60
ELECTRICAL DATA (With Convenience Outlet) (cont)
LEGEND
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker
**Fuse only.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
UNIT
48TF
NOMINAL
VOLTAGE
IFM
TYPE
VOLTAGE
RANGE
COMPR
(ea)
OFM
(ea)
IFM
COMBUSTION
FAN MOTOR
FLA
POWER SUPPLY
DISCONNECT
SIZE*
Min Max RLA LRA Hp FLA FLA MCA MOCP† FLA LRA
012
(10 Tons)
208/230-3-60
Std
187 254 15.8 130.0
1
/
4
1.4
5.8
.6
49.1/49.1 60/60 50/50 311/311
Alt 7.5 50.8/50.8 60/60 52/52 330/330
High 15.0 58.3/58.3 70/70 61/61 378/378
460-3-60
Std
414 508 7.9 64.0
1
/
4
0.7
2.6
.3
23.7 30 24 154
Alt 3.4 24.5 30 25 193
High 7.4 28.5 30 30 187
575-3-60
Std
518 632 6.6 52.0
1
/
4
0.7
2.6
.3
20.6 25 21 109
Alt 3.4 21.2 25 21 141
High 7.4 24.4 30 25 136
014
(12
1
/
2
Tons)
208/230-3-60
Std
187 254 23.0 146.0
1
/
4
1.4
10.6
.6
71.2/71.2 80/80** 74/74 387/387
Alt 15.0 75.6/75.6 90/80** 79/79 410/410
460-3-60
Std
414 508 10.4 73.0
1
/
4
0.7
4.8
.3
32.3 45 34 194
Alt 7.4 34.9 45 37 205
575-3-60
Std
518 632 8.3 58.4
1
/
4
0.7
4.8
.3
26.3 30 27 156
Alt 7.4 28.4 30 29 165
FLA —
Full Load Amps
HACR —
Heating, Air Conditioning and Refrigeration
IFM —
Indoor (Evaporator) Fan Motor
LRA —
Locked Rotor Amps
MCA —
Minimum Circuit Amps
MOCP—
Maximum Overcurrent Protection
NEC —
National Electrical Code
OFM —
Outdoor (Condenser) Fan Motor
RLA —
Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
7
457
Electrical data (cont)