
TABLE VI-AIR DELIVERY (FtVMin) AT INDICATED EXTERNAL STATIC PRESSURE & VOLTAGE*
Model
Blower
Motor
Speed
Opera
ting
Voltage
Applica-
tiont
External Static Pressure—Inches wc
0.0 0.1
0.2
0.3 0.4 0.5 0.6
0.7
542E024 Low
208
Heating
880 835
790
740
690
630 565 470
Cooling
850 810
770
725
675 615 550 465
230
Heating
965 925
880
835
780 720 655
575
Cooling
940 900
855 810
755
700 635
560
High 208 Heating
1015 970
920 870
815 750 685 605
Cooling
985
940
890 840 785
730 665 585
230
Heating
1070
1030
985 940 885
830 765 680
Cooling
1040
1000
955 910 855 800
735
660
542E030
Low
208
Heating
995
965
930 890 845 785
705
590
Cooling
980
945 910 865 820 760
680
560
230 Heating
1070
1050 1025
995 960 915
840 730
Cooling
1055
1030 1005
970 930 880 800 680
High
208 Heating
1165
■ 1145
1125
1095 1065 1020 955 845
Cooling
1150
1130 1105 1075 1035
980
900
770
230 Heating
1260
1245 1225 1200 1165
1125
1065 970
Cooling
1245
1225
1200 1170
1135 1080 1005 875
542E036
Low
208 Heating
1280
1235
1185 1135
1080 1020 955 875
Cooling 1225
1185 1140
1095
1040 985 920 850
230 Heating
1485
1435 1380
1325 1265
1200
1115
1025
Cooling
1400
1350 1300
1250 1190
1125 1050 970
High 208 Heating 1685
1630
1575
1510
1440 1360 1275 1160
Cooling 1565
1510 1455
1395 1325 1250 1160
1045
230 Heating
1850
1785 1720
1650 1575
1490 1395 1280
Cooling
1670
1615 1560
1495 1425
1345 1250 1100
542E042 Low
208 Heating
1400 1360 1315
M265v
1:205: 1130 : 1015-
_
Cooling 1370
1330 1280
1230 : 1165 : ■ 1085 955
■ ■
230 Heating
1655
1610 1560 1505 1435 1360 1270
: 1140
Cooling
1615
1565 1510 1450 1380 1305 1205 1050
High 208 Heating
1895 1840 1780
1715 1645 1570 1480 1365
Cooling 1825
1770 1710 1645 1570 1490 1395 1270
230 Heating
2125 2065 2005
1935 1860
1775
1685 1570
Cooling 2030
1970 1905 1835 1760 1675 1575 1440
542E048
Low
208 Heating
1690 1635 1575
1510
1440
1360 1270 : 1140
Cooling 1650
1595 1535 1475 1405
1325
1,230
1100
230 Heating
1905 1855 1800
1740 1675 1600 1510
:1370
Cooling 1860
1810 1755
1690 1625 1545 1445 1290
High 208 Heating
2005
1955 1900 1845 1780 1705
1625 1510
Cooling
1955 1905
1850 1790 1725 1650 1560 1430
230
Heating 2270
2195 2120
2040 1955 1870 1765 1650
Cooling 2180
2110 2040 1960 1880
1785 1685 1570
460 Heating
2070 2000
1925 1845 1760 1665
1560
1425
Cooling 2000
1930 1855
1775 1690 1595 1490 1355
542E060
(Single-
Low 230 Heating
2250
2205 2160 2110 2050 1990
1915 1830
Cooling
2180 2135 2085
2030 1970 1900 1815 1700
Phase
Units)
High 230 Heating 2700
2625 2550 2465 2380 2285
2175 2055
Cooling 2550
2475 2395 2315 2220 2120 2005
1860
* Deduct field-supplied air filter pressure drop & heater loss (when used) to obtain available external static pressure for ducting,
t Heating airflow values are with a dry coil. Cooling airflow values are with a wet coil.
NOTE: Shaded portions of this table fall below 350ft^/min per 12,000 Btuh of rated cooling capacity. Indoor coil icing may ocur at airflows
below this point. Dashes are used in those areas of the table that fall beyond the capability of the indoor blower motor.
D. Unit Controls
All compressors have the following internal protection con
trols:
1. High-Pressure Relief VaZue—This valve opens when the
pressure differential between the low and high side
becomes excessive.
2. Compressor Ckterload—This internal overload interrupts
power to the compressor windings when either the cur
rent or internal temperature become excessive, and au
tomatically resets when the internal temperature drops
to a safe level. This overload may require up to 60
minutes (or longer) to reset; therefore if the internal
overload is suspected of being open, disconnect the
electrical power to the unit and check the circuit thru
the overload with an ohmmeter or continuity tester.
3. Low-Pressure Switch—This switch with automatic reset
interrupts the compressor control circuit when the
refrigerant high-side pressure becomes too low. It pro
tects the compressor from damage attributable to loss of
the refrigerant charge.
4. TimelTemperature Defrost System—The defrost control
system consists of a defrost timer, a defrost thermostat
switch, and a defrost relay. The system initiates defrost
cycle operation every 90 minutes if a coil icing condition
exists. See the defrost cycle sequence of operation in
Section VII.
5. Crankcase Heater—This device prevents overdilution of
compressor oil with refrigerant during shutdown
, periods, thereby extending the life of the compressor.
See the crankcase heater sequence of operation in Sec
tion VII.
6. Compressor Quick-Start Components—These components
are used with all single-phase units to improve com
pressor starting characteristics.
-11-
Comments to this Manuals