PremierLink™ Direct Digital controls —
The Premier-
Link Direct Digital Controls (DDC) requires the use of a
Carrier electronic thermostat or a CCN connection for
time broadcast to initiate its internal time clock. This is nec-
essary for broadcast of time of day functions (occupied/
unoccupied).
PremierLink Features:
Equipment Control Functions
Cooling Stages
Heating Stages
Indoor-Fan Motor
4-Way Valve
Economizer Control Functions
Dry Bulb Control
Enthalpy Control
Differential Enthalpy
Power Exhaust
Advanced Control Functions
Smoke Detection
Optimal Start (90.1)
Unoccupied Free Cool
Smart Staging and Optimal Staging
Network Protocol
CCN
Internet Ready 38.4 baud rate
Diagnostics/Advanced Service Features
Diagnostics
Onboard display
•Scheduling
Via Communicating Stat
•User Interface
Navigator (LEN protocol)
LID2B (CCN)
PC w/Carrier software (CCN)
DESCRIPTION STATUS UNITS POINT LIMITS ACCESS
Space Temperature
xxx.x dF SPT -40.0 to 245.0 dF R/W
Supply Air Temperature
xxx.x dF SAT -40.0 to 245.0 dF R/W
Outside Air Temperature
xxx.x dF OAT -40.0 to 245.0 dF R/W
Control Setpoint
xxx.x dF CLSP R
Cooling % Total Capacity
xxx % CCAP 0 to 100 % R
Heating % Total Capacity
xxx % HCAP 0 to 100 % R
Economizer Active
No/Yes ECOS 0 to 1 R
Supply Fan Relay
Off/On SF 0 to 1 R/W
Supply Fan Status
Off/On SFS 0 to 1 R
Economizer Position
xxx.x % ECONPOS 0.0 to 100.0 % R/W
Current Min Damper Pos
xxx.x % IQMP 0.0 to 100.0 % R
Filter Status
Clean/Dirty FLTS 0 to 1 R/W
Remote Occupied Mode
Off/On RMTOCC 0 to 1 R/W
Heat Stage 1
Off/On HS1 0 to 1 R
Heat Stage 2
Off/On HS2 0 to 1 R
Heat 3/Exhaust/Rev Valve
Off/On H3_EX_RV 0 to 1 R
Enthalpy
Low/High ENTH 0 to 1 R/W
Indoor Air Quality
xxxx.x IAQI 0.0 to 5000.0 R/W
Indoor Air Quality Setpt
xxxx.x IAQS 0.0 to 5000.0 R
Outdoor Air Quality
xxxx.x OAQ 0.0 to 5000.0 R/W
Fire Shutdown
Normal/Alarm FSD 0 to 1 R/W
SPT Offset
xx.x ^F STO -15.0 to 15.0 ^F R/W
Compressor 1
Off/On CMP1 0 to 1 R
Compressor 2
Off/On CMP2 0 to 1 R
Compressor Safety
Off/On CMPSAFE 0 to 1 R
Controls (cont)