MODE — CONFIGURATION (cont)
ITEM EXPANSI O N RANGE UNITS DEFAULT
CCN TABLE/
S u b --- T A B L E
CCN POINT ENTRY
ALM.O Alarm Relay Config. ALM_CFG
A.SPC SPT/SPRH Sensor Failure No/Y es Yes SP ACE_AL
A.SRT SAT/RAT Sensor Failure No/Yes Yes SA TRATAL
A.OAT OAT Thermis tor Failu re No/Yes Yes OA T _AL
A.CS Current Sensor Failure No/Yes No CS _AL
A.CMP Compressor Failure No/Y es Yes COMP_AL
A.CKT Refrig Circuit Failure No/Yes Yes CKT_AL
A.SSP SSP T rans ducer Failure No/Yes Yes SS P_AL
A.SCT SCT Thermis tor Failure No/Yes Yes SCT_AL
A.FAN Indoor F an F ail u re No/Yes Yes FAN_AL
A.FIL Dirty Filter No/Yes Yes FILT_AL
A.TST Thermostat Failure No/Y es Yes TST AT_AL
A.ECO Econ omi zer F ail ur e No/Yes Yes ECON_AL
A.OAU Ou tside Air unit Alarms No/Yes Yes OAU_AL
PID PID Configurations PID_CFG
EC.P Econ om izer PID --- kP 0.00 to 99.90 2.5 ECONO_P
EC.I Econom izer PID --- kI 0.00 to 99.90 0.12 ECON O_I
EC.D Econom izer PID --- kD 0.00 to 99.90 1 ECONO_D
EC.DT Ec on om iz er PID --- rate 10.00 to 180.00 secs 15 ECONO_DT
EC.DB Econom izer PID Deadb and 0to25 % 3 ECONBAND
LK.P Linkage Staging PID - -- kP 0.00 to 99.90 10 LINK_P
LK.I Linkage Staging PID --- kI 0.00 to 99.90 5 LINK_I
LK.D Linkage Staging PID - -- kD 0.00 to 99.90 5 LINK_D
LK.DT Linkage Staging PID --- rate 10.00 to 180.00 secs 30 LINK_DT
(GENERIC = CCN only) GENERIC S
POINT 01 Definition Point_01
POINT 02 Definition Point_02
POINT 03 Definition Point_03
POINT 04 Definition Point_04
POINT 05 Definition Point_05
POINT 06 Definition Point_06
POINT 07 Definition Point_07
POINT 08 Definition Point_08
POINT 09 Definition Point_09
POINT 10 Definition Point_10
POINT 11 Definition Point_11
POINT 12 Definition Point_12
POINT 13 Definition Point_13
POINT 14 Definition Point_14
POINT 15 Definition Point_15
POINT 16 Definition Point_16
POINT 17 Definition Point_17
POINT 18 Definition Point_18
POINT 19 Definition Point_19
POINT 20 Definition Point_20
TRIM Sensor Calibration (CCN TRIM --- see
Maintenance Display)
SPT.C Sp ace Temp Calib rati on --- 30 to 130 °F
SPT.T Space T emp T rim --- 30 to 30 ^F 0
SAT.C Supply Air Temp Calib. --- 30 to 130 °F
SAT.T Supply Air Temp T rim ---30 to 30 ^F 0
RAT.C Return Air Temp Calib. --- 30 to 130 °F
RAT.T Return Air Temp Trim ---30 to 30 ^F 0
CCN CONFIGURATION
CCN CCN Configuration 48_50_HC
CCN.A CCN Elemen t Num ber 1 to 239 1 CCNADD
CCN.B CCN Bus Number 0 to 239 0 CCNBUS
BAUD CCN Baud Rate 1=2400
2=4800
3=9600
4=19200
5=38400
3 CCNBAUDD
BROD CCN Broadcast Config. BRODEFS
B.TIM CCN Time/Date Broadcast No/Yes No CCNBC
B.OAT CCN OA T Broadcast No/Yes No OAT BC
B.GS Global Sc h ed u le Broadc s t No/Yes No GS BC
B.ACK CCN Broadcast Ack’er No/Y es No CCNBCACK
SCH.O CCN Schedule Overrides SCHEDOVR
SCH.N Schedule Number
0 = Always Occupied
1 --- 6 4 = Loca l Sche d u l e
65---99 = Global Sch edu le
0 SCHEDNUM
HOL.G Accept Global Holidays No/Yes No HOL I D AYT
OV.TL Override Time Limit 0to4 hours 4 OTL
OV.EX Timed Override Hours 0to4 hours --- OVR_EX T
OV.SP SPT Override Enabled No/Y es Yes TIMEOVER
LDSH CCN LOADSHED CONFIG. LOADSHED
S.GRP Loadshed Group Number 0to16 0 SHED_NUM
R.MXC Redl in e Max Cool Stages 0to3 2 MAXCREDL
S.MXC Load s h ed Max Cool Stages 0to3 2 MAXCSHED
R.MXH Redl in e Max Heat Stag es 0to2 2 MAXHREDL
S.MXH L oads h ed Max Heat Stages 0to2 2 MAXHSHED
ComfortLINK v2.X