Carrier 25VNA8 Instruction Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 22
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
17
Refer to Table 5 and Fig. 21 and 22 for resistance values versus
temperature.
Table 5 10K/50Kohm Resistance Values vs Temperature
10Kohm
_C(_F)
TEMPERA TURE RESIST ANCE (ohms)
25.0 (77.0) 10.0 + / --- 2.3%
0.0 (32.0) 32.6 + / --- 3.2%
-28.0 (-18.4) 85.5 + / --- 3.4%
50Kohm
125.0 (257.0) 1.7 + / --- 1.6%
75.0 (167.0) 7.40 + / --- 2.0%
25.0 (77.0) 50.0 + / --- 2.3%
0
10
20
30
40
50
60
70
80
90
0 20 40 60 80 100 120
TEMPERATURE (DEG. F)
RESISTANCE (KOHMS)
THERMISTOR CURVE
A91431
Fig. 21 -- 10K Thermistor Resistance Versus Temperatur e
0
50
100
150
200
250
300
350
400
450
020406080100120
RESISTANCE (KOHMS)
TEMPERATURE (°°F)
50K THERMISTOR
A14022
Fig. 22 -- 50K Thermistor Resistance Versus Temperatur e
If the outdoor air or coil thermistor should fail, the control will
flash the appropriate fault code (see Table 7).
IMPORTANT: The outdoor air thermistor, coil thermistor and
suction thermistor should be factory mounted in the final
locations. Check to ensure thermistors ar e mounted properly
(See Fig. 23, 24, 25 and 26).
Thermistor Sensor Comparison
The control continuously monitors and compares the outdoor air
temperature sensor and outdoor coil temperature sensor to ensure
proper operating conditions. The comparison is:
S In cooling if the outdoor air sensor indicates 10_F( 5.6_C)
warmer than the coil sensor (or) the outdoor air sensor indicates
25_F( 15_C) cooler than the coil sensor, the sensors are out
of range.
S In heating if the outdoor air sensor indicates 35_F( 19.4_C)
warmer than the coil sensor (or) the outdoor air sensor indicates
10_F( 5.6_C) cooler than the coil sensor, the sensors are out
of range.
If the sensors are out of range, the control will flash the appropriate
fault code as shown in Table 7.
The thermistor comparisons are not performed during low ambient
cooling or defrost operation.
Failed Thermistor Default Operation
Factory defaults have been provided in the event of failure of
outdoor air thermistor (OAT) and/or outdoor coil thermistor
(OCT).
If the OAT sensor should fail, defrost will be initiated based on coil
temperature and time.
If the OCT sensor should fail, defrost will occur at each time
interval during heating operation, but will terminate after 2
minutes.
If there is a thermistor out--of--range error, defrost will occur at
each time interval during heating operation, but will terminate after
2 minutes.
Count the number of short and long flashes to determine the
appropriate flash code. Table 7 gives possible causes and actions
related to each error.
Outdoor Coil Thermistor
The outdoor coil thermistor is a 10Kohm resistor used for multiple
system operations. It provides the coil/liquid line temperature to
the heat pump board and user interface. Low ambient operation,
defrost initiation, defrost termination and assistance with OAT
temperature measurement of some of the functions. The sensor
must be securely mounted to the tube connecting the EXV and
distributor. See Fig. 24 for proper placement. See Table 5 for
proper resistances.
A14302
Fig. 23 -- Outdoor Coil Thermistor (OCT) Attachment
(On Distributor Tube)
OAT Thermistor must be locked in place with
spherical nib end facing towards the front of
the control box
A11142
Fig. 24 -- OAT Thermistor Location (Bottom of Control Box)
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22

Comments to this Manuals

No comments