Carrier 60 Service Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
1-9
T--295
1.10 RELAY BOARD
1.10.1 Permanent Magnet Motors with 2 speed switching from series to parallel connection (Option 1)
JP2
D2 D6
CB 4
K2
CB 3
CB 2
K1
CB 1
CB 6
EF4EF3
EF6
D14
EF2
K5
EF1
D17
K4
EF5
CF3
D26 D30
CB 10
CB 8
CB 9
CF1
CB 5
K3
CB 7
K20K18
K22K24
CF4
K23K21
CF6 CF5
D38 D41
CF2
K11
K10
K12
D85
JP1
K13K19
JP3
JP4
K9
CB 11
CB 12
CB 13
JP6
K15K14
K17K16
JP5
D60
D66
D69
D51
D72
D57
D63
K8
K7
K6
D54
23
4
5
1
23
1
2
3
4
5 6
1
2
3
4
1
Figure 1-8 Relay Board (Option 1)
a. Relays
K1 Energizes evaporator fans 1 & 2 in high speed
or evaporator fans 1,2,3 & 4 in low speed.
K2 Energizes evaporator fans 3 & 4 in high speed
(not energized in low speed).
K3 Energizes evaporator fan 5 in high speed or
evaporator fans 5 & 6 in low speed.
K4 Energizes evaporator fan 6 in high speed (not
energized in low speed).
K5 Connects the negative side of evaporator fans
1 & 2 to ground in high speed. Connects the
negative side of evaporator fans 1 & 2 to
positive side of evaporator fans 3 & 4 in
low speed
K6 Connects the negative side of evaporator fan
5 to ground in high speed. Connects the
negative side of evaporator fan 5 to
positive side of evaporator fan 6 in
low speed
K 7 Energizes condenser fans 1 & 2 in high speed
or condenser fans 1,2,3 & 4 in low speed
K 8 Energizes condenser fans 3 & 4 in high speed
(not energized in low speed).
K 9 Energizes condenser fan 5 in high speed or
condenser fans 5 & 6 in low speed.
K10 Energizes condenser fan 6 in high speed
(not energized in low speed).
K11 Connects the negative side of condenser fans
1 & 2 to ground in high speed. Connects the
negative side of condenser fans 1 & 2 to
the positive side of condenser fans 3 & 4 in
low speed.
K12 Connects the negative side of condenser fan
5 to ground in high speed. Connects the
negative side of condenser fan 5 to
the positive side of condenser fan 6 in
low speed.
K13 Energizes the A/C clutch.
K14 Energizes unloader 1.
K15 Energizes unloader 2.
K16 Energizes the fresh air damper.
K17 Energizes the heat valve.
K18 Energizes the fault light output.
K19 Energizes the Boost Pump.
K20 Energizes the spare output.
K21 Is energized by the logic board to turn the
evaporator fans on high. The contacts of this
relay energize the coils of relays K1, K2,
K3 & K4.
K22 Is energized by the logic board to turn the
evaporator fans on low. The contacts of this
relay energize the coils of relays K1, K3,
K5 & K6.
K23 Is energized by the logic board to turn the
condenser fans on high. The contacts of this
relay energize the coils of relays K7, K8,
K9 & K10.
K24 Is energized by the logic board to turn the
condenser fans on low. The contacts of this
relay energize the coils of relays K7, K9,
K11 & K12.