Carrier 30GTR Specifications Page 63

  • Download
  • Add to my manuals
  • Print
  • Page
    / 84
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 62
Safety Devices Chillers contain many safety de-
vices and protection logic built into electronic control. Fol-
lowing is a brief summary of major safeties.
COMPRESSOR PROTECTION
Circuit Breaker One manual-reset, calibrated-trip mag-
netic circuit breaker for each compressor protects against over-
current. Do not bypass or increase size of a breaker to cor-
rect problems. Determine cause for trouble and correct before
resetting breaker. Circuit breaker must-trip amps (MTA) are
listed on individual circuit breakers, and on unit label
diagrams.
30GTN,R070 (50 Hz), 080-110 and 230B-315B Compres-
sor Protection Board (CPCS) The CPCS is used to con-
trol and protect compressors and crankcase heaters. Board
provides following features:
compressor contactor control
crankcase heater control
ground current protection
status communication to processor board
high-pressure protection
One large relay is located on CPCS board that controls
crankcase heater and compressor contactor. In addition, this
relay provides a set of contacts that the microprocessor moni-
tors to determine operating status of compressor. If the MBB
determines that compressor is not operating properly through
signal contacts, control locks compressor off.
The CPCS contains logic that can detect if current-to-
ground of any winding exceeds 2.5 amps; if so, compressor
shuts down.
A high-pressure switch with a trip pressure of
426 ± 7 psig (2936 ± 48 kPa) is mounted on each compres-
sor; switch setting is shown in Table 32. Switch is wired in
series with the CPCS. If switch opens, CPCS relay opens,
processor detects it through signal contacts, and compressor
locks off.Aloss-of-charge switch is also wired in series with
the high-pressure switch and CPCS.
If any of these switches opens during operation, the com-
pressor stops and the failure is detected by the MBB when
signal contacts open. If lead compressor in either circuit is
shut down by high-pressure switch, ground current protec-
tor, loss of charge switch, or oil pressure switch, all com-
pressors in the circuit are locked off.
30GTN,R130-210, 230A-315AAND 330A/B-420A/B A
control relay in conjunction with a ground fault module re-
places the function of the CPCS (above). To reset, press the
push-button switch near the Marquee display).
Table 32 Pressure Switch Settings,
psig (kPa)
SWITCH CUTOUT CUT-IN
High Pressure
426±7
(2936 ± 48)
320±20
(2205 ± 138)
Loss-of-Charge 7 (48.2) 22 (151.6)
LOW OIL PRESSURE PROTECTION Lead compressor
in each circuit is equipped with a switch to detect low oil
pressure. Switch is connected directly to processor board.
Switch is set to open at approximately 5 psig (35 kPa) and
to close at 9 psig (62 kPa) maximum. If switch opens when
compressor is running, CR or processor board stops all com-
pressors in circuit. During start-up, switch is bypassed for
2 minutes.
CRANKCASE HEATERS Each compressor has a
180-w crankcase heater to prevent absorption of liquid re-
frigerant by oil in crankcase when compressor is not run-
ning. Heater power source is auxiliary control power, inde-
pendent of main unit power. This assures compressor protection
even when main unit power disconnect switch is off.
IMPORTANT: Never open any switch or disconnect
that deenergizes crankcase heaters unless unit is being
serviced or is to be shut down for a prolonged period.
After a prolonged shutdown or service, energize crank-
case heaters for 24 hours before starting unit.
COOLER PROTECTION
Freeze Protection Cooler can be wrapped with heater cables
as shown in Fig. 32, which are wired through an ambient
temperature switch set at 36 F (2 C). Entire cooler is cov-
ered with closed-cell insulation applied over heater cables.
Heaters plus insulation protect cooler against low ambient
temperature freeze-up to F (−18 C).
IMPORTANT: If unit is installed in an area where am-
bient temperatures fall below 32 F (0° C), it is rec-
ommended that inhibited ethylene glycol or other suit-
able corrosion-inhibitive antifreeze solution be used in
chilled-liquid circuit.
Low Fluid Temperature Main Base Board is programmed
to shut chiller down if leaving fluid temperature drops below
34 F (1.1 C) for water or more than F (4.4° C) below
set point for brine units. The unit will shut down without a
pumpout. When fluid temperature rises to F (3.3° C ) above
leaving fluid set point, safety resets and chiller restarts. Re-
set is automatic as long as this is the first occurrence.
Loss of Fluid Flow Protection Main Base Board contains
internal logic that protects cooler against loss of cooler flow.
Entering and leaving fluid temperature sensors in cooler de-
tect a no-flow condition. Leaving sensor is located in
leaving fluid nozzle and entering sensor is located in first
cooler baffle space in close proximity to cooler tubes, as shown
in Fig. 20. When there is no cooler flow and the compressors
start, leaving fluid temperature does not change. However,
entering fluid temperature drops rapidly as refrigerant enters
cooler through EXV. Entering sensor detects this tempera-
ture drop and when entering temperature is F (1.6° C)
below leaving temperature, unit stops and is locked off.
Loss-of-Charge A pressure switch connected to high side
of each refrigerant circuit protects against total loss-of-
charge. Switch settings are listed in Table 32. If switch is
open, unit cannot start; if it opens during operation, unit locks
out and cannot restart until switch is closed. Low charge is
also monitored by the processor when an EXV is used. The
loss-of-charge switch is wired in series with the high-
pressure switch on each circuit’s lead compressor.
LEGEND
T—Thermistor
Fig. 32 Cooler Heater Cables
63
Page view 62
1 2 ... 58 59 60 61 62 63 64 65 66 67 68 ... 83 84

Comments to this Manuals

No comments