Table 7 -- Electrical Data
UNIT
38
AQ007
ARQ008
ARQ012
AQS016
FACTORY-INSTALLED
OPTION
NONE
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
CONVENIENCE OUTLET
NONE OR DISCONNECT
NONE
NONE
NOMINAL VOLTAGE VOLTAGE RANGE* COMPRESSOR FAN MOTORS POWER SUPPLY
(V-Ph-Hz) Min Max RLA LRA FLA MCA MOCP
208/230-3-60 187 253 18.9 146 5.1 28.7 45
460-3-60 414 506 9.5 73 2.6 14.5 20
575-3-60 517 633 7.6 58 1.2 10.7 15
39.0 60
208/230-3-60 187 254 29.0 190 1.5
43.8 60
19.8 30
460-3-60 418 506 15.0 95 0.7
21.9 30
400-3-50 360 440 15.0 95 0.7 19.8 30
45.0 60
208/230-3-60 187 254 34.0 225 1.5
50.0 70
23.0 30
460-3-60 418 506 17.0 114 0.7
25.0 30
18.0 25
575-3-60 523 632 14.0 80 0.7
20.0 25
400-3-50 360 440 17.2 125 0.7 22.9 30
208/230-3-60 187 253 63.6 266 4.3 87.5 125
460-3-60 414 528 29.3 120 2.3 40.7 60
575-3-60 518 660 23.8 96 1.8 33.0 50
230-3-50 198 264 47.9 200 3.5 66.9 100
400-3-50 342 457 29.3 115 3.5 43.0 60
LEGEND
FLA -- Full Load Amps
LRA -- Locked Rotor Amps
MCA -- Minimum Circuit Amps
MOCP -- Maximum Overcurrent Protection
NEC -- National Electrical Code (U.S.A. Standard)
RLA -- Rated Load Amps
*Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the
NEC, Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters' Laboratories (UL), Standard 1995.
3. The 575-v units are UL Canada-listed only.
4. Convenience outlet is available as factory-installed option only and
is 115-v, 1 ph, 60 Hz.
"[ DEFROSTr_T_V- _
q;ArCONTRO __ __
J
R C O Y W
R
-BL 4
- BL-- i i 14
- Y - #'LP/HP
-(_
I I LW._____DEFROSTHEAT _
i --COMPRESSOR
_- i i i_ i i -O-- ---It-- --HEAT/COOL J
_------4---BL-----_---- COMMON
L R _-- 24 VAC
LEGEND
DF -- Defrost Relay
LP/HP -- Low- or High-Pressure Switch (Optional)
PS -- Pressure Switch
RV -- Reversing Valve
SEN -- Outdoor Coil Temperature Sensor
TSTAT -- Thermostat
Line Voltage Factory Wiring
Low Voltage Factory Wiring
Low Voltage Field Wiring
COLOR CODE
BK Black
BL Blue
O Orange
R Red
W White
Y Yellow
NOTES:
1. All electrical work must be done in conformance with the
National Electrical Code (NFPA No. 70) and in conformance
with local codes and authorities having jurisdiction.
2, For use with copper conductors only.
Not suitable for use on systems exceeding 150 volts to ground,
Fig. 8 -- Wiring Diagram -- 38AQ007 208/230-3-60 Units