GENUNIT (General Unit Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Control Mode 0 = Service Test
1 = OFF - local control
2 = OFF-CCN control
3 = OFF-timeclock
4 = Emergency stop
5 = ON-local control
6 = ON-CCN control
7 = ON-timeclock
MODE N
2 Occupied Yes/No OCC N
3 CCN Chiller Start/Stop CHIL S S
Y
4 Alarm State Normal ALM N
5 Active Demand Limit 0-100 % DEM LIM
Y
6 Percent Total Capacity 0-100 % CAP T
N
7 Requested Stage nn STAGE N
8 Load/Unload Factor snnn.n SMZ N
9 Active Setpoint snnn.n °F SP N
10 Control Point snnn.n °F CTRL PNT
Y
11 Entering Fluid Temp snnn.n °F EWT N
12 Leaving Fluid Temp snnn.n °F LWT N
13 Emergency Stop Enable/Emstop EMSTOP Y
14 Minutes Left for Start nn min MIN LEFT
N
CIRCA AN (Circuit A Analog values)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Circuit A Analog Values
2 Percent Total Capacity 0-100 % CAPA T
N
3 Percent Available Cap 0-100 % CAPA A
N
4 Discharge Pressure nnn.n PSI DP A
N
5 Suction Pressure nnn.n PSI SP A
N
6 Saturated Condensing Tmp snnn.n °F TMP SCTA
N
7 Saturated Suction Temp snnn.n °F TMP SSTA
N
8 Compressor Suction Temp snnn.n °F CTA TMP
N
9 Suction Superheat Temp snnn.n ^F SH A
N
10 EXV % Open 0-100.0 % EXV A
N
CIRCA DO (Circuit A Discrete Parameters)
DESCRIPTION STATUS UNITS POINT FORCEABLE
1 Circuit A Discretes
2 Fan A1 Relay ON/OFF FAN A1
N
3 Fan A2 Relay ON/OFF FAN A2
N
4 Oil Pressure Switch OPEN/CLOSE OILSW A
N
5 Compressor A1 Relay ON/OFF K A1 RLY
N
6 Compressor A2 Relay ON/OFF K A2 RLY
N
7 Compressor A3 Relay ON/OFF K A3 RLY
N
8 Compressor A4 Relay ON/OFF K A4 RLY
N
9 Unloader A1 Relay ON/OFF UNL A1
N
10 Unloader A2 Relay ON/OFF UNL A2
N
11 Hot Gas Bypass Relay ON/OFF HGAS N