118
is lit continuously, there is a problem that requires
replacing the module
is off continuously, the power should be checked
blinks 3 times per second, a software error has been dis-
covered and the module must be replaced
If there is no input power, check the fuses and circuit break-
er. If the fuse is good, check for a shorted secondary of the
transformer or, if power is present to the module, replace the
module.
GREEN LED (Labeled as COM) — These LEDs indicate
the communication status between different parts of the con-
troller and the network modules and should blink continuously.
Notes on Module Operation
1. The chiller operator monitors and modifies configura-
tions in the microprocessor by using the 4 softkeys and
the ICVC. Communications between the ICVC and the
CCM is accomplished through the SIO (Sensor Input/
Output) bus, which is a phone cable.
2. If a green LED is on continuously, check the communica-
tion wiring. If a green LED is off, check the red LED op-
eration. If the red LED is normal, check the module ad-
dress switches (SW1) (Fig. 52 and 53). Confirm all
switches are in OFF position.
All system operating intelligence resides in the ICVC.
Outputs are controlled by the CCM as well.
3. Power is supplied to the modules within the control panel
via 24-vac power sources.
The transformers are located within the power panels.
In the power panel, T1 supplies power to the compressor
oil heater, oil pump, and optional hot gas bypass, and T2
supplies power to both the ICVC and CCM.
T3 provides 24-v power to the optional modules.
Power is connected to Plug J1 on each module.
Chiller Control Module (CCM) (Fig. 53)
INPUTS — Each input channel has 2 or 3 terminals. Refer to
individual chiller wiring diagrams for the correct terminal
numbers for your application.
OUTPUTS Output is 24 vac. There are 2 terminals per out-
put. Refer to the chiller wiring diagram for your specific appli-
cation for the correct terminal numbers.
Integrated Starter Module (Fig. 54)
INPUTS Inputs on strips J3 through J6 are analog inputs
and J2 is discrete (on/off) input. The specific application of the
chiller determines which terminals are used. Refer to the indi-
vidual chiller wiring diagram for the correct terminal numbers
for your application.
OUTPUTS — Outputs are rated for 115-277 vac and wired to
strip J9. There are 2 terminals per output.
CCN INTERFACE
CONNECTION
SW1BACK OF CVC
MODULE PART NUMBER
SOFTWARE PART NUMBER
J7 SIO J1 POWER/
CCN
J8 SERVICE
ICVC
Fig. 52 — Rear of ICVC (International Chiller Visual Controller)
a19-1868