Alert Code T416 -- OAQ Input Out of Range
This alert occurs when the OAQ input (on ECB) is less than 3.5
mA and the sensor is configured as installed. OAQ operation will
be disabled. Check sensor and wiring. This alert clears
automatically.
Alert Code T418
There are 4 different alerts under this one alert code. Pressing enter
and esc on the marquee or navigator to expand the T418 alert will
show you one of the below alerts. All these alerts are generated by
the OAU device and reported to the MBB. These alerts can only
occur if the Outdoor Air Unit Type (Configuration OAU
OA.TY) is not set to 0. Control action is only taken on the OAU
side and these alerts will reset automatically when the OAU clears
them. Refer to the EnergyX Supplemental Installation Instructions
for more information on these alarms.
S OAU Motor Failure
This alert occurs when the OAU Motor Failure Alarm
(Operating Modes OAU ALM.1) is on. This is usually
due to motor status reporting a failure on the OAU.
S OAU Dirty Filter
This alert occurs when the OAU Dirty Filter Alarm (Operating
Modes OAU ALM.2) is on. This is usually due to filter
status reporting a dirty filter on the OAU.
S OAU Low CFM
This alert occurs when the OAU Low CFM Alarm (Operating
Modes OAU ALM.3) is on. This is usually due to OAU
not capable of achieving proper CFM. If unit is equipped with a
VFD on the indoor fan, the configuration OAU Fan Boost
Enable is set to yes (Configuration OAU EFBE = Yes),
and this alarm is active for 10 minutes, the fan will be
commanded to the next highest configured fan speed. If this
alarm is still active after another 10 minutes, the fan will again
change to the next highest configured fan speed, and so on every
10 minutes until the maximum speed is commanded. The fan
will stay at this override commanded speed until this alarm
clears and a different function changes the commanded speed.
S OAU General Alarm
This alert occurs when the OAU Alarm (Operating Modes
OAU ALM.4) is on. Refer to the specific OAU
documentation for details.
Alert Code A420 -- Supply VFD Fault
This alarm occurs when the VFD has faulted and communicates it
to the Main Base Board (MBB). The last VFD fault number can be
viewed as VFD1 Last Full code (Run Status
S.VFD
LFC).
Refer to VFD major component section for details on its alarms
and faults. The alarm will shut down the unit if the fan ramps down
to 0%. This alarm will automatically reset or can be reset through
the display.