62-61107-02
7.2. Starting the unit – Road operation
1. Complete the PRETRIP inspection described in the previous section.
2. Place the RUN/STOP switch (O/I) (4.) to the RUN position (I)
3. Press the ROAD operation key (5.) (only if the unit has been previously used in standby mode).
4. Place either one or two compartments OFF/ON switches (6. or 8.) to ON (I) - For Mt° only
5. Then, the unit will :
- perform a complete diagnostic check on the microprocessor controller
- pre-heat for the required amount of time based on the engine temperature
- starts automatically
7.3. Starting the unit – Standby operation
1. Check that the unit is connected to a suitable electricity supply. (see section
7.3.1).
2. Place the RUN/STOP switch (4.) (O/I) to the RUN position (I)
3. Press the STANDBY operation key (12.).
4. Place either one or two compartments OFF/ON switches (6. or 8.) to ON (I) - For Mt° only
5. Then, the unit will begin to run on electric power.
7.3.1. Standby operation guidelines
For safe, reliable operation in Standby mode, it is important to consider the following guidelines :
a. NEVER plug the unit in to the power source with the main switch in the RUN position. The main
switch should always be in the STOP position when connecting the unit to the power source.
b. The fusing and extension cable used for Standby operation should conform to the following:
Standardized extension cable
H.07.RNF
Unit
Fuse
200/240/3/50Hz
220/256/3/60Hz
Fuse
350/415/3/50Hz
380/460/3/60Hz
230 volts 400 volts
Supra 450 16 A 10 A
Supra 550 16 A
4 x 4 mm
2
4 x 2.5 mm
2
Supra 750
Supra 750Mt°
Supra 850
Supra 850Mt°
23 A
13 A
4 x 6 mm
2
Supra 950 50 A 30 A 4 x 10 mm
2
4 x 6 mm
2
Supra 950Mt° 40 A 29 A 4 x 6 mm
2
c. The unit connection cable must be fitted with a ground connection. The cable must be connected to
earth.
d. On standby mode, the unit MUST BE CONNECTED to a high sensibility (30mA) differential
protection.
16