Required Compressor Modification for
38AH044-084 Optional Single-Circuit Units,
When Compressor A1 is Out —
To maintain unit
operation, compressor no.1 must be operable. If it is not opera-
ble, the following temporary modifications must be made to
keep the unit running:
1. Change the oil pressure switch connections from com-
pressor A1 to compressor A2.
2. Connect compressor A2 into the Time Guard circuit as
compressor A1 was originally.
3. Open compressor A1 circuit breaker.
NOTE: Make sure the crankcase heaters are energized when
compressors are off.
Preliminary Checks
1. Ensure that compressor service valves are backseated.
2. Verify that each compressor on units 38AH044-084,
124, and 134 floats freely on its mounting springs. Ver-
ify that each compressor on units 38AH094 and 104
floats freely on its rails.
3. Check that electric power supply agrees with unit
nameplate data.
4. Verify that compressor crankcase heaters are securely
in place.
5. Check that compressor crankcase heaters have been on
at least 24 hours.
6. Note that compressor oil level is visible in the sight
glass.
7. Recheck for leaks using same procedure as previously
outlined in Step 3 — Make Refrigerant Piping Con-
nections, page 15.
8. If any leaks are detected, evacuate and dehydrate as
previously outlined in Step 3 — Make Refrigerant Pip-
ing Connections, page 15.
Preliminary Oil Charge — Each compressor is facto-
ry charged with oil (see Tables 3A-4B). When oil is checked at
start-up, it may be necessary to add or remove oil to bring it
to the proper level. One recommended oil level adjustment
method is as follows:
ADD OIL Close suction shutoff valve and pump down
crankcase to 2 psig (14 kPa). (Low-pressure cutout must be
jumpered.) Wait a few minutes and repeat until pressure re-
mains steady at 2 psig (14 kPa). Remove oil fill plug above the
oil level sight glass, add oil through plug hole, and replace
plug. Run compressor for 20 minutes and check oil level.
FAN CONTACTORS
COMPRESSOR
CIRCUIT
BREAKERS
FAN CIRCUIT
BREAKER
TERMINAL
BLOCKS
TIMERS
TIME-DELAY
RELAY
OIL PRESSURE
SWITCHES
FUSE
HOLDERS
COMPRESSOR
CONTACTORS
TERMINAL
BLOCKS
TRANSFORMERS
Fig. 33 — Unit Control Box
NOTE: Fan rotation is clockwise when viewed from top of unit.
Fig. 34 — Condenser Fan Adjustment
IMPORTANT: For units with 2 compressors per refrig-
eration circuit, both compressors must be running to
adjust the oil level. Two oil level equalizer lines between
compressors distribute the oil to each compressor.