Press and keys to move through following parameters.
*Vector control is not used in this configuration.
Press softkey to select a parameter menu screen.
Press and keys to adjust the selected parameter.
Press the softkey until the PROGRAM LED
turns off to exit the program.
ACCESSING PASSWORD PROTECTED PARAME-
TERS Although the VFD controller has been preconfig-
ured as the factory, the user will need to be able to access the
parameters to verify the job specific parameters are correct,
tune the controller or correct a problem. The two passwords
protecting the VFD configuration are Parameter Set Display
(P.006) password and Program Disable (P.051) password. The
Parameter Set Display password restricts viewing. P.nnn pa-
rameters above 007 and all H.nnn and R.nnn screens. The pass-
word can be accessed at parameter P.006 and will switch be-
tween enabled and disabled each time the password 107 is en-
tered. The Program Disable password restricts the changing of
the drive parameter set. To enable or disable changes select pa-
rameter P.051 and enter the password 26.
NOTE: Some of the parameters can be changed only when the
drive is stopped.
See the Initial Start-Up Checklist section for VFD Job Spe-
cific Configuration table. For job specific parameters see inside
of the VFD enclosure door, next to the keypad. Refer to the
VFD Configuration table for the entire list of parameters.
NOTE: Restoring the default parameter P.050 will require all
the Carrier default parameters to be restored manually.
LABEL LOCATIONS Verify the following labels have
been installed properly and match the chiller requisition:
Surge Parameters — Located inside the chiller control
panel.
Chiller identification nameplate — Located on the right
side of the control panel. (See Fig. 35.)
VFD Parameter — Located to the right of the VFD con-
troller keypad on the VFD module.
VFD Enclosure Nameplate — Located on the right side
of the VFD as viewed from its front. (See Fig. 35.)
Record all nameplate information on the unit-mounted
VFD configuration sheet. (See page CL-14.)
DRIVE PROTECTION AND OTHER INCOMING
WIRING
1. Verify that the branch disconnects or other local discon-
nects are open and properly tagged out.
2. Verify that the branch circuit protection and AC input
wiring to the VFD are in accordance with NEC/CEC
(National Electrical Code/California Energy Commis-
sion) and all other local codes.
3. Verify that the fuses are per the field wiring diagram.
4. Verify that the incoming source does not exceed 85 kA.
5. Verify the power lugs in the VFD and branch protection
are properly secured. Inspect the ground cable and ensure
it is properly connected at the branch and to the ground
lug in the VFD.
P.nnn General Parameters
U.nnn Vector Control Parameters*
H.nnn Volts/Hertz Control Parameters
R.nnn RMI Remote Monitor Interface
Parameters
E.nnn Error Log (See fault codes)
CAUTION
Changing parameters may adversely affect chiller
operation.
WARNING
It is the operators responsibility to distribute access to the
passwords. Carrier is not responsible for unauthorized
access violations within the operators organization. Failure
to observe this warning could result in bodily injury.
ENTER
PROGRAM
SAFETY CODE CERTIFICATION
COMPRESSOR MOTOR DATA
R-
REFRIGERATION MACHINE
CARRIER CHARLOTTE
9701 OLD STATESVILLE ROAD
CHARLOTTE, NORTH CAROLINA 28269
MADE IN USA
PRODUCTION YEAR: 20XX
19XR05009801
A United Technologies Company
T
M
THIS UNIT IS DESIGNED,CONSTRUCTED,
AND TESTED IN CONFORMANCE WITH
ANSI/ASHRAE 15 (LATEST REVISION),
SPECIFICATION Z-415.
IN ACCORDANCE WITH CARRIER
AND OVERLOAD PROTECTION MUST BE
THE COMPRESSOR MOTOR CONTROLLER
REFRIGERATION.
SAFETY CODE FOR MECHANICAL
TEST PRESSURE
DESIGN PRESSURE
CLR.WATER PRESSURE
COND.WATER PRESSURE
PSI
PSI
PSI
PSI
KPA
KPA
KPA
KPA
CAZTREH/ESAHP/STLOV
RL AMPS
OLT AMPS
LR AMPS Y-
LR AMPS D-
MAX FUSE/CIRCUIT BKR
MIN. CIRCUIT AMPACITY
LBS.
CHARGED
KGS.REFRIGERANT
MODEL NUMBER
SERIAL NO.
MACHINE
COMP'R
COOLER
CONDENSER
ECON
STOR TANK
RATED iKW
RATED TONS
Fig. 35 — Machine Electrical Data Nameplates
VFD ENCLOSURE
NAMEPLATE
CHILLER ID NAMEPLATE — CONSTANT SPEED
CHILLER
a19-1881
a19-1882
a19-1883
CHILLER ID NAMEPLATE —
VFD-EQUIPPED CHILLER