INDOOR UNITS
OUTDOOR UNITS
LEGEND
NOTES:
1. If the indoor unit is powered from the outdoor unit, the outdoor
MOCP is for both sections.
2. All units are 208/230-1-60, voltage range is 187 min to 253 max.
UNIT SIZE MCA MOCP FLA
FAN MOTOR
AMPS
COMPRESSOR
AMPS
COMPRESSOR
LRA
40BNB
018 .5 15 .4 .4
N/A N/A
024 .5 15 .4 .4
030 .5 15 .4 .4
036 .8 15 .6 .6
40BNE
018 .5 15 .4 .4
024 .5 15 .4 .4
030 .5 15 .4 .4
036 .8 15 .6 .6
UNIT SIZE MCA MOCP FLA
FAN MOTOR
AMPS
COMPRESSOR
AMPS
COMPRESSOR
LRA
38BNB
018 11 15 8.2 0.8 7.4 48
024 19 30 15.0 1.4 13.6 63
030 21 35 16.8 1.8 15.0 73
036 25 40 20.2 1.8 18.4 95
38BNE
018 11 15 8.2 0.8 7.4 48
024 19 30 15.0 1.4 13.6 63
030 21 35 16.8 1.8 15.0 73
036 25 40 20.2 1.8 18.4 95
FLA Full Load Amps
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
Electrical data