Carrier 19XRV Specifications Page 1

Browse online or download Specifications for Oxygen Equipment Carrier 19XRV. Carrier 19XRV Specifications User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 206
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190010-01 Printed in U.S.A. Form 19XR-6SS Pg 1 312 7-11 Replaces: 19XR-5SS
Start-Up, Operation, and Maintenance Instructions
SAFETY CONSIDERATIONS
Centrifugal liquid chillers are designed to provide safe and
reliable service when operated within design specifica-
tions. When operating this equipment, use good judgment
and safety precautions to avoid damage to equipment and
property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions as
well as those listed in this guide.
DO NOT VENT refrigerant relief valves within a building. Outlet
from rupture disc or relief valve must be vented outdoors in accor-
dance with the latest edition of ANSI/ASHRAE 15 (American
National Standards Institute/American Society of Heating, Refrigerat-
ing, and Air Conditioning Engineers). The accumulation of refrigerant
in an enclosed space can displace oxygen and cause asphyxiation.
PROVIDE adequate ventilation in accordance with ANSI/ASHRAE
15, especially for enclosed and low overhead spaces. Inhalation of
high concentrations of vapor is harmful and may cause heart irregular-
ities, unconsciousness, or death. Misuse can be fatal. Vapor is heavier
than air and reduces the amount of oxygen available for breathing.
Product causes eye and skin irritation. Decomposition products are
hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for
any purpose. Oxygen gas reacts violently with oil, grease, and other
common substances.
NEVER EXCEED specified test pressures, VERIFY the allowable
test pressure by checking the instruction literature and the design pres-
sures on the equipment nameplate.
DO NOT USE air for leak testing. Use only refrigerant or dry
nitrogen.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and
functioning before operating any chiller.
RISK OF INJURY OR DEATH by electrocution. High voltage is
present on motor leads even though the motor is not running when a
solid-state or wye-delta mechanical starter is used. Open the power
supply disconnect before touching motor leads or terminal
s.
D
O NOT WELD OR FLAMECUT any refrigerant line or vessel until
all refrigerant (liquid and vapor) has been removed from chiller.
Traces of vapor should be displaced with dry air or nitrogen and the
work area should be well ventilated. Refrigerant in contact with an
open flame produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the
entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified
electrician.
DO NOT WORK ON electrical components, including control pan-
els, switches, starters, or oil heater until you are sure ALL POWER IS
OFF and no residual voltage can leak from capacitors or solid-state
components.
LOCK OPEN AND TAG electrical circuits during servicing. IF
WORK IS INTERRUPTED, confirm that all circuits are deenergized
before resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the
eyes. USE SAFETY GOGGLES. Wash any spills from the skin with
soap and water. If liquid refrigerant enters the eyes, IMMEDIATELY
FLUSH EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant cylinder.
Dangerous over pressure can result. When it is necessary to heat
refrigerant, use only warm (110 F [43 C]) water.
DO NOT REUSE disposable (nonreturnable) cylinders or attempt to
refill them. It is DANGEROUS AND ILLEGAL. When cylinder is
emptied, evacuate remaining gas pressure, loosen the collar and
unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to
the chiller. The introduction of the wrong refrigerant can cause dam-
age or malfunction to this chiller.
Operation of this equipment with refrigerants other than those cit-
ed herein should comply with ANSI/ASHRAE 15 (latest edition).
Contact Carrier for further information on use of this chiller with other
refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while
chiller is under pressure or while chiller is running. Be sure pressure is
at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief devices, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a
corrosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief
device when corrosion or build-up of foreign material (rust, dirt, scale,
etc.) is found within the valve body or mechanism. Replace the
device.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act
as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Fol-
low safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or
move inspection covers or other heavy components. Even if compo-
nents are light, use mechanical equipment when there is a risk of slip-
ping or losing your balance.
BE AWARE that certain automatic start arrangements CAN
ENGAGE THE STARTER, TOWER FAN, OR PUMPS. Open the
disconnect ahead of the starter, tower fans, or pumps.
USE only repair or replacement parts that meet the code requirements
of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process
control group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been
completely drained.
DO NOT LOOSEN a packing gland nut before checking that the nut
has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corro-
sion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure
relief device to prevent a build-up of condensate or rain water.
DANGER
WARNING
CAUTION
19XR,XRV
Hermetic Centrifugal Liquid Chillers
with PIC II Controls and HFC-134a
50/60 Hz
Page view 0
1 2 3 4 5 6 ... 205 206

Summary of Contents

Page 1 - 50/60 Hz

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 2 - CONTENTS

10ISOLATIONVALVESIGHTGLASSFILTERISOLATIONVALVEOIL SKIMMER LINEFILTEREDUCTOROIL PUMPTXV BULB PRESSURETRANSDUCERISOLATIONVALVESOILCOOLEROIL PUMP MOTOROI

Page 3 - CONTENTS (cont)

100pump, water pumps, tower control, and other on/off out-puts while the compressor is stopped. It also has the abil-ity to lock off the compressor an

Page 4 - INTRODUCTION

101Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides A. MANUAL STOPB. READY TO STARTC. IN RECY

Page 5

102Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)D. PRE-START ALERTS: These alerts o

Page 6

103Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)E. START-UP IN PROGRESSF. N O R M A

Page 7 - FRONT VIEW

104Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)G. NORMAL RUN WITH OVERRIDES*[LIMIT

Page 8 - Summary —

105Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)H. OUT-OF-RANGE SENSOR ALARMSSTATE

Page 9 - STARTING EQUIPMENT

106Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)I. CHILLER PROTECTIVE LIMIT FAULTS

Page 10 - Fig. 5 — Gerotor Oil Pump

107Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)I. CHILLER PROTECTIVE LIMIT FAULTS

Page 11

108Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)I. CHILLER PROTECTIVE LIMIT FAULTS

Page 12

109Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)I. CHILLER PROTECTIVE LIMIT FAULTS

Page 13 - OPTIONAL

11All starters must include a Carrier control module called theIntegrated Starter Module (ISM), excluding the Benshaw solid-state and wye-delta MX3™ s

Page 14

110Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)J. CHILLER ALERTS (cont)*[LIMIT] is

Page 15

111Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)J. CHILLER ALERTS (cont)*[LIMIT] is

Page 16

112Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)K. ISM ALARMS*[LIMIT] is shown on t

Page 17 - 21.8 132.9 93

113Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)K. ISM ALARMS (cont)*[LIMIT] is sho

Page 18

114Table 17 — ICVC Primary and Secondary Messages andCustom Alarm/Alert Messages with Troubleshooting Guides (cont)K. ISM ALARMS (cont)*[LIMIT] is sho

Page 19

115Table 18A — Thermistor Temperature (F) vs. Resistance/Voltage DropTEMPERATURE(F)PIC IIVOLTAGEDROP (V)RESISTANCE(Ohms)–25 4.700 97,706–24 4.690 94,5

Page 20

116Table 18B — Thermistor Temperature (C) vs. Resistance/Voltage DropTEMPERATURE(C)PIC IIVOLTAGEDROP (V)RESISTANCE(Ohms)–33 4.722 105 616–32 4.706 99

Page 21

117NOTE: If the cooler or condenser vessels are at0 psig (0 kPa) or are open to atmospheric pressure, thetransducers can be calibrated for zero withou

Page 22 - CCN — Carrier Comfort Network

118• is lit continuously, there is a problem that requiresreplacing the module• is off continuously, the power should be checked• blinks 3 times per s

Page 23

119115 VACLL1LL2 1ACONTACT INPUTSSPAR ICE REM STRT 1M 2MSFTY BLD STRT FLT AUX AUXFUSELINE VOLTAGESL1L2L3IL1LINE CURRENTSGROUND FAULTSIL2

Page 24

12General — The 19XR hermetic centrifugal liquid chillercontains a microprocessor-based control center that monitorsand controls all operations of the

Page 25

120Replacing Defective Processor Modules —The module replacement part number is printed on a smalllabel on the rear of the ICVC module. The chiller mo

Page 26 - 0.1-3.0 SP_HIGH

1215. Using an ohmmeter, perform the following resistancemeasurements and record the results: If all measured values are greater than 5K ohms, proceed

Page 27

122Table 20A — 19XR Heat Exchanger Data — Drive End Entering Cooler Water*Rigging weights are for standard tubes of standard wall thickness (0.025-in.

Page 28

123Table 20A — 19XR Heat Exchanger Data — Drive End Entering Cooler Water (cont)*Rigging weights are for standard tubes of standard wall thickness (0.

Page 29

124Table 20B — 19XR Heat Exchanger Data — Compressor End Entering Cooler Water*Rigging weights are for standard tubes of standard wall thickness (0.02

Page 30

125Table 20B — 19XR Heat Exchanger Data — Compressor End Entering Cooler Water (cont)*Rigging weights are for standard tubes of standard wall thicknes

Page 31

126Table 21 — 19XR Additional Data for Marine Waterboxes**Add to heat exchanger data for total weights or volumes.NOTE: For the total weight of a vess

Page 32

127Table 22 — 19XR Compressor Weights*Transmission weight does not include rotor, shaft, and gear. NOTE: The weights indicated do not include motor, s

Page 33

128 Table 23B — 19XR Compressor and Motor Weights — Compressor Frame Size 3*Total compressor weight is the sum of the compressor aerody-namic componen

Page 34

129 Table 23B — 19XR Compressor and Motor Weights — Compressor Frame Size 3 (cont)*Total compressor weight is the sum of the compressor aerody-namic c

Page 35

13SPEEDVOLTSAMPSHzKwTORQUEPasswordRUNNINGREMOTEJOGAUTOFORWARDREVERSEPROGRAMPRO-GRAMForwardReverseENTERRUNJOBAUTOMANSPEEDVOLTSAMPSHzKwTORQUEPasswordRUN

Page 36 - 1-5 OFF_SEL 3

130 Table 23C — 19XR Compressor and Motor Weights — Compressor Frame Size 4*Total compressor weight is the sum of the compressor aerody-namic componen

Page 37

131 Table 23D — 19XR Compressor and Motor Weights — Compressor Frame Size 4 (cont)*Total compressor weight is the sum of the compressor aerody-namic c

Page 38

132 Table 23E — 19XR Compressor and Motor Weights — Compressor Frame Size 5*Total compressor weight is the sum of the compressor aerody-namic componen

Page 39

133 Table 23E — 19XR Compressor and Motor Weights — Compressor Frame Size 5 (cont)*Total compressor weight is the sum of the compressor aerody-namic c

Page 40

134Table 24A — 19XR Waterbox Cover Weights — English (lb) LEGENDNOTE: Weight for NIH 2-pass cover, 150 psig, is included in the heat

Page 41

135Table 24A — 19XR Waterbox Cover Weights — English (lb) (cont) LEGENDNOTE: Weight for NIH 2-pass cover, 150 psig, is included in the he

Page 42

136Table 24A — 19XR Waterbox Cover Weights — English (lb) (cont) LEGENDNOTE: Weight for NIH 2-pass cover, 150 psig, is included in the h

Page 43 - Error, Gain = 3

137Table 24B — 19XR Waterbox Cover Weights — SI (kg) LEGENDNOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in theheat excha

Page 44

138Table 24B — 19XR Waterbox Cover Weights — SI (kg) (cont) LEGENDNOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in thehe

Page 45

139Table 24B — 19XR Waterbox Cover Weights — SI (kg) (cont) LEGENDNOTE: Weight for NIH 2-pass cover, 1034 kPa, is included in theheat exc

Page 46

14PIC II System Components — The chiller controlsystem is called the PIC II (Product Integrated Control II). SeeTable 1. The PIC II controls the opera

Page 47

140Table 25 — 19XR Component Weights*To determine compressor frame size, refer to 19XR,XRV Computer Selection Program.†Included in total cooler weight

Page 48

14119XRV COMPRESSOR FITS AND CLEARANCES (in.)*Depends on impeller size, contact your Carrier Service Represen-tative for more information.NOTES:1. All

Page 49

142SEE VIEW A1 OR A2A23SEE VIEW B41COMPRESSOR, TRANSMISSION AREA (FRAME 5 COMPRESSOR SHOWN)1) OIL HEATER RETAINING NUT (NOT SHOWN)2) BULL GEAR RETAINI

Page 50 - Table 7 — Capacity Overrides

143POF1HEF2KIJIMPELLER SHIMMINGTO BE DETERMINEDAT ASSEMBLYSEE VIEW CTHRUSTSEENOTE 5GL+0.0007-0.00070.00110.0013THRUST0.0250.005INTERFERENCE0.00110.001

Page 51

144NMVIEW C — HIGH SPEED SHAFT RING SEALMOTOR LEAD INSTALLATION LABELS19XR COMPRESSOR ASSEMBLY TORQUES* Not shown.Fig. 56 — Compressor Fits and Cleara

Page 52

145Fig. 57 — PIC II Control Panel Wiring Schematic (Frame 2, 3, 4 Compressors without Split Ring Diffuser)a19-1870

Page 53

146Fig. 57 — PIC II Control Panel Wiring Schematic (Frame 2, 3, 4 Compressors without Split Ring Diffuser) (cont)a19-1870

Page 54

147a19-1871Fig. 58 — PIC II Control Panel Wiring Schematic (Frame 4 and 5 Compressors with Split Ring Diffuser)

Page 55

148Fig. 58 — PIC II Control Panel Wiring Schematic (Frame 4 and 5 Compressors with Split Ring Diffuser) (cont)

Page 56 - Fig. 27) —

149 AUX — AuxiliaryC—ContactorCB — Circuit BreakerCCM — Chiller Control ModuleCOMM — CommunicationCOMPR — CompressorDISCH — Discharge

Page 57

15The ICVC has a stop button, an alarm light, four buttons forlogic inputs, and a backlight display. The backlight will auto-matically turn off after

Page 58

150 AUX — AuxiliaryC—ContactorCB — Circuit BreakerCT — Current TransformerDS — Disconnect SwitchFU — FuseG—GroundHPR — High Pre

Page 59

151 AUX — AuxiliaryC—ContactorCB — Circuit BreakerCT — Current TransformerDS — Disconnect SwitchFU — FuseG—GroundFig. 61 — Cutl

Page 60

152Fig. 62 — Ground Fault Phase Current OptionFig. 63 — Separate Metering OptionLEGENDAM — AmmeterCT — Current TransformerL—Main Power SupplyVM — Volt

Page 61

153Fig. 64 — Benshaw, Inc. Wye-Delta Unit Mounted Starter Wiring Schematic (Low Voltage)a19-1873

Page 62 - Local Start-Up —

154Fig. 64 — Benshaw, Inc. Wye-Delta Unit Mounted Starter Wiring Schematic (Low Voltage) (cont)AUX — AuxiliaryBR — Bridge RectifierCB — Circuit Breake

Page 63

155Fig. 65 — Benshaw, Inc. Solid-State Unit Mounted Starter Wiring Schematic NOTES:LED status with power applied and prior to RUN command. Transformer

Page 64

156Fig. 65 — Benshaw, Inc. Solid-State Unit Mounted Starter Wiring Schematic (cont) CHART 1SYSTEM VOLTAGE3

Page 65

157Fig. 66 — Typical Across-the-Line Starter Wiring Schematic (Medium Voltage) LEGENDAUX — AuxiliaryC—ContactorCB — Circui

Page 66

158Fig. 67 — Typical Primary Reactor Starter Wiring Schematic (Medium Voltage) LEGENDAUX — AuxiliaryC—ContactorCB — Circui

Page 67

1591AFig. 68 — Typical Autotransformer Starter Wiring Schematic (Medium Voltage) LEGENDAUX — AuxiliaryC—ContactorCB — Circ

Page 68 - Temperature (C)

16OIL HEATER CONTACTOR (1C) — This contactor is lo-cated in the power panel (Fig. 12) and operates the heater at ei-ther 115 or 230 v. It is contro

Page 69

160Fig. 69 — Typical Variable Frequency Drive (VFD) Wiring Schematica19-1878

Page 70

161Fig. 69 — Typical Variable Frequency Drive (VFD) Wiring Schematic (cont)

Page 71

162Fig. 69 — Typical Variable Frequency Drive (VFD) Wiring Schematic (cont)

Page 72

163Fig. 69 — Typical Variable Frequency Drive (VFD) Wiring Schematic (cont)a19-1879

Page 73

164Fig. 69 — Typical Variable Frequency Drive (VFD) Wiring Schematic (cont)a19-1880

Page 74

165LEGEND FOR FIG. 69 AUX — AuxiliaryCB — Circuit BreakerCCM — Chiller Control ModuleCCN — Carrier Comfort NetworkCOMM — CommunicationsCT — Current Tr

Page 75 - VFD-EQUIPPED CHILLER

166APPENDIX A — ICVC PARAMETER INDEXPARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLE1CR Start Complete S TAT US I SM _S TAT1CR Stop Complete S TAT

Page 76

167APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLECCM Pressure Transducers Test SERVICE CONTROL TESTCCM PR

Page 77

168APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLECondenser Freeze Point SERVICE EQUIPMENT SERVICE SETUP1

Page 78

169APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLEDischarge Alert SERVICE EQUIPMENT SERVICE SETUP1 XDischa

Page 79 - • Surge/ HGBP Deadband = 1

17Table 2 — Standard Instrumentation SensorsICVC Operation and Menus (Table 3 andFig. 15-21)GENERAL — The ICVC display automatically reverts to thedef

Page 80 - ΔT increase

170APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLEGuide Vane Position, Actual SERVICE CONTROL ALGORITHM S

Page 81 - Delta Tsat

171APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLELAG STOP Timer SERVICE EQUIPMENT SERVICE LEADLAG XLAG ST

Page 82 - ALARM ROUTING

172APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLEModel Number SERVICE ICVC CONFIGURATIONModel Number SE

Page 83

173APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLEPumps Test SERVICE CONTROL TEST PUMPSRamp Loading Active

Page 84

174APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLESpare Temperature 2 SERVICE CONTROL ALGORITHM STATUS LL_

Page 85 - LIQUID LINE

175APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLESurge Prevention Active? STATUS VPFSTATSurge Protection

Page 86

176APPENDIX A — ICVC PARAMETER INDEX (cont)PARAMETERMENU SOFTKEYTABLE SCREEN NAME CONFIGURABLETower Fan High Setpoint SETPOINT XTower Fan Relay High S

Page 87

177APPENDIX B — LEAD/LAG WIRING 19XR Lead Lag Schematic Series Cooler Flowa19-1655

Page 88

178APPENDIX B — LEAD/LAG WIRING (cont)19XR Lead Lag Schematic Parallel Cooler Flowa19-1717

Page 89

179APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS19XR,XRV Maintenance Interval RequirementsNOTE: Equipment failures caused by lack of adherence to th

Page 90

18ALARMS AND ALERTS — An alarm shuts down the com-pressor. An alert does not shut down the compressor, but it no-tifies the operator that an unusual c

Page 91 - Fig. 46 — Refrigeration Log

180APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS19XR,XRV Monthly Maintenance LogNOTE: Equipment failures caused by lack of adherence to the Maintena

Page 92

181APPENDIX C — MAINTENANCE SUMMARY AND LOG SHEETS19XR,XRV Seasonal Shutdown LogNOTE: Equipment failures caused by lack of adherence to the Maintenanc

Page 93

182APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRINGOptional BACnet* Communications Wiring —The following section is used to configure the UPC Open c

Page 94

183APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)CONFIGURING THE BAS PORT FOR BACNET MS/TP — Use the same baud rate and communication setti

Page 95 - CONDITION CCCCCCCCC

184APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)To install a BT485 terminator, push the BT485 terminatoron to the BT485 connector located

Page 96

185APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)Table D — Open System Wiring Specifications and Recommended Vendors LEGENDLO

Page 97

186APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)COMMUNICATION LEDS — The LEDs indicate if thecontroller is communicating with the devices

Page 98

187APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)Table G — Network Points List LEGENDPOINT DESCRIPTIONCCNPOINT NAMEREAD/WRITEUNI

Page 99

188APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)Table G — Network Points List (cont) LEGENDPOINT DESCRIPTIONCCNPOINT NAMEREAD/W

Page 100

189INDEXAbbreviations and Explanations, 5Accidental Start-Up (Prevent), 89Adding Refrigerant, 95Adjusting the Refrigerant Charge, 95After Extended Shu

Page 101 - LEGEND TO TABLES 17A-17K

192. Press or to highlight the desiredstatus table. The list of tables is:•MAINSTAT — Overall chiller status•VPF_STAT — Variable primary flow surge

Page 102

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 103 - F. N O R M A L RU N

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 104 - G. NORMAL RUN WITH OVERRIDES

CL-2- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Page 105 - H. OUT-OF-RANGE SENSOR ALARMS

CL-319XR, XRV PIC II SETPOINT TABLE CONFIGURATION SHEETICVC Software Version Number:ICVC Controller Identification: BUS: ADDRESS:DESCRIPTION RANGE UNI

Page 106

CL-4- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Page 107

CL-519XR, XRV PIC II ISM_CONF TABLE CONFIGURATION SHEET* Option 3 for VFD is available on software version 9 or higher. Allother software versions use

Page 108

CL-6- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Page 109 - J. CHILLER ALERTS

CL-719XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET — MACHINES WITH SERIAL NUMBERS 1410QXXXXX AND LATER OR VERSION 9 OR LATER SOFTWARE NOTE: No var

Page 110 - J. CHILLER ALERTS (cont)

CL-8- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Page 111

CL-919XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUEComp Motor Temp Override150 to 20066 to 93DEG FDEG C20093Con

Page 112 - K. ISM ALARMS

2CONTENTSPageSAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 113 - K. ISM ALARMS (cont)

20CCNLOCAL RESETMENUDEFAULT SCREENStart Chiller In CCN Control Start Chiller in Local Control Clear AlarmsSTAT U SSCHEDULE SETPOINTSERVICE(SOFTKEYS)Ac

Page 114

CL-10- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Page 115

CL-1119XR, XRV PIC II LEADLAG TABLE CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUELead Lag ControlLEAD/LAG: ConfigurationDSABLE=0, LEAD=1,LA

Page 116

CL-12- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Page 117 - Control Modules

CL-13BROADCAST (BRODEF) CONFIGURATION SHEETDESCRIPTION RANGE UNITS DEFAULT VALUETime Broadcast Enable DSABLE/ENABLE DSABLEDaylight SavingsStart Month

Page 118 - Notes on Module Operation

CL-14- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Page 119 - INTEGRATED STARTER MODULE

CL-15ICVC DISPLAY AND ALARM SHUTDOWN STATE RECORD SHEETPRIMARY MESSAGE:SECONDARY MESSAGE:DATE:TIME:COMPRESSOR ONTIME:CHW INOILPRESSCHW OUTOIL TEMPCDW

Page 120

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Cata

Page 121 - WASHER (S)

21NEXTPREVIOUSSELECTEXITSERVICE TABLEDisplay Alarm History(The table holdsup to 25 alarms with the most recent alarm at the top of the screen.) See no

Page 122

22NEXTPREVIOUSSELECTEXITSERVICE MENU CONTINUEDFROM PREVIOUS PAGESelect a Service TableSelect a Service Table ParameterNEXTPREVIOUSSELECTEXITModify a S

Page 123

23TIME SCHEDULE OPERATION (Fig. 20)On the Menu screen, press .4. Press or to highlight the desiredschedule.OCCPC01S — LOCAL Time ScheduleOCCPC02S —

Page 124

242. There are 5 set points on this screen: BASE DEMANDLIMIT, LCW SETPOINT (leaving chilled water setpoint), ECW SETPOINT (entering chilled water setp

Page 125

25Table 3 — ICVC Display Data (cont)EXAMPLE 1 — CHILLER DISPLAY DEFAULT SCREENThe following data is displayed in the Default screen.NOTES:1. The Evapo

Page 126

26Table 3 — ICVC Display Data (cont)EXAMPLE 3 — VPF STAT DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scro

Page 127

27Table 3 — ICVC Display Data (cont)EXAMPLE 4 — STARTUP DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scrol

Page 128

28Table 3 — ICVC Display Data (cont)EXAMPLE 6 — HEAT_EX DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scrol

Page 129

29Table 3 — ICVC Display Data (cont)EXAMPLE 8 — ISM_STAT DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scro

Page 130

3CONTENTS (cont)PageSafety Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64BEFORE INITIAL START-UP . . . . . . . . . . . .

Page 131

30Table 3 — ICVC Display Data (cont)EXAMPLE 10 — SETPOINT DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Pr

Page 132

31Table 3 — ICVC Display Data (cont)EXAMPLE 13 — LL_MAINT DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Sc

Page 133

32Table 3 — ICVC Display Data (cont)EXAMPLE 14B — SURGPREV DISPLAY SCREEN (Machines with Serial Numbers 1410Qxxxxx and Lateror Version 9 or Later Soft

Page 134

33Table 3 — ICVC Display Data (cont)EXAMPLE 16 — WSMCHRLE DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scr

Page 135

34Table 3 — ICVC Display Data (cont)EXAMPLE 18 — ISM_CONF DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scr

Page 136

35Table 3 — ICVC Display Data (cont)EXAMPLE 19A — OPTIONS DISPLAY SCREEN (Machines with Serial Numbers Prior to 1410Qxxxxx)To access this display from

Page 137

36Table 3 — ICVC Display Data (cont)EXAMPLE 19B — OPTIONS DISPLAY SCREEN (Machines with Serial Numbers 1410Qxxxxx and Lateror Version 9 or Later Softw

Page 138

37Table 3 — ICVC Display Data (cont)EXAMPLE 21 — SETUP1 DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scrol

Page 139

38Table 3 — ICVC Display Data (cont)EXAMPLE 22 — SETUP2 DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Scrol

Page 140 - Table 27 — Motor Voltage Code

39Table 3 — ICVC Display Data (cont)EXAMPLE 24 — RAMP_DEM DISPLAY SCREENTo access this display from the ICVC default screen:1. Press .2. Press .3. Sc

Page 141

4CONTENTS (cont)PageRepair the Leak, Retest, and ApplyStanding Vacuum Test . . . . . . . . . . . . . . . . . . . . . . . . 95Checking Guide Vane Link

Page 142 - COMPRESSOR, TRANSMISSION AREA

40PIC II System Functions — Refer to ICVC Opera-tion and Menus section on page 17.NOTE: Words not part of paragraph headings and printed in allcapital

Page 143

41A No Flow determination is made on the evaporator side if(1) the EVAP SATURATION TEMP reads lower than 1° F (0.6°C) below the EVAP REFRIG TRIPPOINT,

Page 144

42Constant Flow Surge PreventionNormal Capacity Control Mode occurs when ACTIVEDELTA T> SURGE LINE DELTA T.Surge Prevention Mode Level 1 occurs whe

Page 145

43The ECW GAIN affects the size of the LCW CONTROLPOINT change in proportion to the difference between theECW SETPOINT and ECW TEMPERATURE.NOTE: Befo

Page 146

44A diffuser pressure transducer is installed on compressorswith a split ring diffuser. The CCM monitors pressure fluctua-tions at the inlet to the in

Page 147

45STAT display screen). It cannot be started or run during an un-occupied time period (when OCCUPIED? is set to NO on theMAINSTAT display screen). The

Page 148

46Table 6 — Protective Safety Limits and Control SettingsMONITORED PARAMETER STATE LIMIT COMMENTSTemperature Sensors Out of Range260-270, 272,140, 141

Page 149

47Table 6 — Protective Safety Limits and Control Settings (cont)MONITORED PARAMETER STATE LIMIT COMMENTSLow Pressure 142OIL PRESSURE DELTA P < 18 P

Page 150

48Table 6 — Protective Safety Limits and Control Settings (cont)Default Screen Freeze — When the chiller is in analarm state, the default ICVC display

Page 151

49Ramp Loading — The ramp loading control slows downthe rate at which the compressor loads up. This control can pre-vent the compressor from loading u

Page 152

5ABBREVIATIONS AND EXPLANATIONSFrequently used abbreviations in this manual include:Words printed in all capital letters or in italics may beviewed on

Page 153

50Table 7 — Capacity OverridesOVERRIDE CONDITION (Configurable Override Paramter)FIRST STAGE SET POINT (Capacity Inhibit)SECOND STAGE SET POINT (Force

Page 154 - "OFF"

51The oil heater is always off during start-up or when thecompressor is running.The oil pump is also energized during the time the oil is be-ing heate

Page 155 - "OFF "

52Condenser Freeze Prevention — This control algo-rithm helps prevent condenser tube freeze-up by energizing thecondenser pump relay. The PIC II contr

Page 156

53SETPOINT (from the SETPOINT screen) and a Water/BrineReset value, if any. CONTROL POINT is limited to a minimumof 35 F (+1.7 C) for water, or 10 F (

Page 157

54the HOT GAS BYPASS/SURGE PREVENTION is off, thepoint must pass through the deadband region to the line deter-mined by the configured values before t

Page 158

55to the sum of HGBP ON DELTA T plus HGBP OFF DELTA TSee Fig. 26.The HGBP ON DELTA T must be set to a value largerthan the minimum delta T to which th

Page 159

56the graph (default settings are shown) describe a line the algo-rithm uses to determine the maximum lift of the compressor forthe particular maximum

Page 160

57system as a standby chiller to start up in case the lead or lagchiller in the system has shut down during an alarm conditionand additional cooling i

Page 161

58If the lead chiller is stopped in CCN mode for any reasonother than an alarm (*) condition, the lag and standby chillersare also stopped. If the con

Page 162

59CURRENT on the MAINSTAT screen) is less than thelead chiller percent capacity.NOTE: The use of AVERAGE LINE CURRENT or PER-CENT MOTOR KILOWATTS in t

Page 163

6 27 10 Q 19843Week of YearYear of ManufactureUnique NumberPlace of ManufactureMODEL NUMBER NOMENCLATURESERIAL NUMBER BREAKDOWNCooler Si

Page 164

60from another CCN device, or changed by other algorithms inthe PIC II control system.NOTE: The Ice Build steps do not occur if the chiller is config-

Page 165 - LEGEND FOR FIG. 69

61information on another device. Therefore, a CCN module mustbe attached when this screen is entered. To attach any CCN device, highlight it using the

Page 166

62This may be done for the local (table OCCPC01S), Ice Build(OCCPC02S), and/or CCN (OCCPC03S) schedule(s). If thechiller is on a CCN network, the acti

Page 167

63schedule. Select OVERRIDE, and set the desired overridetime.Another condition for start-up must be met for chillers thathave the REMOTE CONTACTS OPT

Page 168

64Shutdown Sequence — Chiller shutdown begins ifany of the following occurs:• the STOP button is pressed continuously for at least onesecond (the alar

Page 169

65BEFORE INITIAL START-UPJob Data Required• list of applicable design temperatures and pressures(product data submittal)• chiller certified prints• st

Page 170

66Table 10 — Bolt Torque Requirements, Foot Pounds2. If the pressure readings are abnormal for the chiller con-dition:a. Prepare to leak test chill

Page 171

67Fig. 32 — 19XR Leak Test Procedures

Page 172

68Table 11A — HFC-134a Pressure —Temperature (F)Table 11B — HFC-134a Pressure —Temperature (C)TEMPERATURE,FPRESSURE(psig)0 6.502 7.524 8.606 9.668 10.

Page 173

69Standing Vacuum Test — When performing thestanding vacuum test or chiller dehydration, use a manometeror a wet bulb indicator. Dial gages cannot ind

Page 174 - STATUS VPFSTAT

7341819 20 21 222331302928272625243233241235641112131615141779108Fig. 2 — Typical 19XR,XRV Components LEGEND1—Guide Vane Actuator2—Suc

Page 175

70Inspect Wiring1. Examine the wiring for conformance to the job wiring di-agrams and all applicable electrical codes.2. On low-voltage compressors (6

Page 176

71Use the instruction and service manual supplied by the start-er manufacturer to verify the starter has been installed correct-ly, to set up and cali

Page 177 - APPENDIX B — LEAD/LAG WIRING

72NOTE: The default CCN Occupied Schedule OCCPC03S isconfigured to be occupied (software versions 4.0 and later).Input Service Configurations — The fo

Page 178

73Table 12 — Job Site Parameters*With variable flow systems this point may be configured to the lower end ofthe range.NOTE: Other parameters: Screens

Page 179

74VFD Field Setup and VerificationUSING THE KEYPAD — The keypad display is used to mon-itor, view fault history and adjust the program of the VFDmicro

Page 180

75Press and keys to move through following parameters.*Vector control is not used in this configuration.Press softkey to select a parameter menu s

Page 181

766. Verify the conduit for the power wiring in securely con-nected to the VFD flanged cover and runs continuously tothe branch protection.7. Verify t

Page 182 - 1's

776. Press to the softkey to save changes when exitingthe ISM_CONF screeen.7. Press the softkey to and exit the ISM Configura-tion Screen.VFD Enable

Page 183

784. Calculate the line side error ratio using the followingequation:* in POWER screen.5. Shut down the chiller.6. If the Line Side Error Ratio is gre

Page 184

79To avoid unnecessary surge prevention, add about 10 psid(70 kPad) to P2 from these conditions:T4 = 10º F (5.5º C)P4 = 93 psid (642 kPad)Hand Calc

Page 185

8MOTOR AND OIL COOLING CYCLE The motor and the lubricating oil are cooled by liquid refriger-ant taken from the bottom of the condenser vessel (Fig. 3

Page 186 - — The LEDs indicate if the

80• Surge Line Speed Factor determines how much the surgeline moves to accommodate lower compressor speed. Ascompressor speed drops the ΔT values on t

Page 187 - Table G — Network Points List

812. If ACTUAL GUIDE VANE POSITION is still less than30 and step 1 failed, then increase the value of SURGELINE SHAPE FACTOR in steps of 0.01 up to 2

Page 188

82should be only one device on a CCN network which is desig-nated as the Time Broadcaster.ALARM ROUTING — This is in the table SERVICE–>EQUIPMENT C

Page 189

83GUIDE VANE ACTUATOR CALIBRATION — This auto-mated procedure is performed at the factory prior to new chillershipment. During this test, the CCM out

Page 190

84Increase the sensitivity of the flow switch by turning the ad-justment potentiometer clockwise until the yellow LED is lit.In case of nuisance trips

Page 191 - INITIAL START-UP CHECKLIST

85STORAGETANK LIQUIDVALVEOILSEPARATORPUMPOUTCONDENSERWATER SUPPLYAND RETURNPUMPOUTCONDENSERSTORAGE TANKVAPOR VALVE2345PRESSURERELIEF SAFETY VALVEPUMPO

Page 192 - CERTIFIED DRAWINGS)

86Table 16A — Refrigerant (HFC-134a) Charge with Compressor End Cooler Nozzles*Not used on 19XRV units.CodeEnglishMetric (SI)Machine Charge Machine Ch

Page 193

87Table 16B — 19XR Heat Exchanger Data — Drive End Entering Cooler Water*Not used on 19XRV units.CodeEnglishMetric (SI)Machine Charge Machine ChargeRe

Page 194

88TRIMMING REFRIGERANT CHARGE — The 19XRchiller is shipped with the correct charge for the design duty ofthe chiller. Trimming the charge can best

Page 195

89To Prevent Accidental Start-Up — A chiller STOPoverride setting may be entered to prevent accidental start-upduring service or whenever necessary. A

Page 196

9The oil pump suction is fed from the oil reservoir. An oilpressure relief valve maintains 18 to 25 psid (124 to 172 kPad)differential pressure in the

Page 197 - 0.1 to 3.0

90demand charge for the short period of high demand oper-ation. Pulldown rate can be based on load rate or temper-ature rate and is accessed on the EQ

Page 198 - 1 to 5 3

91REFRIGERATION LOG CARRIER 19XR HERMETIC CENTRIFUGAL REFRIGERATION MACHINEPlant MACHINE MODEL NO. MACHINE SERIAL NO. REFRIGERANT TYPE REMARKS: Indi

Page 199

92 Operating the Optional Pumpout Unit(Fig. 47) — Oil should be visible in the pumpout unit com-pressor sight glass under all operating condition

Page 200

93Transfer Refrigerant from Pumpout Storage Tank to Chiller1. Equalize refrigerant pressure.a. Turn on chiller water pumps and monitor chillerpressure

Page 201

94c. Equalize the refrigerant in the chiller cooler andcondenser.d. Turn off chiller water pumps and pumpout con-denser water supply.e. Turn on pumpou

Page 202

953. Transfer remaining refrigerant.a. Close valve 3.b. Open valve 2.c. Turn on pumpout condenser water.d. Run the pumpout compressor until the storag

Page 203

964. Rotate the guide vane sprocket fully clockwise andspot-drill the guide vane actuator shaft. Spot-drilling isnecessary when the guide vane actuato

Page 204

97Check Safety and Operating Controls Monthly —To ensure chiller protection, the automated Control Testshould be performed at least once per month. Se

Page 205 - CCN LOCAL RESET MENU

98As a minimum, the following maintenance is required.1. At least once a year, disconnect the vent piping at thevalve outlet and carefully inspect the

Page 206

99Periodically vacuum or blow off accumulated debris on theinternal parts with a high-velocity, low-pressure blower.Power connections on newly install

Comments to this Manuals

No comments