Master (control) units are factory supplied. On slave units,
however, the damper must be field connected to the mas-
ter unit by control tubing, plastic tees and connectors. A
typical master/slave arrangement is shown here.
A maximum of three units can be controlled by a single
thermostat. Care must be taken in locating slave units and
the wall thermostat. For proper control the control tubing
run must be limited to 25 ft and no more than four
90-degree bends should be made in the tubing.
ONE TEE AND
ONE CONNECTOR
TAPED TO EACH
SLAVE UNIT
BELLOWS
36RV SLAVE UNIT
36RV MASTER UNIT
WITH CHANGEOVER
VALVE
T
O COOLING POINT
TO WALL-MOUNTED
T
HERMOSTAT
TO HEATING PORT
TO CHANGEOVER VALVE
ON CHANGEOVER SYSTEM
T
O THERMOSTAT ON
NONCHANGEOVER
SYSTEM
TEE
DAMPER
CONNECTOR
BELLOWS
DAMPER
36RV SLAVE UNIT
BELLOWS
DAMPER
CONNECTOR
CHANGEOVER VALVE
MASTER/SLAVE CONTROL ARRANGEMENTS
Application data (cont)
a36-523