64 Johnson Controls Unitary Products
FLASH CODES
The UCB will initiate a flash code associated with errors
within the system. Refer to UNIT CONTROL BOARD FLASH
CODES Table 80.
RESET
Remove the call for heating by lowering the thermostat set-
ting lower than the conditioned space temperature.This
resets any flash codes.
ELECTRIC HEAT ANTICIPATOR SETPOINTS
It is important that the anticipator setpoint be correct. Too
high of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter “ON” cycles
and may result in the lowering of the temperature within the
conditioned space. Refer to Table 66 for the required electric
heat anticipator setting.
GAS HEATING SEQUENCE OF OPERATIONS
When the thermostat calls for the first stage of heating, the
low-voltage control circuit from “R” to “W1” is completed. A
call for heat passes through the UCB to the Ignition Control
Board (ICB). The UCB monitors the “W1” call and acts upon
any call for heat by monitoring the Gas Valve (GV). Once
voltage has been sensed at the GV, the UCB will initiate the
fan on delay for heating, energizing the indoor blower the
specified delay has elapsed.
When the thermostat has been satisfied, heating calls are
ceased. The GV is immediately closed. The blower is de-
energized after the fan off delay for heating has elapsed. The
draft motor performs a 30-second post purge.
IGNITION CONTROL BOARD
FIRST STAGE OF HEATING
When the ICB receives a call for first stage of heating, “W1,”
the draft motor is energized. Once the draft motor has been
proven, a 30-second purge is initiated. At the end of the
purge, the GV is opened, and the spark ignitor is energized
for 10 seconds. The ICB then checks for the presence of
flame. If flame is detected, the ICB enters a flame stabiliza-
tion period. If flame was not detected, the GV closes, and a
retry operation begins.
During the flame stabilization period, a loss of the flame for 2
seconds will cause the GV to close and the retry operation to
begin. After the flame stabilization period, a loss of flame for
3/4 second will cause the GV to close and the retry operation
to begin.
At the conclusion of the flame stabilization period, the ICB will
operate the gas heat in high fire for an additional 60 seconds
(for a total for 120 seconds of high fire operation). After this
60 seconds, the ICB will then use the call for the second
stage of heat to control second stage operation of the GV.
When “W1” is satisfied, both valves are closed.
SECOND STAGE OF HEATING
When the ICB receives a call for the second stage of heating,
“W2,” the ICB conducts a complete first stage ignition
sequence. If this sequence is satisfied, the second main
valve of the GV is opened.
When “W2” is satisfied, the second main valve is closed.
RETRY OPERATION
When a flame is lost or is not detected during an attempt to
achieve ignition, a retry operation occurs. A 30-second purge
is performed between ignition attempts.
If the unit fails after three ignition attempts, the furnace is
locked-out for one hour. The furnace is monitored during this
one-hour period for unsafe conditions.
RECYCLE OPERATION
When a flame is lost after the flame stabilization period, a
recycle operation occurs. If the unit fails after five recycle
attempts, the furnace is locked-out for one hour.
GAS HEATING OPERATION ERRORS
LOCK-OUT
A one-hour lockout occurs following three retries or five recy-
cles. During the one-hour lockout, flame detection, limit con-
ditions, and main valves are tested. Any improper results will
cause the appropriate action to occur. Recycling the low volt-
age power cancels the lock-out.
TABLE 65: ELECTRIC HEAT LIMIT SETTING 42”
CABINET
UNIT (TONS) VOLTAGE
HEATER
kW
LIMIT
SWITCH
OPENS °F
DL-07, -08 (7.5, 8.5)
DU-06, -07, -08 (6.5, 7.5, 8.5)
208/230
9135
18 150
24 165
34 190
DL-07, -08(7.5, 8.5)
DU-06, -07, -08 (6.5, 7.5, 8.5)
480
9 135
18 150
24 165
34 185
DL-07, -08 (7.5, 8.5)
DU-06, -07, -08 (6.5, 7.5, 8.5)
600
9 135
18 150
24 150
34 185
TABLE 66: ELECTRIC HEAT ANTICIPATOR
SETPOINTS
SETTING, AMPS
W1 W2
0.13 0.1