Johnson Controls Unitary Products 11
6. Maintain level tolerance to 1/2” across the entire width
and length of unit.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig
the unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit, MUST be
used across the top of the unit.
Units may be moved or lifted with a forklift. Slotted openings
in the base rails are provided for this purpose.
LENGTH OF FORKS MUST BE A MINIMUM OF 60
INCHES.
Excessive exposure of this furnace to contaminated
combustion air may result in equipment damage or
personal injury. Typical contaminates include: per-
manent wave solution, chlorinated waxes and clean-
ers, chlorine based swimming pool chemicals, water
softening chemicals, carbon tetrachloride, Halogen
type refrigerants, cleaning solvents (e.g. perchloro-
ethylene), printing inks, paint removers, varnishes,
hydrochloric acid, cements and glues, antistatic fab-
ric softeners for clothes dryers, masonry acid wash-
ing materials.
If a unit is to be installed on a roof curb other than a
UP roof curb, gasketing must be applied to all sur-
faces that come in contact with the unit underside.
Before lifting, make sure the unit weight is distrib-
uted equally on the rigging cables so it will lift evenly.
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rig-
ging cable damage with plywood or other suitable
material.
FIGURE 5 - UNIT 4 POINT LOAD
TABLE 3: UNIT WEIGHTS
Model
Shipping Weight
1
(lb.)
1.
54 kW heater.
Operating Weight
1
(lb.)
DL-06
1056 1041
DL-07
865 860
DL-08
880 875
DL-10
1131 1116
DL-12
1210 1195
DU-06
888 883
DU-07
895 890
DU-08
905 900
DU-10
1222 1207
DU-12
1212 1197
w/Econ.
85 84
w/ PE
150 148
w/Elec. Heat
49 49
w/Gas Heat
2
2.
8 Tube Heat Exchanger.
110 110
TABLE 4: 4 POINT LOAD WEIGHT
Model
Location (lbs.)
1
1.
Weights include largest gas heat option.
ABCD
DL-06
228 195 285 333
DL-07
192 143 224 301
DL-08
195 146 228 306
DL-10
245 209 305 357
DL-12
262 224 327 382
DU-06
197 147 230 309
DU-07
199 148 232 311
DU-08
201 150 234 315
DU-10
265 226 330 386
DU-12
263 224 327 383
D
A
CB
L E F T
F R O N T