Table 27 Alarm and Alert Codes (cont)
ALARM/
ALERT
CODE
ALARM
OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM
GENERAED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
112 Alert Circuit A High Suction
Superheat
If EXV is greater than
98%, suction superheat is
greater than 75 F (41.7 C)
and saturated suction tem-
perature is less than MOP
for 5 minutes
Circuit A shutdown
after pumpdown
complete.
Manual Faulty expansion valve
or EXV board, low re-
frigerant charge,
plugged filter drier,
faulty suction gas ther-
mistor (T7) or cooler
thermistor (T5).
113 Alert Circuit B High Suction
Superheat
If EXV is greater than
98%, suction superheat is
greater than 75 F (41.7 C)
and saturated suction tem-
perature is less than MOP
for 5 minutes
Circuit B shutdown
after pumpdown
complete.
Manual Faulty expansion valve
or EXV board, low re-
frigerant charge,
plugged filter drier,
faulty suction gas ther-
mistor (T8) or cooler
thermistor (T6).
114 Alert Circuit A Low Suction
Superheat
If EXV is greater than
10%, and either suction
superheat is less than
19 F (10.6 C) or saturated
suction temperature is
greater than MOP for
5 minutes
Circuit A shutdown
after pumpdown
complete.
Automatic restart
after first daily
occurrence. Manual
restart thereafter.
Faulty expansion valve
or EXV board, faulty
suction gas thermistor
(T7) or cooler ther-
mistor (T5).
115 Alert Circuit B Low Suction
Superheat
If EXV is greater than
10%, and either suction
superheat is less than
19 F (10.6 C) or saturated
suction temperature is
greater than MOP for
5 minutes
Circuit B shutdown
after pumpdown
complete.
Automatic restart
after first daily
occurrence. Manual
restart thereafter.
Faulty expansion valve
or EXV board, faulty
suction gas thermistor
(T8) or cooler ther-
mistor (T6).
116 Alert Circuit A Low Cooler
Suction Temperature
1. If the saturated suction
temperature is 24 to
29° F (13.3 to 16.1° C)
below cooler LWT and
is also F (1.1° C)
less than freeze*
2. If the saturated suction
temperature is 30° F
(16.7° C) below cooler
LWT and is also F
(1.1° C) less than
freeze* for 10 minutes
1. Mode 7 initiated.
No additional
capacity in-
creases. Alert
not tripped.
2. Circuit shutdown
without going
through pump-
down.
1. Automatic reset
if corrected.
2. Manual
Faulty expansion valve
or EXV board, low re-
frigerant charge,
plugged filter drier,
faulty suction gas ther-
mistor (T7) or cooler
thermistor (T5), low
cooler fluid flow.
117 Alert Circuit B Low Cooler
Suction Temperature
1. If the saturated suction
temperature is 24 to
29° F (13.3 to 16.1° C)
below cooler LWT and
is also F (1.1° C)
less than freeze*
2. If the saturated suction
temperature is 30° F
(16.7° C) below cooler
LWT and is also F
(1.1° C) less than
freeze* for 10 minutes
1. Mode 8 initiated.
No additional
capacity in-
creases. Alert
not tripped.
2. Circuit shutdown
without going
through pump-
down.
1. Automatic reset
if corrected.
2. Manual
Faulty expansion valve
or EXV board, low re-
frigerant charge,
plugged filter drier,
faulty suction gas ther-
mistor (T8) or cooler
thermistor (T6), low
cooler fluid flow.
118 Alert Circuit A Low Oil
Pressure
Oil pressure switch open
after 1 minute of continu-
ous operation
Circuit shutdown
without going
through pumpdown.
Manual Oil pump failure, low
oil level, switch failure
or compressor circuit
breaker tripped.
119 Alert Circuit B Low Oil
Pressure
Oil pressure switch open
after 1 minute of continu-
ous operation
Circuit shutdown
without going
through pumpdown.
Manual Oil pump failure, low
oil level, switch failure
or compressor circuit
breaker tripped.
LEGEND
CCN Carrier Comfort Network
CPCS Compressor Protection Control System
CXB Compressor Expansion Board
EMM Energy Management Module
EXV Electronic Expansion Valve
FSM Flotronic™ System Manager
MBB Main Base Board
MOP Maximum Operating Pressure
WSM Water System Manager
*Freeze is defined as 34° F (1.1 C) for water. For brine fluids, freeze
is CSP.1 −8° F (4.4 C) for single set point and lower of CSP.1/CSP.2
−8° F (4.4 C) for dual set point configuration.
NOTE: The following table shows illegal configurations:
1 Zero compressors in a circuit
2 Four compressors in a circuit with two unloaders
3
Four compressors in a circuit with one unloader and hot gas
bypass
4 Two unloaders and hot gas bypass in a circuit.
5 More than one compressor quantity difference between circuits
6 Fluid type of low temperature brine
7
Air cooled head pressure control with common fan staging and
different head pressure control methods for each circuit.
49