Insulate Motor Terminals and Lead Wire Ends
Insulate compressor motor terminals, lead wire ends, and electrical wires to prevent moisture
condensation and electrical arcing. For low-voltage units (up to 600 v), obtain insulation
material from machine shipping package consisting of 3 rolls of insulation putty and one roll of
vinyl tape.
1. Insulate each terminal by wrapping with one layer of insulation putty.
2. Overwrap putty with 4 layers of vinyl tape.
High Voltage Units
High-voltage units require special terminal preparation. Follow local electrical codes for high-
voltage installation. The vinyl tape is not acceptable, a high voltage terminal methods must be
used.
Connect Power Wires to Oil Pump Starter
See Figure 28. Connect power wires to oil pump starter mounted in machine power panel.
Use separate fused disconnect or circuit breaker as shown on job wiring diagrams and
Figure 27. Check that power supply voltage agrees with oil pump voltage. Follow correct
phasing for proper motor rotation.