Figure 4—542D060 Dimensional Drawing
TABLE ll-ELECTRICAL DATA-MODEL 542E-SIZES 024 THRU 042
MODEL
542E
SIZE
J024 J030 J036 1 P036
B042 1 P042
SERIES
A
A
A
A
Unit Volts—Phase (60Hz)
208-230-1 208-230-1 208-230-1
208/230-3 230-1
208/230-3
Operating Voltage Range
197-253 197-253
197-253
187-253 207-253 187-253
Total Unit Amps
16.7 22.7 23.9
14.8
28.7 21.0
Max Branch Circuit Fuse Size (Amps)
30 45
45 25
50 40
Unit Ampacity for Wire Sizing
20.2 27.5
29.2 17.8 34.9
25.2
Minimum Wire Size (AWG)*
10 10
10
12 8 10
Maximum Wire Length (Ft)*
115 85
80 95 112
107
TABLE lll-ELECTRICAL DATA-MODELS 542E048, 542D060, & 542E060
MODEL
542E
542E 542D & 542E
SIZE
B048 P048
E048 060 P060
E060
SERIES
A A A
Unit Volts—Phase (60Hz)
230-1
208/230-3 460-3 230-1 208/230-3
460-3
Operating Voltage Range
207-253 187-253
414-506 207-253
187-253 414-506
Total Unit Amps
31.9
22.4
10.9
40.9
30.1 13.7
Max Branch Circuit Fuse Size (Amps)
60
45 20 60
50 25
Unit Ampacity for Wire Sizing
38.9 27.1 13.2 49.8 35.6
15.7
Minimum Wire Size (AWG)*
8
10
14 6
8 12
Maximum Wire Length (Ft)*
101 100 181 123
119 229
* Use only copper wire for field connections to unit. Wire size is based on 60 or 75°C copper conductor at 86°F (30°C) ambient tempera
ture and ampacity shown in table. If other than 60 or 75°C copper conductor is used, if ambient temperature is above 86°F, or if voltage
drop of wire exceeds 2% of unit rated voltage, determine wire size from ampacity shown and the National Electrical Code. Wire lengths
shown are measured one way along the wire path between unit and service panel for minimum voltage drop.
-3-