Carrier 19XRV Specifications Page 117

  • Download
  • Add to my manuals
  • Print
  • Page
    / 206
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 116
117
NOTE: If the cooler or condenser vessels are at
0 psig (0 kPa) or are open to atmospheric pressure, the
transducers can be calibrated for zero without remov-
ing the transducer from the vessel.
3. Access the HEAT_EX screen and view the particular
transducer reading (the EVAPORATOR PRESSURE or
CONDENSER PRESSURE parameter on the HEAT_EX
screen). To calibrate oil pressure or liquidside flow
device, view the particular reading (CHILLED WATER
DELTA P and CONDENSER WATER DELTA P on the
HEAT_EX screen, and OIL PUMP DELTA P on the
COMPRESS screen). It should read 0 psi (0 kPa). If the
reading is not 0 psi (0 kPa), but within ± 5 psi (35 kPa),
the value may be set to zero by pressing the
softkey while the appropriate transducer parameter is
highlighted on the ICVC screen. Then press the
softkey. The value will now go to zero. No high end
calibration is necessary for OIL PRESSURE DELTA P or
flow devices.
If the transducer value is not within the calibration
range, the transducer returns to the original reading. If
the pressure is within the allowed range (noted above),
check the voltage ratio of the transducer. To obtain the
voltage ratio, divide the voltage (dc) input from the
transducer by the TRANSDUCER VOLTAGE REF
supply voltage signal (displayed in CONTROL TEST
menu in the PRESSURE TRANSDUCERS screen) or
measure across the positive (+ red) and negative
(– black) leads of the transducer. For example, the
condenser transducer voltage reference is measured
at CCM terminals J2-4 and J2-6, the condenser trans-
ducer voltage input. The input to reference voltage
ratio must be between 0.80 and 0.11 for the software to
allow calibration. Pressurize the transducer until the
ratio is within range. Then attempt calibration again.
4. A high pressure point can also be calibrated between 25
and 250 psig (172.4 and 1723.7 kPa) by attaching a regu-
lated 250 psig (1724 kPa) pressure (usually from a
nitrogen cylinder). The high pressure point can be
calibrated by accessing the appropriate transducer param-
eter on the HEAT_EX screen, highlighting the parameter,
pressing the softkey, and then using the
or softkeys to adjust the
value to the exact pressure on the refrigerant gage. Press
the softkey to finish the calibration. Pressures at
high altitude locations must be compensated for, so the
chiller temperature/pressure relationship is correct.
The PIC II does not allow calibration if the transducer is too
far out of calibration. In this case, a new transducer must be in-
stalled and re-calibrated. If calibration problems are encoun-
tered on the OIL PRESSURE DELTA P channel, sometimes
swapping the compressor oil discharge pressure transducer and
the oil sump pressure transducer will offset an adverse trans-
ducer tolerance stack up and allow the calibration to proceed.
Control Algorithms Checkout Procedure — One
of the tables on the ICVC SERVICE menu is CONTROL AL-
GORITHM STATUS. The maintenance screens may be
viewed from the CONTROL ALGORITHM STATUS table to
see how a particular control algorithm is operating.
These maintenance screens are very useful in helping to de-
termine how the control temperature is calculated and guide
vane positioned and for observing the reactions from load
changes, control point overrides, hot gas bypass, surge preven-
tion, etc. The tables are:
Control Test — The Control Test feature can check all the
thermistor temperature sensors, pressure transducers, pumps
and their associated flow devices, the guide vane actuator, and
other control outputs such as tower fans, shunt trip relay, oil
heater, alarm relay, and hot gas bypass. The tests can help to
determine whether a switch is defective or a pump relay is not
operating, as well as other useful troubleshooting issues. Dur-
ing pumpdown operations, the pumps are energized to prevent
freeze-up and the vessel pressures and temperatures are dis-
played. The Pumpdown/Lockout feature prevents compressor
start-up when there is no refrigerant in the chiller or if the ves-
sels are isolated. The Terminate Lockout feature ends the
Pumpdown/Lockout after the pumpdown procedure is reversed
and refrigerant is added.
Control Modules
The ICVC and CCM modules perform continuous diagnos-
tic evaluations of the hardware to determine its condition.
Proper operation of all modules is indicated by LEDs (light-
emitting diodes) located on the circuit board of the ICVC and
CCM.
There is one green and one red LED located on the CCM
and ICVC boards.
RED LED (Labeled as STAT) — If the red LED:
blinks continuously at a 2-second interval, the module is
operating properly
SELECT
ENTER
SELECT
INCREASE
DECREASE
ENTER
CAPACITY Capacity
Control
This table shows all values used
to calculate the chilled water/brine
control point.
OVERRIDE Override
Status
Details of all chilled water control
override values.
SURG_PREV Surge/
HGBP
Status
The surge and hot gas bypass
control algorithm status is viewed
from this screen. All
values dealing with this control
are displayed.
HEAT_EX Heat
Exchanger
Points
Status
All sensor inputs and calculated
values related to the heat
Exchangers. Also some of the
surge control points are shown.
LL_MAINT LEAD/LAG
Status
Indicates LEAD/LAG operation
status.
OCCDEFCM Time
Schedules
Status
The Local and CCN occupied
schedules are displayed here to
help the operator quickly deter-
mine whether the schedule is in
the “occupied” mode or not.
WSMDEFME Water
System
Manager
Status
The water system manager is a
CCN module that can turn on the
chiller and change the chilled
water control point. This screen
indicates the status of this sys-
tem.
ISM_HIST ISM Alarm
History
Displays ISM values at last fault.
LOADSHED Loadshed
Status
Displays Loadshed (Demand
Limit) status.
CUR_ALARM Current
Alarm Status
Displays current chiller alarms.
SURGPREV Surge Pre-
vention Sta-
tus
Displays all information used or
supplied by the surge prevention
algorithm.
CAUTION
Turn controller power off before servicing controls. This
ensures safety and prevents damage to the controller.
Page view 116
1 2 ... 112 113 114 115 116 117 118 119 120 121 122 ... 205 206

Comments to this Manuals

No comments