34
6. Connect power to the duct detector then perform a
sensor alarm test.
IRFLOW
HVAC DUCT
SAMPLING
TUBE
RETAINER
CLIP
OPTIC
PLATE
OPTIC
HOUSING
SENSOR
HOUSING
C07305
Fig. 47 -- Sensor Cle aning Diagram
Indicators
Normal State:
The smoke de tector operate s in the normal state in the
absence of any trouble conditions and when its sensing
chamber is free of smoke. In the norma l state, the Power
LED on both the sensor and the controller are on and all
other LEDs are off.
Alarm State:
The smoke detector enters the alarm state when the
amount of smoke particulate in the sensor’s sensing
chamber exceeds the alarm threshold value. See Table 11.
Upon entering the alarm state:
S The sensor’s Alarm LED and the controller’s Alarm
LED turn on.
S The contacts on the controller ’s two auxiliary relays
switch positions.
S The contacts on the controller ’s alarm initiation relay
close.
S The control ler’s remote alarm LED output is activated
(turned on).
S The controller’s high impedance multiple fan shutdown
control line is pulled to ground Trouble state.
The SuperDuct duct smoke detector enters the trouble
state under the following conditions:
S A sensor’s cover is removed and 20 minutes pass before
it is properly sec ured.
S A sensor’s environmental compensation limit is reached
(100% dirty).
S A wiring fault between a sensor and the controller is
detected.
An i nternal sensor fa ult is det ected upon entering the
trouble state:
S The conta cts on the controller’s supervisory relay
switch positions. See Fig. 48.
S If a sensor trouble, the sensor’s Trouble LED and the
controller’s Trouble LED turn on.
S If 100% dirty, the sensor’s Dirty LED turns on and the
controller’s Trouble LED flashes continuously.
S If a wiring fault between a sensor and the controller, the
controller’s Trouble LED turns on but not the sensor’s.
Alarm
Power
Test/reset
switch
Trouble
C07298
Fig. 48 -- Controller Assembly
NOTE: All troubles a re latche d by the duct smoke
detector. The trouble condition must be cleared and then
the duct smoke detector must be reset in order to restore it
to the normal state.
Resetting Alarm and Trouble Condition Trips
Manual reset is required to restore smoke detector systems
to Normal opera tion. For instal lations using two sensors,
the duc t smoke detect or does not differentiate whic h
sensor signals an alarm or trouble condition. Check each
sensor for Alarm or Trouble status as indicated by the
LEDs. Clear the condition that has generated the trip at
this sensor. Then reset the sensor by pressing and holding
the reset button, on the side, for 2 seconds. Verify that the
sensor’s Alarm and Trouble LEDs are now off. At the
controller, clea r its Alarm or Trouble state by pressing and
holding the manua l reset button, located on the front
cover, for 2 seconds. Verify that the controller’s Alarm
and Trouble LEDs are now off. Replace all panels.
Troubleshooting
Controller’s Trouble LED is On:
1. Check the Trouble LED on each sensor connected to
the controller. If a sensor’s Trouble LED is on, de-
termine the cause and make the necessary repairs.
2. Check the wiring between the sensor and the control-
ler. If wiring is loose or missing, repair or replace as
required.
Controller’s Trouble LED is Flashing:
1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean
that sensor assembly as describe d in the dete ctor
cleaning section.
Sensor’ s Trouble LED is On:
1. Check the sensor’s Dirty LED. If it is flashing, the
sensor is dirty and must be cleaned.
2. Check the sensor’s cover. If it is loose or missing, se-
cure the cover to the sensor housing.
3. Replace sensor assembly.
50TCQ