T -295
4-14
Table 4-2. PressureT ransducer Voltage
“/hg Voltage Psig Voltage Psig Voltage
20” 0.369 100 1.446 215 2.573
10” 0.417 105 1.495 220 2.622
Psig Voltage 110 1.544 225 2.671
0 0.466 115 1.593 230 2.720
5 0.515 120 1.642 235 2.769
10 0.564 125 1.691 240 2.818
15 0.614 130 1.740 245 2.867
20 0.663 135 1.789 250 2.916
25 0.712 140 1.838 255 2.965
30 0.761 145 1.887 260 3.014
35 0.810 150 1.936 265 3.063
40 0.858 155 1.985 270 3.112
45 0.907 160 2.034 275 3.161
50 0.956 165 2.083 280 3.210
55 1.007 170 2.132 285 3.259
60 1.054 175 2.181 290 3.308
65 1.103 180 2.230 295 3.357
70 1.152 185 2.279 300 2.406
75 1.204 190 2.328 305 3.455
80 1.250 195 2.377 310 3.504
85 1.299 200 2.426 315 3.553
90 1.348 205 2.475 320 3.602
95 1.397 210 2.524 325 3.651
Table 4-3. Logic Board Configuration
Jumper
Description
A. High Reheat -- Selects fan speed
B. High Vent -- Selects fan speed
C. Dry Heat -- Selects re--heat configuration
D. Reheat/Cycle -- Selects clutch cycle
E. Transducers -- Selects transducer configu-
ration
F. Refrigerant -- Selects refrigerant
G. Unit Type -- Selects software configuration
H. Unit Type -- Selects software configuration
I. Factory -- Reserved for t he manufacturer.
J. Invert H
2
O -- Selects temperature switch
configuration
K. Voltage -- S elects unit voltage
L. Factory -- Reserved for t he manufacturer.
M. Psig/Bars -- Select s display configuration
N. C/F -- Selects display configuration
O. Loaded Start -- Selects start--up configura-
tion
P. PI Reheat -- Selects reheat algorithm