Carrier INDUCTION AIR TERMINALS 36S User Manual Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 26
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
8
RIGHT SIDE VIEW
FRONT VIEW
A
D
E"3
F
3"
PLENUM
END PLUG
OPTIONAL AIR
VENT AVAILABLE
SEE CHART BELOW
FOR OPTIONAL
FITTINGS
OPTIONAL
LINT SCREEN
AVAILABLE
OPTIONAL
CONDENSATE PAN
WITH 11/16" DRAIN
ODF SWEAT
SUPPLY
RETURN
CONTROLS
SEE OPTIONS
BALANCING
DAMPER ADJUSTMENT
BELLOWS
AIR
CONNECTION
5/16" x 5/8" SLOTS IN
SUSPENSION MTG.
"Z" BARS
TYP (6) PLACES
3 1/2"
4 7/8"
4"
MIN
7 3/16"
4 1/2"
4 1/2"
3/4"
"61/11 6"61/11 6
11 3/8"
1"3 3/16"
10 5/16" 9 7/8"
13 7/16"
1 5/8"
21 9/16"
WALL
3 9/16"
4" O.D.
TRANSITION
FITTING
AVAILABLE
PRIMARY
AIR INLET
NOTES:
1. Thermostat is mounted on the right side only on on the wall.
2. Slave units are dimensionally the same, except without controls.
3. Non-changeover units do not have changeover valve.
4. A 4-in. minimum distance from the wall is required to obtain rated capacity.
An 8
1
/
2
in. minimum clearance is required for screen removal.
5. Condensate connection is mounted on the same side as the coil connection.
6. The unit is shipped with two Z brackets for mounting the unit and a hardware
kit including the following: 8 mounting screws, 8 tinnerman nuts, and 1 lint screen clip.
7. Shipping weight includes packaging.
SPECIFICATION
UNIT SIZE OPTIONAL FITTINGS
1234 CODE DESCRIPTION
Base Unit Dimension A (in.) 31 39 47 59 0 1/2” ODF Sweat Fitting
Drain Pan Dimension D (in.) 30 1/4 38 1/4 46 1/4 58 1/4 1 1/2” ODF Sweat Fitting with Vent
Coil Dimension E (in.) 24 1/8 32 40 52 2 1/2” ODM Flare Fitting
Hanger Dimension F (in.) 27 1/8 35 43 55 3 1/2” ODM Flare Fitting with Vent
Minimum Height from Floor (in.) 3333
Clearance from Discharge
Grille (sq in.)
81 108 135 175
Clearance from Recirculation
Grille (sq in.)
234 288 343 439
Shipping Weight (lb) 38 47 54 66
a36-518
Dimensions — 36RH