, the IAQ switch inputis provided on the field connection term

Page 47

System PilotTM Device -- The System Pilot (33PILOT-01) device is a component of Ca_cier's 3VTM system and servesas a user-interface and confimlra

Page 48

Shut Down on IDF Failure (IDF..F) This conli_rationapplies only ifa tan switch is installed and configured. A YESvalue wilt enable diagnostic Alert T4

Page 49 - (bnfigura

Indoor Fan -- The indoor thn is controlled by the indoortan relay output (Outputs--->FA?_i9--->IDF)on the MBB (mainbase board) control, wNch the

Page 50

Two methods are used to add and relnove stages of coolingfor units with more than one compressor. The first methodcauses the unit to operate around it

Page 51 - ITEM EXPANSION

Iftheindoortancontrolisconfiguredtocyclewiththeheat-ing demand((bnfiguration---_UNIr_OC.FN= No) thethn will stop after a conligured delay, (bnfigurati

Page 52

The control uses rvvomethods to add a stage of heating. Thefirst method will add a stage of heating when theHeating Demand (Operating Modes-+HEAT---aq

Page 53 - TM Alarm Codes

SPACESENSORCONTROL If theunitis in cooling,operatingunderspacetcnnperaturecontrol,theeconomizerisavailableforcooling,andnocompressorsareoperating,thee

Page 54 - TM Alarm Codes (cont)

Outdoorfan controlfor Humidi-MiZersTstemunitsincludesaMotonnaster(r9variable-speedcontrolofsomeoralloutdoorPans,dependingonunitmodelsize.TheMotonnaste

Page 55 - TM system, the

RH2.x)METERINGDEVICE_,-_,_ CLOSED VALVEOPEN VALVE[_ 3-WAY VALVEI}INDOOR ENTERINGAIRFig. 8 -- Hot Gas Reheat Mode (Reheat2) -- Humidi-MiZer TM SystemSp

Page 56

REHEATMODESELECTIONPROCESSSelectionofthereheatmodeforeachrefi-igerantcircuitisdeterminedfiomthespacehumidity(tiomRHsensoror switchinput)andthecircuitc

Page 57

\\\\\\_\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\8 PLACES ON 020 0__9 PLACES O_ 628_s Et_CHS_EFig. 10- Wind Baffle DimensionsIndoor Air Quality (IAQ) -- The (

Page 58 - TM Scrolling Marquee

RUNSTATUSAuto View ofRun Status(VIEW)¢SoftwareVersionNumbers(VERS)4,ComponentRun Hours{HRS)¢ComponentStarts(STRT)¢Control Modes(MODE)4,Cooling Status(

Page 59 - TM Service Analysis

---_ECMNor Configuration---_AIR.Q_OVR.P to provideeconomizer cooling.IA.CF = 3 (Control Minilnmn Position) When IA.CF =3, an external 4 to 20 mA somce

Page 60

Configuration--+AIR.Q--+IA.FN= 2 (Always) The indoortan performance for IA.FN = 2 is the sane as the perforlnancewhen IA.FN = 1 except the algorithm i

Page 61 - Seethetablebelow

Timed Override Hours (SCH.O_OV.EX) This displaysthe current number of hours left in an override. It is possible tocancel an override in pr%mess by wri

Page 62

Table 43 -- ComfortLink TM Alarm CodesALARM ORALERT DESCRIPTION ACTION TAKEN RESET PROBABLE CAUSENUMBER BY CONTROL METHODT051 Compressor A1 Safety Tri

Page 63 - "AUTO" position

ALARM ORALERTNUMBERT410T411T412T413T414T415T416ECB -- Economizer Control BoardIGC -- integrated Gas ControllerTable 43 -- ComfortLink TM Alarm Codes (

Page 64

andthereisnocurrent,verilyCSwiringandreplaceifnecessary.4. ReturntoNormalmodeandobsmTecompressoropera-tiontoverifythatcompressorcurrentsensorisworking

Page 65

returnair,orstuckopeneconomizerwhentheambienttempera-tureislow.Alert Code T140 (Loss of Charge) See Alert Tll0.Alert Code T141 (Low Refrigerant Pressu

Page 66

Alert Code T412 (W2 without Wl) This alert occurs inThermostat mode when W2 is energized and Wl is not. Veri_thermostat and thermostat wiring. When W2

Page 67

Table 44 -- Cooling Service AnalysisPROBLEMCompressor and Fan Will Not Start.Compressor Cycles (other thannormally satisfying thermostat).Compressor O

Page 68

Table 45 -- Humidi-MiZer TM Service AnalysisPROBLEMSubcooling Reheat ModeWill Not Activate.Hot Gas Reheat ModeWill Not Activate.No Dehumidification De

Page 69

START-UPUse the t'ollowing information and Start-Up Checklist onpage CL-1 to check out unit PRIOR to start-up.Unit Preparation -- Check that unit

Page 70 - = =i=,i: -'o_l::L_:

Table 46 -- Economizer Service AnalysisPROBLEMDamper Does Not Move.POSSIBLE CAUSEIndoor Fan is off.Economizer Operation is Limitedto Minimum Position,

Page 71

A redLEDisprovidedtoindicatethefunctionoftheboard.Seethetablebelow.LED STATUS FUNCTIONOn Continuously Relay contact closed (normal operation).Relay co

Page 72 - HEAT LAREL

Table 48 -- IGC Board LED Alarm CodesLED FLASH DESCRIPTION ACTION TAKEN BY RESET METHOD PROBABLE CAUSECODE CONTROLOn Normal Operation -- -- --Off Hard

Page 73 - __:RENL ORN OPV,QT_ YEL_

I I FLASH - INDOOR F/_ D_.AY I_ iMOC_FIED (HEA_NG)I 2 _ - OPENING OF UMffI 3 FLASHES - FLAME SENSORINDICATES _ Win-{CLOSED GAS VALVE4 _ - LIMFFSW_CHCY

Page 74

Fig. 13 -- SAT and OAT Thermistor MountingIfa more accurate check is required, unit must be shut do,a_and therlnistor relnoved and checked at a kalo,a

Page 75 - :'5

Table 50 -- Temperature (°F) vs ResistanceNoltage Drop Values forOAT, SAT, and SPT Thermistors (10K at 25 C Resistors)TEMP(F)-25-24-23-22-21-20-t9-t8-

Page 76 - FFFFrmDEBFm

Table 51 -- Temperature (°F) vs. Resistance/Voltage Drop Values for SCT Sensors (5K at 25 C Resistors)TEMP(F)-25-24-23-22-21-20-19-18-17-16-15-14-13-1

Page 77 - Table 54 -- ECB Connections

Table 52 -- Pressure (psig) vs. Voltage Drop Values for Suction Pressure TransducersPRESSURE VOLTAGE(psig) DROP (V)0 0.4652 0.4854 0.5056 0.5248 0.544

Page 80 - TM Display

Orifice Change (48PG Only) -- This unit is factoryassembled for heating operation using natural gas at aal eleva-tion lfom sea level to 2000 ft.Use ac

Page 81 - I/" (_.p/ BOX

.=!]I! I.,22II:= =i=,i: -'o_l::L_:i i, _EU)E0011,Io,m4,aEoU_000.3I?0

Page 83 - _'/ coo,_ w_._ \

_ ELECIRIC 1HEAT LARELOF_3OF_6Fig. 18 _ Power Schematic _ Units without Humidi-MiZe rT_ System72

Page 84 - -_ BLK BLK I

I!F _LNSEE 1LABEL_I OPTION DEPENDENTFIELDJ HACR TB1II_ _ K!>t2NEQUIP GNDCONNECT VINE TOAPPROPR[ATE UNIT VOLTAGE_ TNVNI_LN<__(__YEL(__BLUFrqqCSAI

Page 85 - Eql lip174el) t

J_zc8ooooo_b-zww02oo_ qEo_74

Page 86

IzwoiEt_1t.,Ni:'5E,I-I75

Page 87

RED LED - STATUS-\GREEN LED -LEN (LOCAL EQUIPMENT NETWORK)Z/STATUSYELLOW LED -CCN (CARRIER COMFORT NETWORK)INSTANCE JUMPER (SET TO 1)DISPLAY NAMEINPUT

Page 88

L-mRED LEDSTATUSGREEN LED-LEN(LOCAL EQUIPMENT NETWORK)Fig. 23 -- Economizer Control Board (ECB)Table 54 -- ECB ConnectionsDISPLAY NAME POINT DESCRIPTI

Page 89 - '1!

RED LED-STATUS0 UUUUUU.,:4LH33WPOO2A 1088-12Fig. 24 -- Integrated Gas Control (IGC) BoardTable 55 -- IGC ConnectionsTERMINAL LABEL POINT DESCRIPTION S

Page 90 - CHARGING CHART (ALL CIRCUITS)

17 I 14 I I IJ1O J11 RUN TEST J12(_ SEPARATION OF CIRCUITS TO EACH 24V TRANSFORMER MUST BE MAINTAINEDI...I T55IFANSTATOSl1 2 3 4 5 6 7 8 9 10 R

Page 91 - ,, o .,o

AIRFLOW(Cfm)500055006000650070007500800085009000Table 4 -- Fan Performance -- 48PGE20 -- Vertical Supply/Return Units0.2Rpm Bhp607 1,53652 1.90699 2.3

Page 92

Scrolling Marquee Display i This device is the key-pad interface used to access rooftop information, read sensorvalues, and test the unit. See Fig. 26

Page 93 - MODE -- RUN STATUS

CCN BUSBUiLDiNG SUPERVISORNETWORKOPTIONSREMOTE AUTODtAL jCCN SITE -- GATEWAY --NON HvAcCARRtER L_EQUIPMENTCOMFORTCONTROLLERJROOFTOPUNITROOFTOPUNIT_ RO

Page 94 - MODE- RUN STATUS (cont)

Field-Installed AccessoriesSPACE TEMPERATURE SENSOR (T-55) The T-55 spacetemperature sensor (part no. 33ZCT55SPT) is a field-installedaccessory. The s

Page 95 - MODE -- PRESSURES

4.50V3281CLEARANCE HOLES FOR(2) #8 MOUNTINGSCREWS ON CENTERLINE_ /jr,--,----,=!--_], U jNOTE: Dimensions are in inches.Fig. :30 -- Space Temperature S

Page 96 - MODE -- OUTPUTS

TB2-T55] RED] BLKTO MAINBASE BOARDRED REDI BLK BLKI I,I _I_ RED -_BLK Ir? USENSOR 1 SENSOR 27III REDBLK IrJ USENSOR3 SENSOR4SPACE TEMPERATURE AVERAGIN

Page 97

SERVICEBefore performing smTice or ruaintenance operations onunit, turn off main power switch to unit. Electrical shockcould cause personal injury.Pur

Page 98

NOTE:DoNOTUSEwaterinexcessof 130F,astheenzy-maticactivitywillbedestroyed.5. ThoroughlyapplyTotalineenviropanentaltyscumcoilcleanersolutiontoallcoilsur

Page 99

2. Coverareaintiontoftheunitservicepanelwithaterryclothshoptoweltoabsorblubricantspillsandpreventrun-oft;.Towelwilt alsoprotectdropclothfiomtearscause

Page 100 - MODE -- CONFIGURATION (cont)

Evaporator Fan Belt Tension Adjustment -- Toadjust belt tension:1. Turn offunit power.2. Slide out fan deck to service position as shown in Evapo-rato

Page 101 - CCN ONLY TABLES

5OOO45OO4OOO35OO3000o 25002000150010005OOLEAK INVACUUM TIGHTTOO WETTIGHTDRY SYSTEM0 1 2 3 4 5 6 7MINUTESFig. 41 -- Deep Vacuum GraphTRIPLE EVACUATION

Page 102 - MODE -- OPERATING MODES

AIRFLOW(Cfm)500055006000650070007500800085009000Rpm60765269974679484289194099OTable 5 -- Fan Performance --48PGF20 --Vertical Supply/Return UnitsAVAIL

Page 103 - MODE -- ALARMS

CHARGING CHART (ALL CIRCUITS)ALL OUTDOORFANS MUST BE OPERATINGIIIIIII IIIIIIIIIIIIB,I, IIIIIIIIIIII IIIIIIUb lllllllllllIIIIIII 134,t11111111111111111

Page 104 - TM SYSTEM AND ECONOMIZER

Main Burners (48PG Only) -- For all applications,main burners are ti_ctory set and should require no adjustment.MAIN BURNER REMOVAL1. Shut off (field-

Page 105

Filter Drier -- Replace whenever ref-igerant system is ex-posed to atmosphere. Only use factory specified liquid-linetilter driers with working pressu

Page 106

ITEMRUN STATUSVIEWHVACOCCSATALRMTIMEVERSMBBECBMARQHRSA1A2B1CICCHIDFOFC,1OFC,2OFC.3HT,1HT,2PE,1PE,2ALRMCRCRH2,ARH2.BSTRTA1A2B1CICCHIDFOFC,1OFC,2OFC.3HT

Page 107 - MODE -- CONFIGURATION

ITEMRUN STATUS (cont)COOL (cont)CIR.BCMP, BTG.BCS,B1RH2.BSST.BSSP.BSCT.BSCP.BCIR,CCMP, CTG.C1CS.C1RH2.CSST.CSSP.CSCT.CSCP.CHEATDMD.HAVL.HREQ.HIDFHT.1T

Page 108

ITEMSERVICE TESTTES TINDPECONE.CALPE.1PE.2ALRMCCHFANSIDFOFC.1OFC.2OFC.3COOLCMP.ACMP.BCMP.COF.OVHMZRRH1.ARH1.BRHI.CRH2.ARH2.BRH2.CCRCRHV.ARHV.BHEATHT,1

Page 109

DISPLAY MENU/SUB-MENU/NAMESETPOINTSOCSPUCSPOHSPUHSPGAPSTO.RRH. SPRH. DBRH. HBCA.LOCB.LOCC.LOHT.LOEH.LOEL.LOFC.LOLCSPHCSPSAT.USAT.LITEMINPUTSSTATY1Y2WI

Page 110

APPENDIX A -- LOCAL DISPLAY AND CCN TABLES (cont)MODE -- CONFIGURATIONITEMCONFIGURATIONDISPMETRLANGPROTPSWDTESTUNITS.DLYU.CTLT.CTLOC.FNIDF, FEC.ENFN,S

Page 111

ITEM ICONFIGURATION (cont)COOL (cont)CIR, BCS,B1BI .FNB2,FNB3,FNCIR.CCS,C1C1.FNC2,FNC3,FNSSTSST, OSST, ISST,2SST,3OFCOFC.30.MXPI.MXP2.MNP2.ON2.OFF2.MX

Page 112

APPENDIX A -- LOCAL DISPLAY AND CCN TABLES (cont)MODE -- CONFIGURATION (cont)ITEM I EXPANSIONCONFIGURATION (cont)HMZR HumJdimizer ConfigREHT Humidimiz