62-11175 COMFORTPRO SERVICE MANUAL
3-11
3.5 CCU FAN
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
CCU fan not working • Fuse on CCU Board • Check/replace • A-4
• Wiring defective • Repair/replace
• Capacitor defective • Test/replace
CCU fan only works on • Low speed resistor defective • Check/replace heating element • A-2
high speed
• Resistor wiring defective • Repair/replace • A-2
• CCU Board defective • Test/replace
3.6 CCU HEAT
SYMPTOM PROBABLE CAUSE SOLUTION REFERENCE
High Heat Mode does • Heat is not on (heat icon must be on) • Turn temperature setting up • 1- 6, 1- 9
not produce warm air
• Thermo fuse blown • Check/replace thermal fuse • A-2
• CCU Board defective • Replace
Low Heat Mode does • Heat is not on (heat icon must be on) • Turn temperature setting up • 1- 6, 1- 9
not produce warm air
• Thermo fuse blown • Check/replace thermal fuse • A-2
• CCU Board defective • Replace
Produces warm air and • Set point has been reached • Turn set point up • 1- 6, 1- 9
gradually stops
• High temperature cut out due to • Increase air flow/Increase return air
insufficient air flow
High temperature • High temperature cut out due to • Increase air flow, increase return air
sensor tripping insufficient air flow
• Temperature sensor wiring damaged • Repair/replace
• Temperature sensor defective • Verify sensor operation by using
Temperature vs. Resistance Chart • A-11
• Ducting blocked • Check and remove any blockage
Heat works OK, but • Driver Control Panel too close to duct • Remount away from ducts • 1- 1
short cycles
• Driver Control Panel temp sensor • Verify sensor operation by using
defective Temperature vs. Resistance Chart
Heat operates long or • Driver Control Panel temp sensor • Verify sensor operation by using
continuously defective Temperature vs. Resistance Chart • A-11
• Sleeper has an excessive heat loss • Cover windows, close sleeper curtains
• Sleeper has poor insulation • Insulate sleeper
• CCU air filter dirty • Clean/replace CCU filter • A-3
WARNING
Disconnect the batteries from the APU before
performing any repairs.
WARNING
Disconnect the batteries from the APU before
performing any repairs.