13
COIL CAPACITY MULTIPLIERS FOR FLOW RATES
NOTE: For capacities not at 1.50 gpm, multiply capacities from
Coil Cooling Capacities tables by the above multipliers.
COIL WATER PRESSURE DROP (ft of water)
GPM
NOZZLE ARRANGEMENT
FGHJK
Unit Size
12341234123412341234
0.6 0.91 0.90 0.85 0.82 0.88 0.85 0.82 0.79 0.85 0.84 0.80 0.77 0.83 0.82 0.78 0.76 0.84 0.82 0.78 0.76
0.8 0.94 0.92 0.90 0.88 0.91 0.89 0.86 0.84 0.90 0.88 0.85 0.83 0.87 0.85 0.83 0.81 0.89 0.86 0.83 0.80
1.0 0.96 0.95 0.94 0.93 0.95 0.93 0.92 0.91 0.94 0.93 0.91 0.90 0.93 0.92 0.90 0.89 0.93 0.92 0.90 0.88
1.2 0.98 0.97 0.97 0.97 0.97 0.97 0.96 0.96 0.97 0.96 0.96 0.95 0.96 0.96 0.95 0.94 0.96 0.96 0.95 0.94
1.4 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.98 0.99 0.99 0.99 0.98
1.5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
1.6 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.02
1.8 1.02 1.02 1.02 1.03 1.02 1.03 1.03 1.03 1.03 1.03 1.04 1.04 1.03 1.03 1.04 1.04 1.03 1.03 1.04 1.04
2.0 1.03 1.03 1.04 1.04 1.04 1.04 1.05 1.05 1.04 1.05 1.05 1.06 1.04 1.05 1.06 1.06 1.04 1.05 1.06 1.07
2.2 1.04 1.05 1.05 1.06 1.04 1.05 1.06 1.06 1.05 1.06 1.07 1.07 1.05 1.06 1.07 1.08 1.05 1.06 1.07 1.08
GPM
0.60 0.80 1.00 1.20 1.40 1.50 1.60 1.80 2.00 2.20
1.60 2.70 3.90 5.40 7.20 8.00 9.00 11.00 13.40 15.70