VII Select net heating capacity of unit to meet
design condition requirements.
Enter the Heating Capacities and Efficiencies rating
table. The 48TFD006 unit will provide 59,200 Btuh
of heating.
Enter the 62AQ060 Heating rating table at 450 cfm.
At 70 F and 0° F find the heating value for the
Energy$Recycler to be 15.2 MBtuh.
The customer heat requirement is 60,000 Btuh.
Rooftop Heat Capacity 59,200 Btuh
Rooftop fan heat from Step II 4,884 Btuh
Energy$Recycler Heat Capacity 15,200 Btuh
add Energy$Recycler optional
supply fan heat if supplied 0 Btuh
Total Unit heat with Energy$Recycler 79,284 Btuh
The required heating capacity is 60,000 Btuh. The
total unit net heating capacity is 79,284 Btuh. The
48TFD006 unit is sufficient.
VIII Determine net cooling capacity.
Cooling capacities are gross capacities and do not in-
clude indoor (evaporator) or optional Energy$Recycler
supply fan heat.
Determine net cooling capacity using the following
formula:
Net Capacity = (Gross Capacity Rooftop Unit +
Energy$Recycler) – (Indoor [evaporator] fan motor
[IFM] Heat + Optional Energy$Recycler Supply Fan
Motor Heat)
Gross Total Cooling
Rooftop unit 58,400 Btuh
Energy$Recycler 13,000 Btuh
Total 71,400 Btuh
Less
IFM heat (from Step II) <4,884> Btuh
Opt. Energy$Recycler Supply
Fan Motor Heat none
Net Total Capacity 66,516 Btuh
Gross Sensible Cooling
Rooftop unit 51,400 Btuh
Energy$Recycler 10,090 Btuh
Total 61,490 Btuh
Less
IFM heat (from Step II) <4,884> Btuh
Opt. Energy$Recycler Supply
Fan Motor Heat none
Net Sensible Capacity 56,606 Btuh
IX Determine the operating watts of the rooftop
unit and Energy$Recycler unit.
Cooling with Energy$Recycler in operation:
a) Rooftop unit:
Using the 48TF006 cooling capacity table and the
calculations described in Step VI of this procedure,
determine:
compressor watts 5,690 watts
Indoor fan motor from Step II 1,431 watts
Outdoor fan motor from Physical Data table find
1
/
4
hp†
Assume OD motor efficiency is 0.75.
Watts = (746 x hp)/(motor Eff)
= (746 x
1
/
4
)/(0.75)
= 249 watts
†Dual circuit units will have two outdoor fans, dou-
ble values.
b) Energy$Recycler:
Compressor watts from 62AQ060
Cooling Ratings table 1,060 watts
Optional supply fan from
fan curves none selected
Exhaust fan operating watts from 62AQ060
Exhaust Fan Performance Curve at 230-v,
450 cfm, 0.2 in. wg, Static = 110 watts
Total watts for the unit in operation
at design conditions 8,540 watts
X Electrical data RLA, FLA, LRA, MCA and
MOCP.
Separate Power Supply:
If the 62AQ is wired for separate power see the Elec-
trical Data table.
Single Power Supply with Unit:
The unit is 230 v-3-60 Hz, so from the 48TF Electri-
cal Data table, find unit electrical data. For the rooftop
unit with alternate indoor fan motor the data is MCA
= 27.3 amps, MOCP = 35 amps, Min Unit Discon-
nect Size FLA = 27, and LRA = 128.
For this example follow the steps outlined in the
Application Data section of the Energy$Recycler
Product Data for single power supply for all rooftop
units except size 014 (230-v) and 62AQ on 460-v
power supply. For other size and voltage conditions
follow corresponding steps also outlined in the
Energy$Recycler Product Data Application data
section.
From the Single Power Supply table (Electrical Data,
Energy$Recycler Product Data) find 230 v, for
62AQ060300, “X” = 8.1 amps and “Y” = 9.3 amps.
Add “X” amps to the MCA and MOCP and add “Y”
amps to the minimum disconnect size.
(MOCP calculation is 43.1. Round the value down to
40. 40 is greater than the MCA of 35.4, therefore 40
is the correct MOCP.)
The wiring to the unit must be suitable for the MCA
calculated above.
The overcurrent protective device for the combination
load is equal to 40, thus a single disconnect may be
used for BOTH the MAIN UNIT and the 62AQ pro-
vided that the wire supplying the 62AQ is sized for a
minimum of 33% of the maximum overcurrent pro-
tection device value (i.e., 40 x .33 = 14 Amps). No
further subfusing is required.
In this example a 40-amp disconnect would be used
for the combined load of the 48TF006 and the
62AQ060 Energy$Recycler unit.
MCA MOCP FLA LRA
48TF 27.3 35 27 128
62AQ 8.1
8.1 9.3 31.7
Total 35.4 43.1 36.3 159.7