62-11175 COMFORTPRO SERVICE MANUAL
3-6
3.2 GENERATOR
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
No voltage • 35 Amp Breaker tripped • Determine reason and reset • A-5
• Generator Belt loose/broken • Tighten/replace • A-2
Low voltage • Generator belt loose/broken • Tighten/replace • A-2
(below 100 Volts)
• Engine air filter dirty • Clean/replace filter • A-3
• Engine fuel system problem • Change fuel filters • A-3
• Engine exhaust system problem • Clean/replace
• Engine speed low • Adjust • 3- 13
Very low voltage • Wiring to capacitor • Repair/replace
(4-10 Volts AC)
• Capacitor defective • Test and replace • 3- 13, 3- 14
Each symptom is followed by a probable cause and suggested solution. To isolate the
possible cause, proceed in a systematic manner to determine the faulty component. This
guide does not cover all possible situations that may occur under all conditions of operation.
WARNING
Disconnect the batteries from the
APU before performing any repairs.
Integrated APU Generator
Stand-Alone APU Generator