Carrier 38QF User Manual

Browse online or download User Manual for Pumps Carrier 38QF. Carrier 38QF User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 18
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Number One
Air Conditioning
i\Mer
^Sb Division of
^ 0 Carrier Corporation
Carrier Parkway • Syracuse, N.Y. 13221
Heat Pump — Outdoor Section
CONTENTS
SAFETY CONSIDERATIONS
INSTALLATION
.............................
Page
.. 1
. 1-5
.. 1
Step 1 — Check Equipment and Jobsite
UNPACK UNIT
INSPECT EQUIPMENT
COMPLETE OR CONSIDER SYSTEM
REQUIREMENTS
Step 2 Mount Outdoor Heat Pump..................2
ON THE GROUND; MOUNT UNIT
ON A SOLID, LEVEL CONCRETE
PAD
ON THE ROOF: MOUNT UNIT ON
A LEVEL PLATFORM OR FRAME
Step 3 — Make Piping Connections
...................
3
REPLACE THE ACCURATER™ RE
FRIGERANT CONTROL PISTON IN
THE INDOOR COIL AS REQUIRED
CONNECT REFRIGERANT LINES
Step 4 — Make Electrical Connections ... 4
INSTALL A BRANCH CIRCUIT
DISCONNECT PER NEC
ROUTE LINE POWER LEADS
INTO UNIT
CONNECT GROUND LEAD AND
POWER WIRING
SEE INDOOR UNIT AND ELECTRIC
HEATER INSTALLATION, START-UP
AND SERVICE INSTRUCTIONS
CONNECT CONTROL POWER
WIRING (24 v)
START-UP
..............................................................
5-7
SERVICE................................................................. 7-14
MAINTENANCE.....................................................14-17
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning
equipment can be hazardous due to system pressure
and electrical components. Only trained and quali
fied service personnel should install, repair or serv
ice air conditioning equipment.
Untrained personnel can perform basic main
tenance functions of cleaning coils and cleaning
and replacing filters. All other operations should be
performed by trained service personnel. When
working on air conditioning equipment, observe
precautions in the literature, tags and labels attached
to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing oper
ations. Have fire extinguisher available for all braz
ing operations.
W.ARNING: Before performing scr\icc or
maintenance operations on sxstem. turn ofl
main powci switches to indoor unit and out
door unil. 1 urn ofl acccssoiA heater power
switch if applicable, riectrical shock could cause
personal itijur\.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT Move to final location. Lift
carton off, taking special care not to damage service
valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installing the 38QF.
Consult local building codes and National
Electrical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for air
flow clearance, wiring, refrigerant piping and serv
icing. Position so water or ice from roof cannot drop
directly on top of unit.
Make provisions for condensate drainage and
defrost water disposal whether unit is installed on
ground or roof. (Ensure unit basepan drainage holes
are not blocked.) See Step 2 for details. Roof in
stallation method for 38QF depends on building
construction and special requirements of local
codes. Be sure that roof can support unit weight.
It is recommended that 38QF units be used with
Carrier approved indoor sections; see Table 1.
System Refrigerant Control on 38QF units and
matching Carrier indoor units is a factory-installed
AccuRater™ device (bypass type). Bypass-type
AccuRater components are discussed in the service
section of this booklet. The AccuRater piston has a
refrigerant metering hole thru it and is field replace
able. Table 1 indicates indoor units for which the
required replacement piston is factory supplied with
specified 38QF outdoor unit. Replace piston as
described under AccuRater™ Servicing on page 13.
© Carrier Corporation 1983 Form 38QF-2SI
Page view 0
1 2 ... 18

Summary of Contents

Page 1 - Heat Pump — Outdoor Section

Number One Air Conditioning i\Mer^Sb Division of ^ 0 Carrier CorporationCarrier Parkway • Syracuse, N.Y. 13221Heat Pump — Outdoor SectionCONTENTSSAFE

Page 2 - CONCRETE MOUNTING PAD

'®° 70 74 78 82 86 90PRESSURE AT SUCTION SERVICE VALVE (PSIG)Fig 13 — 38QF036 with 28HQ.VQ042, 40AQ036 or 40QB/QH042 Cooling Cycle Charging

Page 3

66 68 70 72 74 76 78 80 82 84 86 88 PRESSURE AT SUCTION SERVICE VALVE (PSIG)Fig. 17 — 38QF048 with 40QB/QH048,060,062. 28HQ,VQ048 or060 Cooling Cycle

Page 4 - \<\ MORI I II \\

Compressor Removal — See Table? for compressor information and Fig. 21 for component location. Shut off power to unit. Remove refrigerant

Page 5

3. Start unit and run until suction pressure reaches 5 psig (see Caution).4. Shut unit off and frontseat suction valve.5. Vent remaining pressure t

Page 6

RETAINERrLARE NUTFLARECONNECTIONFig. 22 — AccuRater™ (Bypass Type) Components5. Slide piston out by inserting a small soft wire, with small

Page 7 - Table 6 — Service Data

COIL REPAIR — A flare-union coupling is used for E-coil repair. A kit is available, with instructions, thru Carrier Service Parts.COMPRESSOR c

Page 8

TROUBLESHOOTING CHART — COOLING CYCLEON

Page 9

TROUBLESHOOTING CHART — HEATING CYCLE

Page 10

For replacement items use Carrier Specified Parts.Manufacturer reserves the right to discontinue, or change at any time, specifications or designs wit

Page 11

Top Cover Removal — Top cover can be removed for wiring or servicing heat pump. Loosen decorative strip and slide down off screw

Page 12

ON THE ROOF; MOUNT UNIT ON A LEVEL PLATFORM OR FRAME: Proper precaution must be taken for support of unit in roof design. Elevate

Page 13

WARNING: If unclcrsi7ed. damaged or elliptiv.-all\-s!iapL'd uibing is used when making Compatible bitting, leaks ma\ result.If 1-1/8 in. tubi

Page 14 - CONNECTION

Table 4 — Electrical Data (60 Hz)OPERCOMPRBRANCH CIRCUITUNIT38QFV/PHVOLTAGE*FANFLAMin WireMax Wire Min GndMax Fuse or HACR Type Ckt Bkr Amps**MCAMaxMi

Page 15

THERMOSTAT SUBBASE HH93AZI73 OR HH93AZI7540AQ.40FQ OR 40QB FAN COIL 38QFCOOLING CONTROL KIT TERM INALTERMINAL BOARD BOARDCOOLING AND ONE-STAGE HEAT

Page 16

MOUNT OUTDOOR THERMOSTAT on control ring, to the left of the low-voltage control connection. See Fig. 1.Attach brackets with short shee

Page 17

To check and/or adjust charging during cooling season, use correct Cooling Cycle Charging Chart (Fig. 7, 9, 11, 13, 15, 17, 19) an

Page 18

320300280260240ina.lU>%o>□:UJtoo DO_l^ 22015 cn </)UJtc Q.200180160COOLING CYCLEmCFM-860:WET BULB TEMP AIR ENT INDOOR UNIT:75F62 f:67 F85

Comments to this Manuals

No comments