ELECTRIC HEATER ELECTRICAL DATA (36TE ONLY)
LEGEND
* Copper wire sizes based upon 60 C. Use latest NEC (National
Electrical Code) standards for wire lengths (allow 3% voltage drop)
and fuse sizes. Follow all local codes required. To obtain maximum wire
length, divide allowable amperage per ft by FLA.
HEATER
(V-Ph-Hz)
WATTS FLA FUSE AMPS
WIRE SIZE
(AWG)
ALLOWABLE
AMPERAGE/FT*
MINIMUM CFM
208-1-60
1000 4.81 15 14 332 32
1500 7.22 15 12 527 51
2000 9.63 15 10 834 67
2500 12.10 15 8 1328 82
3000 14.41 15 6 2061 108
240-1-60
1000 4.17 15 14 383 32
1500 6.25 15 12 609 51
2000 8.33 15 10 962 67
2500 10.40 15 8 1533 82
3000 12.50 15 6 2378 108
277-1-60
1000 3.62 15 14 442 32
1500 5.42 15 12 702 51
2000 7.23 15 10 1111 67
2500 9.03 15 8 1769 82
3000 10.85 15 6 2745 108
AWG American Wire Gage
FLA Full Load Amps
Electrical data