Carrier 48HG014-028 Specifications Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
16
START-UP
Use the following information and Start-Up Checklist on
page CL-1 to check out unit PRIOR to start-up.
Unit Preparation —
Check that unit has been installed in
accordance with these installation instructions and all applica-
ble codes.
Compressor Mounting —
Compressors are internally
spring mounted. Do not loosen or remove compressor hold-
down bolts.
Refrigerant Service Ports —
Each refrigerant sys-
tem has a total of 3 Schrader-type service gage ports per circuit.
One port is located on the suction line, one on the compressor
discharge line, and one on the liquid line. Be sure that caps on
the ports are tight.
Crankcase Heater(s)
Crankcase heaters are ener-
gized as long as there is power to the unit and the compressor is
not operating.
Compressor Rotation
It is important to be certain the compressors are rotating in
the proper direction. To determine whether or not compressors
are rotating in the proper direction perform the following
procedure:
1. Use the Service Test feature to energize a compressor (see
Controls and Troubleshooting literature for details).
2. If the compressor is rotating in the wrong direction, the
control will stop the compressor and an alarm will be
displayed.
NOTE: The evaporator fan is probably also rotating in the
wrong direction.
3. Turn off power to the unit and lock out the power.
4. Reverse any two of the incoming power leads.
5. Turn on power to the unit.
6. Repeat the procedure to energize each compressor and
check the evaporator fan rotation.
Internal Wiring —
Check all electrical connections in
unit control boxes; tighten as required.
Evaporator Fan —
Fan belt and variable pulleys are
factory-installed. Remove tape from the fan pulley. See
Tables 3-23 for Fan Performance Data. Be sure that fans rotate
in the proper direction. See Table 24 for air quantity limits. See
Table 25 and 26 for Evaporator Fan Motor Specifications. See
Table 27 for fan rpm at various motor pulley settings. To alter
fan performance, see Evaporator Fan Performance Adjustment
section on page 42.
Condenser-Fans and Motors —
Condenser fans and
motors are factory set. Refer to Condenser-Fan Adjustment
section (page 42) as required.
Return-Air Filters —
Check that correct filters are in-
stalled in filter tracks (see Table 1). Do not operate unit without
return-air filters.
Outdoor-Air Inlet Screens —
Outdoor-air inlet screens
must be in place before operating unit.
Gas Heat —
Verify gas pressures before turning on heat as
follows:
1. Turn off manual gas stop.
2. Connect pressure gage to supply gas pressure tap (see
Fig. 14).
3. Connect pressure gage to manifold pressure tap on gas
valve.
4. Turn on manual gas stop and set thermostat to HEAT
position. After the unit has run for several minutes, verify
that incoming pressure is 5.5 in. wg to 13.0 in. wg, and
that the manifold pressure is 2.95 in. wg. on horizontal
discharge applications and 3.00 in. wg on vertical dis-
charge applications. If manifold pressure must be adjust-
ed, refer to Gas Valve Adjustment section on page 43.
5. After unit has been in operation for 5 minutes, check tem-
perature rise across the heat exchangers. See unit infor-
mative plate for correct rise limits of the heat supplied.
Air quantities may need to be adjusted to bring the actual
rise to within the allowable limits.
IMPORTANT: Unit power must be on for 24 hours prior
to start-up. Otherwise, damage to compressor may
result.
Improper wiring will cause compressor stoppage and
alarm. Correct wiring by switching leads at contactor.
Page view 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 55 56

Comments to this Manuals

No comments