Carrier 38AQ Specifications Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
Compressor Lockout (CLO) Device-- Tile Com-
pressor lockout (CLO) device prevents the compressor fiom
stariing or running in a high pressure, loss-of-chmge or
fieezestat open situation. Reset the CLO device by setting the
thermostat to eliminate cooling demand and return it to the ong_
inal set point, ff the system shuts down again for the stone fault,
determine the possible cause before attempting to _eset the CLO
device.
Preliminary Oil Charge (38AQS) -- Tile compressor
is factory chm'ged with oil (see N_bles IA-ID). When oil is
checked at stml-up, it may be necess;uy to add or remove oil
to bring it to the proper level. Add oil only if necessary to
bring oil into view in sight glass. Use only Carrier-al)l)nn'ed
¢Xm_l)ressor oil. One recommended oil level adjustment
method is as follows:
ADD OIL--Close vapor service valve and pump down
crankcase to 2 psig. Wait a few minutes and repeat until pres-
sure remains steady at 2 psig. Remove oil fill plug above the
sight glass, add oil through plug hole, and replace plug. Run
compressor for 20 minutes and check oil level.
NOTE: Use only Carrier approved compressor oil. Approved
sources are;
Petroleum Specialties, Inc ..................... Cryol 150A
Texaco, Inc ............................... Capella WF32
Witco Chemical Co .......................... Suniso 3GS
Do not use oil that has been &'ained out, or oil that has been
exposed to atmosphere.
REMOVE OIL -- Pump down compressor to 2 psig. Loosen
the l/4-in, pipe plug at the compressor base and allow the oil to
seep out past the threads of the plug. RetigNen plug when level
is correct.
NOTE: The crankcase is slightly pressurized. Do not remove
the plug, or the entire oil charge will be lost.
Small amounts of oil can be removed through the oil pump
discharge connection while the compressor is running.
Start Unit -- Tile field disconnect is closed, the fan circuit
bleaker is closed, and the space thermostat is set above ambient
so that there is no demand for cooling. Only the crankcase
heater will be energized.
Next, close the compressor circuit breaker and then reset
space thermostat below ambient so that a call for cooling is
ensured.
NOTE: Do not use circuit bleaker to start and stop the com-
plessor except in an emergency.
After starting, there is a delay of at least 3 seconds before
compressor starts.
Adjust Refrigerant Charge -- Refer toChargingCharts
Fig. 19A-19C and Table 8. Do not exceed maximum refriger-
ant charge. Vmy refrigerant until the conditions of the chart are
met. Note that chmging charts are different from type normally
used. Chmls are based on chmging the units to the correct
subcooling for the various operating conditions. Accurate pres-
sure gage and temperature sensing device me required.
Connect the pressure gage to the service port on the liquid
line service valve. Mount the temperature sensing device on
the liquid line, close to the liquid line service valve and insulate
it so that outdoor ambient temperature does not affect the read-
ing. Indoor airflow must be within the normal operating range
of the unit. Operate unit a minimum of 15 minutes. Ensure
pressure and temperature readings have stabilized. Plot liquid
pressure and temperature on chm't and add or reduce charge to
meet curve. Adjust charge to conform with charging chmt,
using the liquid pressure and temperature to read chart.
If the sight glass is cloudy, check refrigerant charge again.
EiIsure all fims arc ol)erating. Also ensme maximum allowable
liquid lift has not been exceeded. If charged per chmt and if the
sight glass is still cloudy, check for a plugged filter drier or a
pmtially closed solenoid v¢flve. Replace or repair, as needed.
55-
_'5¢-
_45"
,<
6O
54
ku
> 49
¢
4_
38
32
27
21
16
E0,
10
O_DOOR FAN MUST BE OPE_TING
1_1111111111111111111111111111II
_o IIIIIIIIIIIII111111 I_
iiiiIlilllll ,lllJl Jtllilii
iiiiiL!oL o!L LL !iiiiiii
,lO ............. IlllllYiil I_
liilllill iiiiiliii iili ii
,oo lllllllH'lllll! 1
_illlll,rllltlill I
1 illllHIIIIllll! I
iliili illi,I/lllltiillli I
_111111 il_lL!o!ltllllll I
_111111111 illllllllllll IIII
III11111 illllllllllllllllllll
°o!illl!lli lll!llil!llll!ltll!ll
50 1_ 1_ 2_ 250 _0 _0
LIQUID PRE_URE AT LIQUID VALVE (PSIG)
LIQUID PRE_URE AT _QUID VALVE (kPa)
Fig, 19A- 38AQ007 Charging Chart
!
1
1
1
1
50
344
400
/
ADD CHARGE IF ABOVE CURVE /
/
/
/
/
/
/
/
/
/ REDUCE CHARGE IF BELOW CURVE
/
/
100 150 200 250 300 350 400
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
6;9 1034 1;79 1724 2089 2414
LIQUID PRESSURE AT LIQUID VALVE (Kilopascals)
70-
65*
0_60.
_J
>,55-
<
> 50-
45-
-_ 40-
'_ 35-
w
30-
25-
20"
5-
Fig. 19B- 38ARQ008,012 Charging Chart
t00 150 200 250 300 350 400 450
LIQUID PRESSURE AT LIQUID VALVE (PSIG)
7;0 _doo_so' _oo' roB' _oo_2ao' _soo'2z;o '3000
LIQUID PRESSURE AT LIQUID VALVE (kPa)
Fig. 19C -- 38AQS016 Charging Chart
2O
Page view 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 31 32

Comments to this Manuals

No comments