Installation Instructions
25HBB, 25HBC, 25HCD
Comfortt Seri es He at Pumps
with Puronr Refrigerant
1–1/2 To 5 Nominal Tons
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory–authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety–alert symbol
!
!
.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety–alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
!
WARNING
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding un-
necessary turns and bends.
4. Leave some slack between structure and unit to absorb vi-
bration.
5. When passing refrigerant tubes through the wall, seal open-
ing with RTV or other pliable silicon–based caulk (see Fig.
1).
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
tubing (see Fig. 1).
8. Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation (see Fig. 1).
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
INSULATION
SUCTION TUBE
LIQUID TUBE
OUTDOOR WALL INDOOR WALL
LIQUID TUBE
SUCTION TUBE
INSULATION
CAULK
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
JOIST
1” (25.4 mm)
MIN
THROUGH THE WALL
SUSPENSION
A07588
Fig. 1 -- Connecting Tubing Installation
When outdoor unit is connected to factory–approved indoor unit,
outdoor unit contains system refrigerant charge for operation with
AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field–supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section of
this instruction.
IMPORTANT: Maximum liquid–line size is 3/8–in. OD for all
residential applications including long line.
IMPORTANT: Always install the factory–supplied liquid–line
filter drier. Obtain replacement filter driers from your distributor or
branch.
Page view 0
1 2 3 4 5 6 ... 11 12

Summary of Contents

Page 1 - Installation Instructions

Installation Instructions25HBB, 25HBC, 25HCDComfortt Seri es He at Pumpswith Puronr Refrigerant1–1/2 To 5 Nominal TonsNOTE: Read the entire instructio

Page 2 - Check Defrost Thermostat

10Table 6 – Additional Subcooling Required – 15 SEER UnitsIndoor UnitSubcooling Delta from Rating Plate ValueOUTDOOR UNIT TONNAGE018 024 030 036 042 0

Page 3 - Make Piping Connections

11Table 7 – Required Liquid Line Temperatures _FLIQUID PRESSURE ATSERVICE VAL VE (PSIG)REQUIRED SUBCOOLING TEMPERATURE (° F)8 10 12 14 16 18251 76 74

Page 4 - Final Tubing Check

12FINAL CHECKSIMPORTANT: Before leaving job, be sure to do the following:1. Ensure that all wiring is routed away from tubing and sheetmetal edges to

Page 5 - Make Electrical Connections

2INSTALLATIONCUT HAZARDFailure to follow this caution may result in personal injury.Sheet metal parts may have sharp edges or burrs. Use care andwear

Page 6 - Start–Up

3Table 1 – Accessory UsageAccessoryREQUIRED FOR LOW–AMBIENTCOOLING APPLICATIONS(Below 55F / 12.8C)REQUIRED FORLONG LINE APPLICATIONS*REQUIRED FORSEA

Page 7 - Check Charge

4Table 2 – Refrigerant Connections and Recommended Liquidand Vapor Tube Diameters (In.)UNIT SIZELIQUID RATED VAPORConnectionDiameterTubeDiameterConnec

Page 8 - Heating Check Chart Procedure

5Make Electrical Connections!WARNINGELECTRICAL SHOCK HAZARDFailure to follow this warning could result in personal injury ordeath.Do not supply power

Page 9

6Final Wiring CheckIMPORTANT: Check factory wiring and field wire connectionsto ensure terminations are secured properly. Check wire routing toensure

Page 10 - 25HBB / 25HBC / 25HCD

7OUTDOOR FANRELAYY OUTPUT TO PRESSURESWITCHES AND CONTACTORTHERMOSTAT INPUTST1 - ENABLES DEFROST TIMER.MUST BE ENERGIZED FOR D

Page 11

8Units with Indoor PistonsUnits installed with indoor pistons require charging by thesuperheat method.The following procedure is valid when indoor air

Page 12 - CARE AND MAINTENANCE

9Table 5 – Additional Subcooling Required – 13 & 14 SEER UnitsIndoor UnitSubcooling Delta from Rating Plate ValueOutdoor Unit Tonnage018 024 030 0