
103
Service Access —
All unit components can be reached
through clearly labeled hinged access doors. These doors are
not equipped with tiebacks, so if heavy duty servicing is need-
ed, either remove them or prop them open to prevent accidental
closure.
Each door is held closed with 3 latches. The latches are se-
cured to the unit with a single
1
/
4
-in. –20 x
1
/
2
-in. long bolt. See
Fig. 111.
To open, loosen the latch bolt using a
7
/
16
-in. wrench. Pivot
the latch so it is not in contact with the door. Open the door. To
shut, reverse the above procedure.
NOTE: Disassembly of the top cover may be required under
special service circumstances. It is very important that the ori-
entation and position of the top cover be marked on the unit
prior to disassembly. This will allow proper replacement of the
top cover onto the unit and prevent rainwater from leaking into
the unit.
COMPRESSORS
Sizes 030-050
— Access to the compressors is through the
doors on the condenser end of the unit. This door also provides
access to the discharge and suction service valves, the crank-
case heaters, and the high- and low-pressure switches. Com-
pressor no. 1 is always the compressor on the left when facing
main control box.
Sizes 055-105
— The oil pump end (compressor access) of
each compressor is readily accessible from sides of unit as shown
in Fig. 112. Access the motor end of the compressor through the
condenser end of the unit or by removing compressor.
LIQUID SERVICE VALVES, FILTER DRIERS, AND
SIGHT GLASSES
Sizes 030-050
— Access to these components is through the
access panel on the right side of the unit. See Fig. 112. There is
also a Schrader port in each suction line that is accessible
through this same panel. When charging unit, route service line
through the round holes and replace panel to minimize air
bypass.
Sizes 055-105
— Access to these components is from the side
of the unit as shown in Fig. 112.
SUPPLY-FAN MOTORS, PULLEYS, AND BELTS — Ac-
cess to these components is through the 2 doors labeled FAN
SECTION on each side of the unit.
POWER EXHAUST MOTORS, PULLEYS, AND BELTS —
Access to these components is through the door below the side
economizer hoods on both sides of the unit. See Fig. 113 and
114.
RETURN AIR FILTERS — Access to these filters is through
the door marked FILTER SECTION on the right side of the
unit.
UNIT CONTROL BOX — Access to this component is
through the doors marked ELECTRICAL SECTION on the
condenser end of the unit (when facing the condenser coil).
GAS HEAT SECTION — Access to the gas heat section is
through the door labeled HEAT SECTION on the right side of
the unit (when facing return air end). See Fig. 115 and 116.
All gas system components are in the gas section.
MAIN BURNERS — At the beginning of each heating sea-
son, inspect for deterioration due to corrosion or other causes.
Observe the main burner flames and adjust if necessary. See
Gas System Adjustment section on page 111.
FLUE GAS PASSAGEWAYS — The flue collector box
and heat exchanger cells may be inspected by removing
heat exchanger access panel (Fig. 15-23), flue box cover,
and main burner assembly (Fig. 117). Refer to Main Burn-
ers section on page 111 for burner removal sequence. If
cleaning is required, remove heat exchanger baffles and
clean tubes with a wire brush.
Use caution with ceramic heat exchanger baffles. When in-
stalling retaining clip, be sure the center leg of the clip extends
inward toward baffle. See Fig. 118.
COMBUSTION-AIR BLOWERS — Clean periodically to
assure proper airflow and heating efficiency. Inspect blower
wheel every fall and periodically during heating season. For
the first heating season, inspect blower wheel bi-monthly to
determine proper cleaning frequency.
To inspect blower wheel, remove heat exchanger access
panel. Shine a flashlight into opening to inspect wheel. If clean-
ing is required, remove motor and wheel assembly by remov-
ing screws holding motor mounting plate to top of combustion
fan housing (Fig. 119). The motor and wheel assembly will
slide up and out of the fan housing. Remove the blower wheel
from the motor shaft and clean with a detergent or solvent. Re-
place motor and wheel assembly.
ECONOMIZER DAMPER MOTOR — On units so equipped,
the economizer motor is located in the mixing box section. Ac-
cess to it is through the door labeled FILTER SECTION on the
right-hand side of the unit.
CONDENSER FANS AND FAN MOTORS — Remove the
wire fan guard on top of the unit to gain access to the condenser
fans and motors.
INLET GUIDE VANE MOTOR — The inlet guide vane mo-
tor is located on the evaporator-fan sled on the side opposite the
fan motor. See Fig. 120A and 120B. Access is through the door
labeled FAN SECTION on the left side of the unit.
25% OUTDOOR-AIR DAMPER — Access to adjust the
damper is through the hoods. Remove filters to gain access into
unit to adjust linkage arms.
IMPORTANT: After servicing is completed, make sure
door is closed and relatched properly, and that the
latches are tight. Failure to do this can result in water
leakage into the indoor-air section of the unit.
R
un Status
S
ervice T
est
T
em
perature
s
P
re
ssures
Setpo
ints
Inputs
O
u
tputs
Co
nfiguration
T
im
e C
lock
O
pera
ting M
od
es
A
la
rm
s
ENTER
ESC
M
ODE
Alarm Status
NAVIGATOR
™
ComfortLink
Fig. 110 — Accessory Navigator™ Display
Comments to this Manuals