Table 8 — Electrical Data, 48ZA,ZE,ZJ035 Units
LEGEND NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors
rated at 0.3 FLA each.
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPR
NO. 1
COMPR
NO. 2
OFM IFM
BASE UNIT
ONLY
EXHAUST
FAN
BASE UNIT WITH
EXHAUST FAN
RLA LRA RLA LRA
Total
FLA
Hp FLA MCA MOCP
Total
Hp
Total
FLA
MCA MOCP
208/230
187-254 53.2 266 69.2 345 13.2
7.5 24.2/22.0 177.1/174.9 225/225
6 21.2/20.0 198.3/194.1 250/250
10 33.4/30.0 210.5/205.3 250/250
15 48.4/44.0 225.5/218.9 250/250
10 30.8/28.0 183.7/180.9 250/250
6 21.2/20.0 204.9/200.1 250/250
10 33.4/30.0 217.1/211.3 250/250
15 48.4/44.0 232.1/224.9 300/250
15 46.2/42.0 199.1/194.9 250/250
6 21.2/20.0 220.3/214.1 250/250
10 33.4/30.0 232.5/225.3 300/250
15 48.4/44.0 247.5/238.9 300/300
20 59.4/54.0 212.3/206.9 250/250
6 21.2/20.0 233.5/226.1 300/250
10 33.4/30.0 245.7/237.3 300/300
15 48.4/44.0 260.7/250.9 300/300
25 74.8/68.0 229.1/220.9 300/250
6 22.0/20.0 250.3/240.1 300/300
10 34.0/30.0 262.5/251.3 300/300
15 48.0/44.0 277.5/264.9 350/300
460
414-508 28.8 120 34.6 173 6.6
7.5 11.0 89.7 110
6 9.6 99.3 125
10 15.2 104.9 125
15 22.0 111.7 125
10 14.0 92.7 125
6 9.6 102.3 125
10 15.2 107.9 125
15 22.0 114.7 125
15 21.0 99.7 125
6 9.6 109.3 125
10 15.2 114.9 125
15 22.0 121.7 150
20 27.0 105.7 125
6 9.6 115.3 125
10 15.2 120.9 150
15 22.0 127.7 150
25 34.0 112.7 125
6 9.6 122.3 150
10 15.2 127.9 150
15 22.0 134.7 150
575
518-632 23.1 96 26.7 120 4.8
7.5 9.0 70.3 90
6 7.8 78.1 100
10 12.2 82.5 100
15 18.0 88.3 110
10 11.0 72.3 90
6 7.8 80.1 100
10 12.2 84.5 110
15 18.0 90.3 110
15 17.0 78.3 100
6 7.8 86.1 110
10 12.2 90.5 110
15 18.0 96.3 110
20 22.0 83.3 100
6 7.8 91.1 110
10 12.2 95.5 110
15 18.0 101.3 125
25 27.0 88.4 110
6 7.8 96.2 110
10 12.2 100.6 125
15 18.0 106.4 125
FLA
Full Load Amps
Hp
Nominal Horsepower
IFM
Indoor (Supply) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps (for wire sizing)
MOCP —
Maximum Overcurrent Protection
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
Page view 43