MODE — CONFIGURATION (cont)
ITEM EXPANSI O N RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN POINT ENTRY
HMZR Humidimizer Config HMZR_CFG
REHT Humidimizer Equipped No/Yes No
Ye s : H u m i d i --- M i Z e r F I O P
REHEA T
R.DEC Reheat2 Stage Decr . Time 0 to 999 secs 60 RSTAGDEC
R.INC Reheat2 Stage Incr . Time 0 to 999 secs 300 RST AGINC
RA.LO Reheat2 OAT Lim it A 20 to 70 °F 40 OAT LRH_A
RA.LP Reheat2 SSP Lo Limit A 50 to 100 psig 80 RHSSPL_A
RA.HP Reheat2 SSP Hi Limit A 50 to 100 psig 90 RHSSPH_A
RB.LO Reheat2 OA T Limit B 20 to 70 °F 50 OAT LRH_B
RB.LP Reheat2 SSP Lo Limit B 50 to 100 psig 80 RHSSPL_B
RB.HP Reheat2 SSP Hi Limit B 50 to 100 psig 90 RHSSPH_B
HEAT Heating Configuration HEAT_CFG
HT.TY Type of Heat Ins tall ed 0=No Heat
1=Gas2=Electric
0 (50 series with no electri c heat)
1(48series)
2 (50 series with elec tric heat)
HEATTY P E
N.HTR N u m ber of Heat Stages 1to2 2 (all except below)
1 (48 series Low Nox or
Single Phase Unit)
1 (50 series 04---14
with low heat)
1 (50 series 04---12
with medium heat)
1 (50 series 04, 05,
with high heat)
1 (50 series 575v 07---09,
with high heat)
1 (50 series 460v 07,
with high heat)
NUM_HEAT
MRT.H Heat Min i m um On T i m e 60 to 999 sec 120 HMIN _O N
MOT.H Heat Minimum Off Time 60 to 999 sec 120 HMI N_OFF
H.DEC Heat Stage Decreas e Tim e 120 to 999 sec 300 HSTAGDE C
H.INC Heat S tage Inc r eas e Tim e 120 t o 999 sec 450 HSTAGIN C
FOD.E Fan--- off Del ay, Elect Heat 10 to 600 sec 30 ELEC_FOD
FOD.G Fan--- off Delay, Gas Heat 45 to 600 sec 45 GAS _FOD
HT.LO Heating Loc k out Temp 40 to 125 °F 75 OATL HEAT
SAT
SAT.H SAT Heat Mode Sens in g Disable/Enable Disable SAT_HEAT
SAM.L Maxim u m SAT Lower Lev el 85 to 200 °F 140 SATMAX_L
SAM.U Maxim u m SAT Upp er Level 85 to 200 °F 160 SATMAX_H
SPT Space Temperature
HT.PD SP T Heat Deman d (+ ) Lev el 0.5 to 5 ^F 1 HDEM_POS
HT.ND SPT Heat Deman d (--- ) Lev el --- 5 t o --- 0 . 5 ^F --- 1 HDEM_NEG
H.LAG Heat Therm al Lag F actor 0to5 1 HEAT_L A G
ECON Economizer Configuration ECON_CFG
EC.EN E con om iz er Ins tal led No/Yes No: no FIOP
Yes: FIOP
ECONO
E.CTL Econom izer Con trol Type 1=Dig/Position
2=Dig/Command
3=Analog Ctrl
1 ECON_CTL
MP.25 Econ Min at 25% Fans peed 0 to 100 % 0 MINP_25
MP.50 Econ Min at 50% Fans peed 0 to 100 % 0 MINP_50
MP.75 Econ Min at 75% Fans peed 0 to 100 % 0 MINP_75
MP.MX E con M in at Max Fans p eed 0 to 100 % 30
0: FIOP EnergyX
MINP_MAX
EC.MX Econo Cool Max P os ition 0 to 100 % 100 ECON OMA X
M.ANG M i n A c tu ator Ctr l An g l e 75 to 90 88 MINANGLE
EH.LO Econ o Cool Hi Temp Lim it 40 to 100 °F 65 OA TL E CL H
EL.LO Econ o Cool Lo Temp Limit ---30 to 50 °F 0 OA TL EC L L
DF.DB Diff Dry Bulb Control Disable/Enable Disable DIFFBUL B
UEFC Un oc cu pi ed Free Cooling 0=Disabled
1=Unoccpied
2=PreOccupancy
2 UEFC _CFG
FC.TM Free Cool PreOcc Ti me 1 to 9999 mins 120 UEFCTIME
FC.LO Free Cool Low Temp Li mi t ---30 to 70 °F 50 OAT L UE FC
PE.EN Power Exhaust Installed No/Y es No: no FIOP
Yes: FIOP
PE_ENABL
PE.1 PE Stage1 Econ o P os ition 0 to 100 % 40 PE1_POS
PE.2 PE Stage2 Econ o P os ition 0 to 100 % 75 PE2_POS
PE1C Power Exh au s t Stage1 CFM 0 to 15000 CFM 800 (04---07)
1600 (08---14)
3200 (17---28)
PE1_CFM
PE2C Power Exh au s t Stage2 CFM 0 to 15000 CFM 0 PE2_CFM
IDF.C Indoor Fan M ax Speed CFM 500 to 15000 CFM 2000 (04--- 07)
4000 (08---14)
8000 (17---28)
IDF_CFM
EN.SW Enthalpy Switch 0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
ENTHLCFG
E.TRV Econ om izer Travel Ti me 5 to 300 secs 150 ECONOT RV
E.MXB Bottom Stage Max Eco n o 0 t o 100 % 50 ECONMAXB
E.MXT Top St a g e M a x E c o n o 0 to 100 % 25 (03--- 14)
0 (17---28)
ECONMAXT
ComfortLINK v2.X