Table 7 — Capacity Overrides
OVERRIDE
CONDITION
(Configurable
Override
Paramter)
FIRST STAGE SET POINT
(Capacity Inhibit)
SECOND STAGE SET POINT
(Forced Capacity Decrease)
OVERRIDE
TERMINATION
View/Modify on
ICVC Screen
Override Default
Value
Configurable Range Value Value
High Condenser
Pressure (COND
PRESS
OVERRIDE)
SETUP1
CONDENSER
PRESSURE > 125
PSIG (862 kPa)
90 to 165 PSIG
(621 to 1138 kPa)
CONDENSER PRESSURE >
COND PRESS OVERRIDE + 2.4
PSIG (16.5 kPA)
CONDENSER PRES-
SURE < CON-
DENSER PRESS
OVERRIDE - 1 PSI
(6.9 kPa)
High Motor
Temperature
(COMP MOTOR
TEMP
OVERRIDE)
SETUP1
COMP MOTOR
WINDING TEMP >
COMP MOTOR
TEMP OVERRIDE
threshold but <=
COMP MOTOR
TEMP OVERRIDE
threshold +10° F
150 to 200 F
(66 to 93 C)
COMP MOTOR WINDING TEMP
> COMP MOTOR TEMP OVER-
RIDE + 10 F (5.6 C)
COMPR MOTOR
WINDING TEMP <
COMP MOTOR TEMP
OVERRIDE - 2 F
(1.1 C)
Low Evaporator
Temperature
(REFRIG
OVERRIDE
DELTA T)
SETUP1
CALC EVAP SAT
TEMP < EVAP
REFRIG TRIP-
POINT + 3 F(1.7 C)
2 to 5 F
(1.1 to 2.8 C)
CALC EVAP SAT TEMP < EVAP
SAT OVERRIDE TEMP - 1 F (0.6
C) NOTE: EVAP SAT OVERRIDE
TEMP = EVAP REFRIG TRIP-
POINT + REFRIG OVERRIDE
DELTA T
CALC EVAP SAT
TEMP > EVAP SAT
OVERRIDE TEMP +
2 F (1.1 C)
High
Compressor Lift
(Surge
Prevention)
(SURGE/HGBP
DELTA T,P)
OPTIONS
Min T1: 1.5 F (0.8 C)
Min P1: 50 PSID
(345 kPa) Max T4:
10 F (5.6 C) Max P4:
85 PSID (586 kPad)
With VFD enabled,
VFD SPEED must
be at maximum
0.5 - 2.0 F (0.3 - 1.1 C)
30 - 170PSID (207 -
1172 kPad) 0.5 - 20 F
(0.3 - 11.1 C) 50 - 170
PSId (345 - 1172 kPad)
None
ACTIVE DELTA T >
SURGE/HGBP DELTA
T + SURGE/HGBP
DEADBAND
High
Compressor Lift
(Surge
Prevention)
(Tsmin, IGVmin,
Tsmax, IGVmax,
Shapefac)
OPTIONS
Tsmain: 45 ^F
IGVmin: 5%
Tsmax: 70 ^F
IGVmax: 100%
shapefac: -0.04
0 to 150 ^F
0 to 110%
0 to 150 ^F
0 to 110%
-1 to 0
None
ActiveTsat < Surge-
Line Tsat + Dead-
band Setting
Manual Guide
Vane Target
(TARGET GUIDE
VANE POS)
COMPRESS Automatic 0 to 100% None
Press RELEASE soft-
key after selecting
TARGET GUIDE
VANE POS
Manual Speed
Control
(TARGET VFD
SPEED)
COMPRESS Automatic
VFD MINIMUM SPEED
to 100%
Forced TARGET VFD SPEED
cannot override either a capacity
inhibit or a capacity decrease
command generated by the PIC II
Press RELEASE soft-
key after selecting
TARGET VFD SPEED
Motor Load
(ACTIVE
DEMAND LIMIT)
MAINSTAT
AVERAGE LINE
CURRENT or
MOTOR PERCENT
KILOWATTS > 100%
40 to 100%
AVERAGE LINE CURRENT or
MOTOR PERCENT KILOWATTS
> ACTIVE DEMAND LIMIT + 5%
AVERAGE LINE CUR-
RENT or MOTOR
PERCENT KILO-
WATTS < ACTIVE
DEMAND LIMIT
Low Discharge
Superheat
OVERRIDE
ACTUAL SUPER-
HEAT < SUPER-
HEAT REQUIRED
for conditions
None
ACTUAL SUPERHEAT <
SUPERHEAT REQUIRED - 0.5 F
(0.3 C)
ACTUAL SUPER-
HEAT > SUPERHEAT
REQUIRED + 1 F
(0.56 C)