SERVICE TEST
The Service Test function can be used to verify proper operation of
compressors, heating stages, Humidi--MiZert System, indoor fan,
power exhaust fans, economizer, and the alarm relay. Use of
Service Test is recommended at initial system start up and during
troubleshooting (See Table 4 for point details).
Service Test mode has the following changes from normal
operation:
S Outdoor air temperature limits for cooling circuits, economizer,
and heating are ignored. Normal compressor time guards and
other staging delays are reduced to 30 seconds or less.
S Circuit alerts are limited to 1 strike (versus 3) before changing to
alarm shut down state.
S The status of ALM.N is ignored so all alerts and alarms are
broadcast on CCN.
S The words “SERVICE TEST” are inserted into every alarm
message.
Service test can only be turned ON/OFF at the unit display. Once
turned ON, other entries may be made with the display or through
CCN. To turn Service Test on, change the value of TEST to ON.
To turn service test off, change the value of TEST to OFF.
NOTE: Service Test mode may be password protected. Refer to
Basic Control Usage section for more information. Depending on
the unit model, factory--installed options, and field--installed
accessories, some of the Service Test functions may not apply.
Independent Outputs
The independent (INDP) submenu is used to change output status
for the economizer, power exhaust stages, crankcase heaters, alarm
relay, and outside air unit.. These independent outputs can operate
simultaneously with other Service Test modes. All outputs return to
normal operation when Service Test is turned off. When the
economizer is using the factory default Digital Control Type
(ConfigurationECONE.CTL is 1 or 2) then the Economizer
Calibration feature may be used to automatically check and reset
the economizer actuator range of motion. Refer to the economizer
operation section of more details. On EnergyX equipped units, use
the outside air unit (OAU) points to test the ERV components.
Fan Test
The fans (FANS) submenu is used to change output status for the
indoor fan. On single speed fan units the indoor fan contactor can
be energized or de--energized using the IDF1 test. For units with a
VFD the indoor fan speed test (F.SPD) is available. F.SPD runs the
fan at the desired speed entered. IDF Fan Mode (F.MOD) will run
the fan at the programmed speed for each mode. IDF2 and IDF3
are reserved for future use.
Cooling Test
The cooling (COOL) submenu is used to change output status for
the individual compressors. Compressor starts are staggered by 15
seconds. The fans (FANS) and heating (HEAT) service test outputs
are reset to OFF for the cooling service test. Indoor fans and
outdoor fans are controlled normally to maintain proper unit
operation. If LEN VFD fan is configured, then the indoor fan
speed will default to the Mech. Cooling Fan Speed configuration
point (ConfigurationI.FANFS.CL) when one compressor is
turned on. The Reduced Cool Fan Speed (F.SPD) can only be
changed while one stage is running. If more then one stage is on
the actual fan speed will be 100%. F.SPD shows the reduced speed
not actual speed. On single stage units, actual fan speed will be
100% when the compressor is on. All normal cooling alarms and
alerts are functional.
NOTE: Circuit A will always be operated with Circuit B.
Humidi--MiZert Test
For units with the factory Humidi-MiZer option, the Humidi-MiZer
(HZMR) submenu is used to change the output status to operate the
circuits in different Humidi--MiZer modes or to separately test the
Humidi--MiZer valve operations. Refer to the Humidi-MiZer operation
section for details on these modes and valves. The fans (FANS),
cooling (COOL), and heating (HEAT) service test outputs are reset to
OFF for the Humdi--MiZer service test. Indoor and outdoor fans are
controlled normally to maintain proper unit operation. If LEN VFD
fan is configured, then the indoor fan speed will default to the Reheat2
Fan Speed configuration point (ConfigurationI.FANFS.RH)
when Reheat2 test is turned on. The Reheat2 fan speed (F.SPD) only
reflects the speed setting for testing Reheat2 circuits, and can only be
changed when a circuit is in Reheat2. Actual speed may be different if
Reheat 1 tests are being performed. All normal cooling alarms and
alerts are functional. Refer to the Humidi--MiZer operating section for
more information.
NOTE: Circuit A will be operated with Circuit B.
Table 4 – Service Test Modes and Submodes Directory
DISPLAY MENU/
SUB-- MENU/
NAME
EXPANDED NAME VALUES
SERVICE TEST
TEST Field Service Test Mode Off/On
INDP Test Independent Outputs
ECON Economizer Position Test 0 to 100%
E.CAL Calibrate Economizer Off/On
PE.1 Power Exhaust 1 Test Off/On
PE.2 Power Exhaust 2 Test Off/On
ALRM Alarm Relay Test Off/On
OA.DM OAU 2-position Damper Close/Open
WHL OAU Wheel Test 0 to 100%
OA.OF OAU OA Fan Speed Test 0 to100
OA.XF OAU PE Fan Speed Test 0 to100
OA.HT OAU Tempring Heater Test 0 to 100
FANS Te st Fa n s
F. S P D Indoor Fan Speed Test 0 to 100
F. M O D IDF Fan Mode 0to7
IDF.1 Indoor Fan 1 Test Off/On
IDF.2 Indoor Fan 2 Test Off/On
IDF.3 Indoor Fan 3 Test Off/On
COOL Test Cooling
CMP.A Cool A Test Off/On
CMP.B Cool B Test Off/On
F. S P D Reduced Cool Fan Speed 60 to 100
HMZR Te s t H u m i d i --- M i Z e r
RH1.B Reheat1 B Test Off/On
RH1.C Reheat1 C Test Off/On
RH2.A Reheat2 A Test Off/On
RH2.B Reheat2 B Test Off/On
F. S P D Reheat2 Fan Speed 0 to 100
CRC Cool->Reheat1 Valve Test Off/On
RHV.A Reheat2 Valve A Test Off/On
RHV.B Reheat2 Valve B Test Off/On
HEAT Te st He a t i n g
HT.1 Heat Stage 1 Test Off/On
HT.2 Heat Stage 2 Test Off/On
F. S P D Reduced Heat Fan Speed 0 to 100
ComfortLINK v2.X