7.2 - Power supply
The power supply must conform to the specication on the
chiller name plate. The supply voltage must be within the range
specied in the electrical data table.
For connections refer to the wiring diagrams.
WARNING: Operation of the chiller with an improper supply
voltage or excessive phase imbalance constitutes abuse which
will invalidate the Carrier warranty. If the phase imbalance
exceeds 2% for voltage, or 10% for current, contact your local
electricity supply source at once and ensure that the chiller is
not switched on until corrective measures have been taken.
30RA 200-240
652
718
783
365
404
442
193
258
324
39
39
8.5
PE
1
X
Y
C
C
Legend
1 Main disconnect switch
PE Earth connection
S Power supply cable section (see table “Recommended wire sections”).
X Disconnect switch position referred to the unit side
Y Control box position referred to the unit base
X (mm) Y (mm)
30RA 040 - 080 190 762
30RA 090 - 160 1415 762
30RA 200 - 240 1161 1107
NOTES:
The 30RA 040-240 units have only one power connection
point located at the main disconnect switch.
Before connecting electric power cables, it is imperative to
check the correct order of the 3 phases (L1 - L2 - L3).
Non-certied drawings. Refer to the certied drawings
supplied with the unit or available on request.
7.3 - Voltage phase imbalance (%)
100 x max. deviation from average voltage
Average voltage
Example:
On a 400 V - 3 ph - 50 Hz supply, the individual phase voltages
were measured to be:
AB = 406 V ; BC = 399 ; AC = 394 V
Average voltage = (406 + 399 + 394)/3 = 1199/3
= 399.7 say 400 V
Calculate the maximum deviation from the 400 V average:
(AB) = 406 - 400 = 6
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6
The maximum deviation from the average is 6 V. The greatest
percentage deviation is:100 x 6/400 = 1.5 %
This is less than the permissible 2% and is therefore acceptable.