Carrier 30GTR Specifications Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 84
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
Thermostatic Expansion Valves (TXV)
Model 30GTN,R040-110 units are available from the fac-
tory with conventional TXVs with liquid line solenoids. The
liquid line solenoid valves are not intended to be a mechani-
cal shut-off. When service is required, use the liquid line serv-
ice valve to pump down the system.
NOTE: This option is not available for modular units.
The TXV is set at the factory to maintain approximately
8 to 12° F (4.4 to 6.7° C) suction superheat leaving the cooler
by monitoring the proper amount of refrigerant into the cooler.
All TXVs are adjustable, but should not be adjusted unless
absolutely necessary. When TXV is used, thermistors T5,
T6, T7, and T8 are not required.
The TXV is designed to limit the cooler saturated suction
temperature to 55 F (12.8 C). This makes it possible for unit
to start at high cooler fluid temperatures without overload-
ing the compressor.
Compressor Protection Control System (CPCS)
or Control Relay(CR)
Each compressor has its own
CPCS module or CR. See Fig. 13 for CPCS module. The
CPCS or CR is used to control and protect the compressors
and crankcase heaters. The CPCS and CR provide the fol-
lowing functions:
compressor contactor control/crankcase heater
crankcase heater control
compressor ground current protection (CPCS only)
status communication to processor board
high-pressure protection
One large relay is located on the CPCS board. This relay
controls the crankcase heater and compressor contactor, and
also provides a set of signal contacts that the microprocessor
monitors to determine the operating status of the compres-
sor. If the processor board determines that the compressor is
not operating properly through the signal contacts, it will lock
the compressor off by deenergizing the proper 24-v control
relay on the relay board. The CPCS board contains logic that
can detect if the current-to-ground of any compressor wind-
ing exceeds 2.5 amps. If this condition occurs, the CPCS
shuts down the compressor.
Ahigh-pressure switch is wired in series between the MBB
and the CR or CPCS. On compressor A1 and B1 a loss-of-
charge switch is also wired in series with the high-pressure
switch. If the high-pressure switch opens during operation
of a compressor, the compressor will be stopped, the failure
will be detected through the signal contacts, and the com-
pressor will be locked off. If the lead compressor in either
circuit is shut down by the high-pressure switch, loss-of-
charge switch, ground current protector, or oil safety switch,
all compressors in that circuit are shut down.
NOTE: The CR operates the same as the CPCS, except the
ground current circuit protection is not provided.
Compressor Ground Current Protection Board
(CGF) and Control Relay (CR)
The 30GTN,R130-
210, and associated modular units (see Table 1) contain one
compressor ground current protection board (CGF) for each
refrigeration circuit. The CGF contains logic that can detect
if the current-to-ground of any compressor winding exceeds
2.5 amps. If this occurs, the lead compressor in that circuit
is shut down along with other compressors in that circuit.
Ahigh-pressure switch is wired in series between the MBB
and the CR or CPCS. On compressor A1 and B1 a loss-of-
charge switch is also included with the high-pressure switch.
The lead compressor in each circuit also has the CGF con-
tacts described above. If any of these switches open during
operation of a compressor, the CR relay is deenergized, stop-
ping the compressor and signaling the processor at the MBB-J9
inputs to lock out the compressor. If the lead compressor in
either circuit is shut down by high-pressure switch, com-
pressor ground fault, oil pressure switch, or the loss-of-
charge switch, all compressors in that circuit are also shut
down.
Fig. 13 Compressor Protection Control
System Module
15
Page view 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 83 84

Comments to this Manuals

No comments