Table 5 — Fan Performance Data, 50HJ015 Units
Ф
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2 0.4 0.6 0.8
1.0
1.2 1.4
1.6
1.8
2.0
Rpm
Watts
Rpm Watts
Rpm Watts
Rpm Watts Rpm Watts
Rpm Watts
Rpm
Watts Rpm
Watts Rpm Watts
Rpm Watts
3750 732
684 848
835 949
977
1041
1119
1124
1270
1194 1430
1247 1599
1274 1767
~ — —
—
4000 764
799
876 968 974
1110
1065 1261
1146 1412
1221 1572
1284 1750 1331
1927
1357
2105
—
—
4250 797
933
904
1101
1001 1261
1089
1412 1170 1581
1244 1741
1312 1909 1369 2096
1413 2282
1440 2469
4500
831 1075
934
1252
1028
1430
1113 1581
1193 1750
1267
1918
1335
2096
1398
2282 1451 2478
1493 2673
4750 865 1226 965 1421 1056
1607
1139
1767
1217
1945
1290
2123
1358
2300 1422 2487
1480 2682
1531
2877
5000 900
1403
996 1599
1084 1803
1166 1980
1241
2149
1314 2336
1381 2522 1444 2709
1504
2904
—
—
5250 935
1590
1028 1794 1112
2007
1193 2202
1266 2371 1338
2567
1405 2762
1468
2948
— —
— —
5500
971
1794 1060
2007
1142
2229 1221
2433 1294 2629
1362 2806
1429
3011
— —
— —
— —
5750 1007
2016
1093
2238
1173
2469
1249
2682 1321 2895
6000 1044
2256
1126
2487
1205
2718
1277 2948
6250
1080 2513
1159
2753
1236
2993
LEGEND
Watts — Input Watts to Motor
NOTES:
1, Factory shipped fan speed is 1092 rpm. The range of the stand
ard evaporator-fan motor is 978 to 1285 rpm. Other rpms may
require a field-supplied drive.
2 Static pressure iosses (i.e., economizer, eiectric heater) must be
added to external static pressure before entering Fan Perfor
mance table.
3. To convert watts to bhp, use the following equation:
„Watts X motor efficiency
^ 746
Motor efficiency: Horsepower — Maximum Continuous Watts:
0 84 3 hp - 3065
4 Interpolation is permissible Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and casing
losses.
6. Extensive motor and drive testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the watts rating shown will not result in nui
sance tripping or premature motor failure Unit warranty will not
be affected.
Table 6A — Fan Performance Data — 50HJ024, 208/230-V and 575-V Units
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2 0.4
0.6
0.8 1.0
1.2 1.3 1.4 1.6
1.8
Rpm Watts
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm
Watts
Rpm Watts
Rpm
Watts
Rpm Watts
Rpm
Watts
6,000
702
1428
796
1723 884 2025 965
2339
1041 2669 1115 3018
1150
3201 1186 3385 1255
3771
1322 4175
6,500
747
1757
835
2073 919
2394
997
2725 1070
3069 1140 3429 1174 3617 1208 3805
1274
4198
1338
4609
7,000
792 2138
877 2476
957
2816
1031 3165
1102 3525 1169 3898 1201
4091
1233 4285 1296
4687
1358
5106
7,500
838 2571 918
2929 996 3290 1067
3658
1135 4035 1199
4422
1230
4622 1262 4822
1322
5235 1381 5662
8,000
885 3060
962 3440 1036 3822 1105
4209
1170 4604 1232 5008 1262 5180 1292 5422 1350
5847
1407 6286
8,500
932 3610 1005
4011 1077
4414
1143 4821 1206 5234 1266
5655
1295
5870
1324
6085 1380 6524
1435
6975
9,000
980 4223 1050
4647
1119
5071
1183
5498
1244
5930 1302
6369
1330
6592 1359 6816 1413 7270 1466 7735
9,500
1028 4904 1096
5350 1162 5796 1224
6243
1283 6695 1340
7152
1367 7384 1394 7616
— — —
—
10,000
1077
5655
1141
6123 1205 6591 1266
7059
1323 7531
LEGEND
Watts — Input Watts to Motor
NOTES-
1. Factory shipped fan speed is 1287 rpm Other rpms may require
a field-supplied drive.
2. Static pressure losses (i e., economizer, electric heater) must be
added to external static pressure before entering Fan Perfor
mance table
3. To convert watts to bhp, use the following equation:
„Watts X motor efficiency
^ 746
Motor efficiency: Horsepower — Maximum Continuous Watts:
0.87 71/2 hp-7915
4 Interpolation is permissible Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and casing
losses.
6. Extensive motor and drive testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the watts rating shown will not result in nui
sance tripping or premature motor failure. Unit warranty will not
be affected.
Table 6B — Fan Performance Data — 50HJ024, 460-V Units
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(Cfm)
0.2
0.4 0.6
0.8
1.0
1.2
1.3
1.4
1.6 1.8
Rpm
Watts Rpm Watts Rpm
Watts Rpm Watts
Rpm Watts Rpm Watts Rpm Watts Rpm
Watts
Rpm
Watts
Rpm
Watts
6,000
702 1428 796 1723
884 2025
965 2339
1041 2669 1115 3018
1150 3201 1186
3385
1255
3771
1322 4175
6,500
747 1757
835
2073
919
2394
997 2725
1070
3069 1140 3429 1174
3617 1208
3805 1274 4198
1338 4609
7,000 792
2138
877
2476
957 2816
1031
3165
1102 3525 1169 3898
1201 4091 1233
4285
1296
4687
1358 5106
7,500 838
2571 918 2929
996 3290 1067
3658 1135
4035
1199
4422
1230 4622
1262 4822 1322
5235
1381
5662
8,000 885
3060 962 3440
1036
3822 1105 4209 1170
4604 1232 5008 1262
5180
1292 5422 1350
5847
1407
6286
8,500
932 3610 1005 4011
1077
4414 1143 4821 1206
5234
1266
5655 1295
5870
1324 6085 1380
6524
1435 6975
9,000 980
4223 1050
4647 1119
5071
1183 5498
1244 5930 1302 6369
1330 6592
1359 6816 1413
7270
1466
7735
9,500 1028
4904
1096 5350
1162 5796 1224
6243 1283
6695
1340
7152 1367 7384 1394 7616
1447 8088
—
—
10,000
1077 5655
1141
6123
1205 6591
1266 7059 1323 7531 1378
8007 1404
8248 1431
8489
— — —
—
LEGEND
Watts — Input Watts to Motor
NOTES:
1 Factory shipped fan speed is 1287 rpm. Other rpms may require
a fieid-supplied drive.
2. Static pressure losses (i.e , economizer, electric heater) must be
added to external static pressure before entering Fan Perfor
mance table
3 To convert watts to bhp, use the following equation:
_ Watts X motor efficiency
746
Bhp
Motor efficiency: Horsepower — Maximum Continuous Watts
0 87 7V2 hp - 8640
4 Interpolation is permissible. Do not extrapolate.
5 Fan performance is based on wet coils, clean filters, and casing
losses.
6. Extensive motor and drive testing on these units ensures that
the fuli range of the motor can be utilized with confidence. Using
your fan motors up to the watts rating shown will not result in nui
sance tripping or premature motor faiiure. Unit warranty wili not
be affected.
11