6
INDOOR HIGH WALL UNITS
COOLING AND HEAT PUMP MODELS
NOTES:
1. Units are shipped with a full factory charge in the outdoor unit
based on 25 ft of refrigerant lines.
2. See Application Data section for long line lengths.
3. See matching outdoor unit for line lengths.
4. Capillary in outdoor unit.
UNIT 40BNB018 40BNB024 40BNB030 40BNB036 40BNE018 40BNE024 40BNE030 40BNE036
NOMINAL CAPACITY (Tons) 1.5 2.0 2.5 3.0 1.5 2.0 2.5 3.0
OPERATING WEIGHT (lb) 27.5 27.5 44.0 83.0 27.5 27.5 44.0 83.0
MOISTURE REMOVAL (pts/hr) 57885788
REFRIGERANT TYPE R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22
METERING DEVICE Capillary Capillary Capillary Capillary Capillary Capillary Capillary Capillary
CHARGE (lb) NOTE 1 3.1 3.8 4.7 8.0 3.1 3.8 4.7 8.0
INDOOR FAN (Direct Drive)
High — CFM 726 726 860 950 726 726 860 950
Med — CFM 565 565 730 770 565 565 730 770
Low — CFM 484 484 580 620 484 484 580 620
Motor Horsepower
1
/
10
1
/
8
1
/
8
1
/
6
1
/
10
1
/
8
1
/
8
1
/
6
REFRIGERANT LINES
Connection Type Flare Flare Flare Flare Flare Flare Flare Flare
Liquid Line (in.)
1
/
4
od
3
/
8
od
3
/
8
od
3
/
8
od
1
/
4
od
3
/
8
od
3
/
8
od
3
/
8
od
Vapor Line (in.)
1
/
2
od
5
/
8
od
5
/
8
od
3
/
4
od
1
/
2
od
5
/
8
od
5
/
8
od
3
/
4
od
Max Length, Lift & Drop (ft) 130/66/66 130/66/66 130/66/66 130/66/66 130/66/66 130/66/66 130/66/66 130/66/66
CONDENSATE DRAIN
Outside Dia (in.)
5
/
8
Dia
5
/
8
Dia
5
/
8
Dia
5
/
8
Dia
5
/
8
Dia
5
/
8
Dia
5
/
8
Dia
5
/
8
Dia
CONTROLS (Microprocessor)
Remote (Wireless I/R) Yes Yes Yes Yes Yes Yes Yes Yes
Freeze Protection Yes Yes Yes Yes Yes Yes Yes Yes
Defrost Method N/A N/A N/A N/A Demand Demand Demand Demand
Warm Start N/A N/A N/A N/A Yes Yes Yes Yes
Auto Changeover N/A N/A N/A N/A Yes Yes Yes Yes
Auto Restart Yes Yes Yes Yes Yes Yes Yes Yes
Diagnostics Yes Yes Yes Yes Yes Yes Yes Yes
Timer Mode (Start/Stop) 24 Hr 24 Hr 24 Hr 24 Hr 24 Hr 24 Hr 24 Hr 24 Hr
Test Mode Yes Yes Yes Yes Yes Yes Yes Yes
Dehumidification Mode Yes Yes Yes Yes Yes Yes Yes Yes
Fan Speeds H/M/L/Auto H/M/L/Auto H/M/L/Auto H/M/L/Auto H/M/L/Auto H/M/L/Auto H/M/L/Auto H/M/L/Auto
Control Voltage 24v 24v 24v 24v 24v 24v 24v 24v
System Voltage 208/230v 208/230v 208/230v 208/230v 208/230v 208/230v 208/230v 208/230v
AIR SWEEP
Horizontal Automatic Automatic Automatic Automatic Automatic Automatic Automatic Automatic
Vertical Manual Manual Manual Manual Manual Manual Manual Manual
FINISH White White White White White White White White
Physical data