Table 17 — ICVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
K. ISM ALARMS
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition.
[VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped. "Exceeded Limit" in Alarm or Alert messages may mean the value is above or
below a threshold
.
ICVC
FAULT
STATE
PRIMARY MESSAGE SECONDARY MESSAGE PRIMARY CAUSE
ADDITIONAL
CAUSE/REMEDY
200 PROTECTIVE LIMIT
1M CONTACT FAULT 200->1M Aux Contact Fault; Check 1M
Contactor and Aux
1M aux contact is open when it should be closed
during start or run mode. Confirm starter 1M aux
contact closes when ISM 1CR contact closes and
terminal J9-2 is energized with 115V. Check wiring
leading to ISM J2-9 and J2-10. Check MOTOR
RATED LOAD AMPS in ISM_CONF screen. Wye-
Delta Starters: Check for failed or incomplete tran-
sition. Check S-2M mechanical interlock operation.
201 PROTECTIVE LIMIT
2M CONTACT FAULT 201->2M Aux Contact Fault; Check 2M
Contactor and Aux
2M aux contact closure was delayed after 1M has
closed. Confirm starter 2M aux contact closes fol-
lowing the 1M aux contact closure and the starter
energizes the motor. Check wiring leading to ISM
J2-11 and J2-12. Check MOTOR RATED LOAD
AMPS and confirm that the correct STARTER
TYPE has been selected in the ISM_CONF
screen. Wye Delta Starters Only: Check wiring
from ISM J9-4 to transition contactor.
202 PROTECTIVE LIMIT
MOTOR AMPS NOT SENSED 202->Motor Amps Not Sensed — Aver-
age Line Current [VALUE]
The ISM has not sensed sufficient current for an
excessive delay after 1M has closed. Check the
MOTOR CURRENT CT RATIO and the MOTOR
RATED LOAD AMPS in the ISM_CONF screen.
Check VFD OPTION in SETUP 2 screen. Check
for wiring of current transformers to the J4 ISM ter-
minals. Check if main circuit breaker has tripped.
Check ISM_HIST screen
203 FAILURE TO START
EXCESS ACCELERATION TIME 203->Motor Acceleration Fault - Average
Line Current [VALUE]
Any line current remains high for an excessive time
duration following 1M aux and either 2M aux or
transition contact closure. Check that inlet guide
vanes are fully closed at start up. Check
ISM_HIST screen.
Check Motor Rated Load Amps in ISM_CONF
screen. Reduce condenser pressure if possible.
204 FAILURE TO STOP
1M/2M CONTACT FAULT 204->1M/2M Aux Contact Stop Fault;
Check 1M/2M Contactors and Aux
The 1M aux or 2M aux contacts are closed during
power up or the 1M aux or 2M aux contacts remain
closed for an excessive delay following a STOP
command. Check wiring and dry contacts leading
to ISM J2-9 and J2-10 and J2-11 and J2-12.
205 FAILURE TO STOP
MOTOR AMPS WHEN
STOPPED
205->Motor Amps When Stopped -
Average Line Current [VALUE]
High line current measured on any phase after
power up or STOP command. Check the MOTOR
CURRENT CT RATIO and the MOTOR RATED
LOAD AMPS in the ISM_CONF screen. Check
VFD OPTION in SETUP 2 screen. Check
ISM_HIST screen. Check for high inrush current
during power-up. Confirm that the starter de-ener-
gizes the motor when the ISM removes 115V from
ISM J9-2. Confirm that the correct STARTER
TYPE has been selected in the ISM_CONF
screen.
206 PROTECTIVE LIMIT
STARTER FAULT 206->Starter Fault Cutout; Check
Optional Starter Contacts
The ISM has received a start command and the
starter has declared a Fault. The dry contacts con-
nected to ISM J2-7 and J2-8 are open. See starter
display for starter Fault Code. For Benshaw Inc.
RediStart starters, view RediStart MICRO display.
For VFD, check VFD display Fault History. Clear
VFD faults with VFD keypad. For Allen-Bradley
wye delta starters with RLA >
718 A, the TR3 timer
may have expired as a result of a delayed transi-
tion.
207 PROTECTIVE LIMIT
HIGH CONDENSER PRESSURE 207->High Cond Pressure Cutout.
[VALUE] exceeded limit of [LIMIT]*
Check Compressor Discharge High Pressure
switch wiring and accuracy. Check for high con-
denser water temperatures, low water flow, fouled
tubes. Check for division plate/gasket bypass.
Check for noncondensables in refrigerant. If
[Value] is less that [Limit], the 1M aux contact was
open for an excessive time following a start com-
mand. Check High Pressure Relay contacts and
115 V wiring leading to ISM J9-1. Verify that 115
VAC is present on J9-1 with oil pump on. Check
115 V wiring leading from ISM J9-2 to the 1M aux
coil and base. Check for 115 VAC at 1M coil during
a startup attempt. Check the 24V circuit leading
from power panel terminal 50 to the 2C aux con-
tact and High Pressure Switch. Check the 24V cir-
cuit leading from power panel terminals 17 and 43
leading to the High Pressure Relay coil and base.
208 PROTECTIVE LIMIT
EXCESSIVE MOTOR AMPS 208->Average Line Current [VALUE]
exceeded limit of [LIMIT]*.
AVERAGE LINE CURRENT > 110% for an exces-
sive amount of time. Check MOTOR RATED LOAD
AMPS and MOTOR CURRENT CT RATIO in
ISM_CONF time. Check ISM_HIST screen. Check
for conditions that cause excessive lift. Check
guide vane actuator for proper operation. Confirm
that guide vanes will fully close prior to start-up.