MAJOR SYSTEM COMPONENTS
General
The 30GTN,R air-cooled reciprocating chill-
ers contain the ComfortLink™ electronic control system that
controls and monitors all operations of the chiller.
The control system is composed of several components as
listed in the sections below. See Fig. 1 for typical control
box drawing. See Fig. 2-4 for control schematics.
Main Base Board (MBB) See Fig. 5. The MBB is
the heart of the ComfortLink control system. It contains the
major portion of operating software and controls the opera-
tion of the machine. The MBB continuously monitors input/
output channel information received from its inputs and from
all other modules. The MBB receives inputs from ther-
mistors T1-T6, T9, and T10. See Table 2. The MBB also
receives the feedback inputs from compressors A1, A2, B1
and B2, and other status switches. See Table 3. The MBB
also controls several outputs. Relay outputs controlled by the
MBB are shown in Table 4. Information is transmitted be-
tween modules via a 3-wire communication bus or LEN (Lo-
cal Equipment Network). The CCN (Carrier Comfort Net-
work) bus is also supported. Connections to both LEN and
CCN buses are made at TB3. See Fig. 5.
Expansion Valve (EXV) Board The electronic
expansion valve (EXV) board receives inputs from ther-
mistors T7 and T8. See Table 2. The EXV board commu-
nicates with the MBB and directly controls the expansion
valves to maintain the correct compressor superheat.
CompressorExpansionBoard(CXB) The com-
pressor expansion board (CXB) receives the feedback in-
puts from compressorsA3, B3 andA4. See Table 3. The CXB
board communicates the status to the MBB and controls the
outputs for these compressors. The CXB board can also be
used as an accessory to control up to two field-installed ac-
cessory unloaders on 080-110, 130 (60 Hz), and 230B-315B
sizes.
ScrollingMarquee Display This device is the key-
pad interface used for accessing chiller information, reading
sensor values, and testing the chiller. The marquee display is
a 4-key, 4-character, 16-segment LED (light-emitting diode)
display. Eleven mode LEDs are located on the display as
well as an Alarm Status LED. See Marquee Display Usage
section on page 29 for further details.
Energy Management Module (EMM) The EMM
module is available as a factory-installed option or as a field-
installed accessory. The EMM module receives 4 to 20 mA
inputs for the temperature reset, cooling set point reset and
demand limit functions. The EMM module also receives the
switch inputs for the field-installed 2-stage demand limit and
ice done functions. The EMM module communicates the sta-
tus of all inputs with the MBB, and the MBB adjusts the
control point, capacity limit, and other functions according
to the inputs received.
Enable/Off/RemoteContactSwitch The Enable/
Off/Remote Contact switch is a 3-position switch used to
control the chiller. When switched to the Enable position the
chiller is under its own control. Move the switch to the Off
position to shut the chiller down. Move the switch to the
Remote Contact position and a field installed dry contact can
be used to start the chiller. The contacts must be rated for
dry circuit application capable of handlinga5vdc,1to
20 mA load. In the Enable and Remote Contact (dry con-
tacts closed) positions, the chiller is allowed to operate and
respond to the scheduling configuration, CCN configuration
and set point data. See Fig. 6.
Emergency On/Off Switch The Emergency On/
Off switch should only be used when it is required to shut
the chiller off immediately. Power to the MBB, EMM, CXB,
and marquee display is interrupted when this switch is off
and all outputs from these modules will be turned off. The
EXV board is powered separately, but expansion valves will
be closed as a result of the loss of communication with the
MBB. There is no pumpout cycle when this switch is used.
See Fig. 6.
Reset Button A reset button is located on the fuse/
circuit breaker panel for unit sizes 130-210 and associated
modules. The reset button must be pressed to reset either
Circuit Ground Fault board in the event of a trip.
BoardAddresses The Main Base Board (MBB) has
a 3-position Instance jumper that must be set to ‘1.’All other
boards have 4-position DIP switches. All switches are set to
‘On’ for all boards.
Control Module Communication
RED LED Proper operation of the control boards can be
visually checked by looking at the red status LEDs (light-
emitting diodes). When operating correctly, the red status LEDs
should be blinking in unison at a rate of once every 2 sec-
onds. If the red LEDs are not blinking in unison, verify that
correct power is being supplied to all modules. Be sure that
the Main Base Board (MBB) is supplied with the current
software. If necessary, reload current software. If the prob-
lem still persists, replace the MBB. A board LED that is lit
continuously or blinking at a rate of once per second or faster
indicates that the board should be replaced.
GREEN LED The MBB has one green LED. The Local
Equipment Network (LEN) LED should always be blinking
whenever power is on. All other boards have a LEN LED
which should be blinking whenever power is on. Check LEN
connections for potential communication errors at the board
J3 and/or J4 connectors. Communication between modules
is accomplished by a 3-wire sensor bus. These 3 wires run
in parallel from module to module. The J4 connector on the
MBB provides both power and communication directly to
the marquee display only.
YELLOW LED The MBB has one yellow LED. The
Carrier Comfort Network (CCN) LED will blink during times
of network communication.
Carrier Comfort Network (CCN) Interface The
30GTN,R chiller units can be connected to the CCN if de-
sired.The communication bus wiring is a shielded, 3-conductor
cable with drain wire and is supplied and installed in the
field. The system elements are connected to the communi-
cation bus in a daisy chain arrangement. The positive pin of
each system element communication connector must be wired
to the positive pins of the system elements on either side of
it. This is also required for the negative and signal ground
pins of each system element. Wiring connections for CCN
should be made at TB3. Consult the CCN Contractors Manual
for further information.
NOTE: Conductors and drain wire must be 20 AWG (Amer-
ican Wire Gage) minimum stranded, tinned copper. In-
dividual conductors must be insulated with PVC, PVC/
nylon, vinyl, Teflon, or polyethylene.An aluminum/polyester
100% foil shield and an outer jacket of PVC, PVC/nylon,
chrome vinyl, or Teflon with a minimum operating tem-
perature range of −20 C to 60 C is required. Wire manu-
factured byAlpha (2413 or 5463),American (A22503), Belden
(8772), or Columbia (02525) meets the above mentioned
requirements.
3