Table 20 Setting an Occupied Time Schedule
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
SCHD
ENTER
MON.O 00.00 MONDAY OCCUPIED TIME TIME IN MILITARY FORMAT (HH.MM)
ENTER
00.00 Scrolling stops
ENTER
00.00 Hours flash
07.00 Select 7 AM
ENTER
07.00 Change accepted, minutes flash
07.30 Select 30
ENTER
07.30 Change accepted
ESCAPE
MON.O 07.30 MONDAY OCCUPIED TIME Item/Value/Units scrolls again
Table 21 Operating Mode and Sub-Mode Directory
SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT
MODE
ENTER
MD01 ON/OFF FSM CONTROLLING CHILLER
MD02 ON/OFF WSM CONTROLLING CHILLER
MD03 ON/OFF MASTER/SLAVE CONTROL
MD04 ON/OFF LOW SOURCE PROTECTION
MD05 ON/OFF RAMP LOAD LIMITED
MD06 ON/OFF TIMED OVERRIDE IN EFFECT
MD07 ON/OFF LOW COOLER SUCTION TEMP A
MD08 ON/OFF LOW COOLER SUCTION TEMP B
MD09 ON/OFF SLOW CHANGE OVERRIDE
MD10 ON/OFF MINIMUM OFF TIME ACTIVE
MD11 ON/OFF LOW SUCTION SUPERHEAT A
MD12 ON/OFF LOW SUCTION SUPERHEAT B
MD13 ON/OFF DUAL SETPOINT
MD14 ON/OFF TEMPERATURE RESET
MD15 ON/OFF DEMAND LIMIT IN EFFECT
MD16 ON/OFF COOLER FREEZE PROTECTION
MD17 ON/OFF LO TMP COOL/HI TMP HEAT
MD18 ON/OFF HI TMP COOL/LO TMP HEAT
LEGEND
FSM Flotronic™ System Manager
WSM Water System Manager