Carrier 30GTN015-035 Specifications Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
4
Step 4 Install Control Wiring
Wires between field-installed components and unit control
box must be enclosed in field-supplied conduit. Follow all local
codes and NEC (National Electrical Code U.S.A.). Wire size is
no. 16 AWG (American Wire Gage) (1.5 mm
2
) minimum. See
Fig. 4-12 for field wiring.
30GN,GT040-420 UNITS — Open the control box door.
Mount the field-supplied hot gas bypass relays A and B
(HGBPR-A, HGRPR-B) in the control box as shown on the
component arrangement label diagrams (Fig. 4). On 30GT
units, mount the field-supplied TDR (time-delay relay) as
shown on the component arrangement label on the unit.
30GN Units
— Using the wires provided in the harness, wire
the coil of HGBPR-A in series between J6-18 and J6-19 of the
4 IN/4 OUT module. Wire the coil of HGRPR-B in series be-
tween J6-21 and J6-22 of the 4 IN/4 OUT module. See Fig. 5.
Locate a black wire in the control harness with the label
HGRPR-A-COM, which originates at TRAN 5. Connect this
wire to the HGBPR-A terminal COM. Connect the wires,
HGBPR-A-NO and TB3-5 to the appropriate terminals per
Fig. 6. For hot gas bypass on circuit B, connect the appropriate
wires to HGBPR-A-COM, HGBPR-B-COM, HGBPR-A-NO,
and TB3-6. See Fig. 6.
Wire in the solenoid valves. Terminal blocks are provided
for easy field wiring. Wires external to the control box must be
run in field-supplied conduit. Use one of the predrilled holes in
the control box with a strain relief to run the wires to the sole-
noid valve from the box. Connect the hot gas bypass solenoid
A (HGBPS-A) between TB3-5 and TB3-8. Connect hot gas
bypass solenoid B (HGBPS-B) between TB3-6 and TB3-8.
See Fig. 6. Check all electrical connections for tightness and
proper location.
30GN HGBP Configuration — Once field-supplied relays are
mounted in the control box, the microprocessor must be con-
figured for the hot gas bypass option. to do this, enter the ser-
vice function using the LID (local interface device). Before
any changes can be made, move the LOCAL/ENABLE-
STOP-CCN switch to the STOP position. The service techni-
cian must also log on to the microprocessor. To do this, press
. The LID will display the word PASSWORD. Press
, and the LID will display LOGGEDON.
To change the configuration:
Press , and the LID will
display FLD CFG. Press until HGB 0 appears in the LID
display screen. Then press for the hot gas bypass
option. The display now reads HGB 1. Once the configuration
is complete, press , and the LID display will now
read LOGGEDON. Press until the LID display reads
LOG OFF. Press and the display will read EXIT LOG.
Using the test function, check the output of the relays. Press
and the display will read OUTPUTS. Press until
the display reads HGBRA 1. Press and the relay energiz-
es. Press and the relay deenergizes. When the check has
been performed, return the LOCAL/ENABLE-STOP-CCN
switch to the proper position. Close and secure the control box
door.
Be sure all power to the unit is off before proceeding. Tag
all disconnects.
When mounting relays, be careful to avoid damaging elec-
trical components and wiring in the mounting area.
Fig. 3 Schematic Piping; 30GTN015-035; 30HK040-060; 30HL050,060
LEGEND
TXV
Thermostatic Expansion Valve
Factory Piping
Field Tube (Copper)
Page view 3
1 2 3 4 5 6 7 8 9 ... 15 16

Comments to this Manuals

No comments