ELECTRICAL DATA (With Convenience Outlet) (cont)
LEGEND
*Used to determine minimum disconnect per NEC.
Fuse or HACR circuit breaker
**Fuse only.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
UNIT
48TF
NOMINAL
VOLTAGE
IFM
TYPE
VOLTAGE
RANGE
COMPR
(ea)
OFM
(ea)
IFM
COMBUSTION
FAN MOTOR
FLA
POWER SUPPLY
DISCONNECT
SIZE*
Min Max RLA LRA Hp FLA FLA MCA MOCP FLA LRA
012
(10 Tons)
208/230-3-60
Std
187 254 15.8 130.0
1
/
4
1.4
5.8
.6
49.1/49.1 60/60 50/50 311/311
Alt 7.5 50.8/50.8 60/60 52/52 330/330
High 15.0 58.3/58.3 70/70 61/61 378/378
460-3-60
Std
414 508 7.9 64.0
1
/
4
0.7
2.6
.3
23.7 30 24 154
Alt 3.4 24.5 30 25 193
High 7.4 28.5 30 30 187
575-3-60
Std
518 632 6.6 52.0
1
/
4
0.7
2.6
.3
20.6 25 21 109
Alt 3.4 21.2 25 21 141
High 7.4 24.4 30 25 136
014
(12
1
/
2
Tons)
208/230-3-60
Std
187 254 23.0 146.0
1
/
4
1.4
10.6
.6
71.2/71.2 80/80** 74/74 387/387
Alt 15.0 75.6/75.6 90/80** 79/79 410/410
460-3-60
Std
414 508 10.4 73.0
1
/
4
0.7
4.8
.3
32.3 45 34 194
Alt 7.4 34.9 45 37 205
575-3-60
Std
518 632 8.3 58.4
1
/
4
0.7
4.8
.3
26.3 30 27 156
Alt 7.4 28.4 30 29 165
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
NEC
National Electrical Code
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
7